HVACR: Walk In Refrigerator ELECTRICAL HAZARD Repair and Upgrade (Walk In Refrigerator hack job)

Поделиться
HTML-код
  • Опубликовано: 4 окт 2024
  • HVACR: Commercial walk In Refrigerator Not Cooling & Repair (Walk In Beer Cooler Control Upgrade) HVACR: HVACR: Water Source Refrigerator Not Cooling(Tecumseh Compressor Not Starting/Tripping Breaker) HVACR Emergency: Commercial Refrigeration Rack System Nightmare (Refrigerator Not Cooling) Refrigeration Rack System Troubleshooting / Refrigeration Rack System Training / Refrigeration Rack System Keeps Tripping Breaker / Refrigeration Rack System Not Getting Cold / HVACR Service Call: Commercial Wine Cooler Not Cooling (Breaker Keeps Tripping) Water Source Refrigerator With High Head Pressure Tripping On Pressure Control / HVAC Troubleshooting / HVACR Troubleshooting / Remote Condenser / Split System Refrigerator / Refrigerator Compressor Not Starting / Refrigerator Compressor Not Working / Refrigerator Not Cooling / Refrigerator Not Working / Refrigerator Not Blowing Cold Air / Refrigerator High Side Pressure Too High / Commercial Refrigeration / Commercial Refrigerator / Cooler Repair / Cooler Troubleshooting / Beer Cooler Repair / Wine Cooler Repair / Walk In Refrigerator / Walk In Freezer / Refrigerator High Head Pressure / Refrigerator High Pressure Control / Refrigerator Low Pressure Control / Refrigerator Dual Pressure Control /Refrigeration Emergency Service Call (Walk In Refrigerator Not Cooling/Walk In Refrigerator Not Working) Beer Cooler Not Working/Compressor Not Starting/Working/How To Check Compressor/How To Check Run Capacitor/How To Check Start Capacitor/Commercial Refrigeration/Walk In Cooler Troubleshooting / Compressor Replacement #HVAC #HVACR #REFRIGERATION #jumpermantech
    GoPro HERO8 Black (Camera Used In This Video)
    amzn.to/3q4FmEz
    Veto Pro Pac TECH MC
    amzn.to/3gURJyZ
    Fluke 902 FC HVAC True-RMS Clamp Meter
    amzn.to/39wvwiK​​
    Fieldpiece ADK7 Deluxe Silicone Test Lead Kit
    amzn.to/3VNYXDv
    Klein Tools ET600 Megohmmeter Insulation Tester
    amzn.to/409iNvu
    Supco M500 Insulation Tester/Electronic Megohmmeter
    amzn.to/42oy0ua
    Fluke 1AC-A1-II VoltAlert Non-Contact Voltage Tester
    amzn.to/3FcWElQ
    Fieldpiece JL3KR4 HVACR Charge Kit (Digital Gauges/Probes)
    amzn.to/3E4W0Fr
    Fieldpiece SPK2 Folding Pocket In-Duct Thermometer
    amzn.to/3mi8Fih
    Fieldpiece SPK3 Folding ROD Dual Temperature Thermometer
    amzn.to/3FbDufQ
    Milwaukee M12 2-Tool Combo Kit 2598-22
    amzn.to/3CtCRNC
    Milwaukee Cut 1 Dipped GLOVES L
    amzn.to/3s8H18O​
    Milwaukee 2351-20 M12 LED Stick Light
    amzn.to/3rVJKEK
    Milwaukee 48-22-1985 Fastback Hawk Bill Folding Knife
    amzn.to/3e53ygW
    Milwaukee 48-22-1500 Fastback Compact Folding Utility Knife
    amzn.to/3qazJkC
    Milwaukee 48-22-4041 Iron Carbide Core Large-Looped Jobsite Scissors
    amzn.to/32fxC6I
    Milwaukee 4932459097 Billet Torpedo Level
    amzn.to/30Dh6Nw
    Milwaukee Wide Blade Magnetic Tape Measure 16 FT
    amzn.to/3yEN7kL
    Milwaukee Fine Pt. Markers Black
    amzn.to/3e4fH5W
    Streamlight 66604 MicroStream USB 250-Lumen Rechargable Pocket Flashlight
    amzn.to/320XiEF
    Klein Tools 11-in-1 Screwdriver / Nut Driver
    amzn.to/3s3o8ql
    Klein Tools 32561 Multi-Bit Screwdriver / Nut Driver 6-in-1
    amzn.to/3e4ur4x
    Klein Tools 32807MAG 7-in-1 Nut Driver, Magnetic Driver
    amzn.to/321n4bW
    Klein Tools 600-4 1/4-Inch Keystone Cushion-Grip Screwdriver
    amzn.to/3J11hS1
    Klein Tools 32581 4-in-1 Electronics Screwdriver Set
    amzn.to/3yEj3WC
    Klein Tools LLK12 L-Style Hex Key Caddy Set 12-Piece (Metric/Sae)
    amzn.to/3yRUiGJ
    Yellow Jacket 18975 Charge Tool
    amzn.to/3J4pfvJ
    Yellow Jacket 60613 Service ratchet Wrench
    amzn.to/3E8iYeZ
    Yellow Jacket 19173 5/16" Female Quick Couplers x 1/4" Male Flare
    amzn.to/3q0TQ4M
    Cooper Bussmann BP-FP-2 Cartridge Carded Fuse Puller
    amzn.to/3e0USrY
    Crescent 2 Pc. X6 4-in-1 Black Oxide Spline Ratcheting SAE Wrench Set
    amzn.to/3qqKlw7
    Crescent 4" Adjustable Cushion Grip Wrench
    amzn.to/3J4qsmL
    Knipex 09 08 240 SBA 9.5-Inch Insulated Ultra-High Leverage Lineman's Pliers (1000v)
    amzn.to/30EQmw5
    Knipex 09 11 240 9.5-Inch Ultra-High Leverage Lineman's Pliers with Fish Tape Puller and Crimper
    amzn.to/3H9iYAu
    KNIPEX Tools - Long Nose Pliers With Cutter, 1000V Insulated
    amzn.to/3e3IEi7
    KNIPEX Tools - Long Nose Pliers With Cutter
    amzn.to/3gUSE2i
    KNIPEX Tools 98 62 02, Flat Nose Plastic Pliers 1000V Insulated
    amzn.to/3p6lFsZ
    KNIPEX - 74 08 200 - High Leverage Diagonal Cutters, 1000V Insulated
    amzn.to/3mh8K5U
    KNIPEX - 74 01 200 Tools - High Leverage Diagonal Cutters
    amzn.to/3F1VScb
    KNIPEX Tools - Cobra QuickSet Pump Pliers, 1000V Insulated
    amzn.to/3sftr5Q
    KNIPEX Tools 3 Piece Cobra Pliers Set
    amzn.to/3FbRwy7
    KNIPEX Tools Pliers Wrench 3-Piece Set
    amzn.to/3nnRLfW

Комментарии • 38

  • @mxslick50
    @mxslick50 5 дней назад +5

    You could have just attached the BX to the stat wire at the condenser end and use it as a pull rope to get to the box instead of all the fussing with a fish tape. It would have taken less that a minute and a half to pull that over, and no moving ladders all over the place.

    • @ronnym1977
      @ronnym1977 4 дня назад +1

      I agree with that one.

  • @ronnym1977
    @ronnym1977 5 дней назад +1

    Nice work JMT.
    You cleaned that mess up real good!

  • @chris66b55
    @chris66b55 5 дней назад +4

    In refrigeration the switch should always be upside down. Installed that way it can’t vibrate and turn itself off.

    • @sherwinalvarez7365
      @sherwinalvarez7365 5 дней назад +2

      Makes sense although I have never seen this in practice or vibrating off.

    • @chris66b55
      @chris66b55 5 дней назад

      @@sherwinalvarez7365 I’ve seen toggles where the spring had worn out so bad it wouldn’t stay in the up position. I can’t remember seeing many mounted in a normal fashion, the one I found was the one that couldn’t stay “On”. Supermarkets, Commissaries, never seen it. Maybe convenience stores are installed with the switch in the normal orientation, or places with overzealous inspectors.

  • @Eddy63
    @Eddy63 5 дней назад +1

    Once again , a beautiful thing ... Thx

  • @zekenzy6486
    @zekenzy6486 5 дней назад +1

    Great video. Thank you for sharing

  • @stevencossaboon3237
    @stevencossaboon3237 5 дней назад +1

    Nice work Jumper Man. It's amazing what you find out there.

  • @johnwalker890
    @johnwalker890 5 дней назад +1

    Putting a relay or contactor on the solenoid circuit to energize it with the thermostat, might work, the coil on the relay has to be rated for 208 volts and the contacts have to be rated 120 volts for the solenoid circuit, to only run when the thermostat energizes the evaporator circuit, just my opinion, I'm sure someone will come up with a negative response, someone always does??? Good job Jumper............

    • @mxslick50
      @mxslick50 4 дня назад

      @@johnwalker890 It's not a bad idea at all. The problem is using low voltage tstat wire on anything higher than 24 volts. It is not rated or agency listed for such use and is a serious shock and fire hazard. A relay using tstat wire on 120 or 208, coil or load, is still wrong and a hazard.

    • @tomoliver8498
      @tomoliver8498 3 дня назад +1

      Could have installed a 24 volt transformer and relay in the condensing unit and continue to use the low voltage wire. I am about to do the same to shut a cooler condensing unit off while the store is closed for one of my customers.

    • @johnwalker890
      @johnwalker890 3 дня назад

      @@tomoliver8498 Correct........

  • @richardwoodwards1202
    @richardwoodwards1202 5 дней назад +1

    Great job 👍

  • @thesilentonevictor
    @thesilentonevictor 6 дней назад +2

    Madness low voltage wire for high voltage well at list it will be fix professionally

    • @sherwinalvarez7365
      @sherwinalvarez7365 5 дней назад +2

      Oh? That's not code?

    • @mxslick50
      @mxslick50 4 дня назад

      @@sherwinalvarez7365 Using low voltage wire is most certainly not Code. Low voltage wires' insulation is too thin for high voltage use, and it is, in most cases, not rated for temperatures over 40deg. C ( high voltage wire is 75 or 90 deg C or higher) so even a modest overload will melt low voltage wire.
      tldr: Never use low voltage wire on 120 or higher regardless of how little current.

    • @sherwinalvarez7365
      @sherwinalvarez7365 3 дня назад +1

      ​@mxslick50 I was being sarcastic, but thanks all the same. Excellent explanation. Not being sarcastic btw.

  • @ericc2233
    @ericc2233 6 дней назад +1

    What Camera are you using......Clear picture?

  • @itsprimetime9865
    @itsprimetime9865 5 дней назад +3

    the gauge of the wire shouldn't matter since is cutting off the contactor coil but 18 is a bit Low 14-16 gauge is just fine

    • @mxslick50
      @mxslick50 5 дней назад +2

      It's not the gauge in this case, thermostat wire is NOT rated or sufficiently insulated for 208 volts.

    • @itsprimetime9865
      @itsprimetime9865 5 дней назад +2

      @@mxslick50 thats true But without a Load on the wire it would never over heat but again yeah Thermostat wire is a no no

    • @mxslick50
      @mxslick50 4 дня назад

      @@itsprimetime9865 Oh it will overheat like a toaster element if it shorts or grounds out to the box. Never say never when it comes to electrical stupidity.

    • @itsprimetime9865
      @itsprimetime9865 4 дня назад

      @@mxslick50 it's on a contactor coil......

    • @mxslick50
      @mxslick50 4 дня назад

      @@itsprimetime9865 That makes absolutely no difference! It is fed 208 directly off the incoming power which will be fused/breakered at a minimum of 15 amps which if grounded or shorted out will smoke that wire in no time. The current the contactor coil draws is within what the wire can handle but that was not the issue here.

  • @terryh8421
    @terryh8421 5 дней назад

    Good video.

  • @ILoveKittys78
    @ILoveKittys78 5 дней назад

    😻💚💜💚

  • @andykuehner2772
    @andykuehner2772 5 дней назад +1

    You didn't need to run the BX just use the 120v to power the tstat and tge solenoid to use the pump down

    • @mxslick50
      @mxslick50 4 дня назад

      @@andykuehner2772 You still can't use tstat wire on 120v. Don't be so dense.

    • @tomoliver8498
      @tomoliver8498 3 дня назад

      There would be no need for any wire between the condensing unit and evaporator if he had just installed a 120 volt coil on the solenoid and powered everything from the 115 volt fan circuit. He clearly doesn't understand the proper way to set up a pump down system... He left the solenoid powered on all the time.

  • @justinhayward5027
    @justinhayward5027 5 дней назад

    Yoyoyo

  • @michaelpaulsen64
    @michaelpaulsen64 5 дней назад

    Don’t smash those bottles of booze how did you like? Working around all those booze bottles