Analog Scaling Concept in PLC || Part #1 || PLC Programming Tutorials for Beginners

Поделиться
HTML-код
  • Опубликовано: 16 ноя 2024

Комментарии • 40

  • @nathanmatthews8172
    @nathanmatthews8172 3 года назад +10

    The calculation should be 4 - 20ma not 0 - 20ma. If you're reading anything less than 4ma at the sensor that indicates a problem.

  • @athilaldurry5880
    @athilaldurry5880 3 года назад +1

    Good

  • @bhagwatprasad4088
    @bhagwatprasad4088 2 года назад

    usefull video good sir

  • @umargul5644
    @umargul5644 2 года назад

    Well done

  • @PINOYTECHMARLON
    @PINOYTECHMARLON 3 года назад

    Nice sir waiting for next video

    • @easyplc
      @easyplc 3 года назад +1

      Next video will be proper scaling with calibration option also .... in process

  • @chappagiridhar5109
    @chappagiridhar5109 3 года назад

    Nice sir

  • @eakubhosen2339
    @eakubhosen2339 2 года назад

    Thank you sir

  • @robertojrcruz8506
    @robertojrcruz8506 3 года назад

    Thank you for this sir very helpful

  • @NoumanOfficialVLOGS
    @NoumanOfficialVLOGS 3 года назад

    very nice work bro

  • @satyanarayanareddy6414
    @satyanarayanareddy6414 3 года назад +1

    Our plant used rice husk hopper bottom RAL and pumping blower all red used VFDs blower back pressure also given Siemens plc, using above parameters how to calculate given my plc TPH

  • @vaseemsaifi613
    @vaseemsaifi613 3 года назад

    Waiting for next upload...

    • @toke7342
      @toke7342 3 месяца назад

      Still waiting?

  • @TopAhmed1
    @TopAhmed1 3 года назад +1

    Shouldn't we must use 0-27648 to compensate for over-range and under-range values?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад +1

      it depends on how much resolution for ADC. it may be 8 bit , ten bit , 13 bit or 16 bits

  • @catalinpanait6954
    @catalinpanait6954 3 года назад

    nice job,keep going

  • @firashamdan4175
    @firashamdan4175 2 года назад

    thanks

  • @pranitdupare2788
    @pranitdupare2788 8 месяцев назад +1

    Sir invt plc raw count is 32767 na?

  • @hehez-x4i
    @hehez-x4i 4 месяца назад

    where did current raw value come from?

  • @onkarkounsalye
    @onkarkounsalye Год назад

    Incomplete video use Normx & Scalex functions for proper scaling & please show practical videos of analog i/p& O/ps

  • @AJinUK007
    @AJinUK007 3 года назад

    Good explanation I am a new subscriber ❤️...

  • @gillussmuts1888
    @gillussmuts1888 3 года назад

    very nice explanations. Could you do some Delta plc videos to please.

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      I will make full series on delta plc and HMI

  • @garanprabaa1793
    @garanprabaa1793 3 года назад

    what is the purpose of resistor between the analogue input .pls

  • @Learn-lp3nf
    @Learn-lp3nf 7 месяцев назад

    sorry, i don't understand, how do you get 65535 ? and you divid by 50 ?

  • @MohamedSalah-fe8xz
    @MohamedSalah-fe8xz 3 года назад

    could you please help me? i am using omron PLC i need to do a scaling of an analog input but i dont know how can i figure out the resolution for ADC?

  • @AritraDalal
    @AritraDalal Год назад

    I think this is very misleading. Siemens documentation has the 20mA conversion at 27648

  • @CaetanoÂngelo
    @CaetanoÂngelo 2 месяца назад

    Please, the second video😢

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  2 месяца назад

      ruclips.net/video/rD764gi3YSQ/видео.htmlsi=3aFZW7feLF2j0khB

  • @moon691000
    @moon691000 3 года назад +1

    How we get 65535 value ?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      65535 is the digital value at 20mA input signal. it depends upon how resolution analog to digital converter have. for example if resolution is 16 bit , the max value will be 65535. if resolution is 8 bit max value will be 256 only.

    • @moon691000
      @moon691000 3 года назад

      @@EASYPLCTRAINING Thank you

    • @marcosrivas800
      @marcosrivas800 3 года назад +1

      Siemens is 27648 20mA

  • @masumahmed7978
    @masumahmed7978 2 года назад

    part two where

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  2 года назад

      ruclips.net/video/rD764gi3YSQ/видео.html

  • @RajeshYadav-be7ds
    @RajeshYadav-be7ds 3 года назад

    From where 65545 came

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      Analog to digital converter is converting 4 to 20mA to 0 to 65535

  • @FarooqAhmad-jw7ol
    @FarooqAhmad-jw7ol 3 года назад

    65536 how it comes

  • @arumugampillaiamourdalinga300
    @arumugampillaiamourdalinga300 7 месяцев назад

    Please Send me the BOM