I agreed, very much informative vedio, bcz which information has given may check from Google. In this case every technician should have this much knowledge, bcz mostly technicians are such practical knowledge don't have, and day to day changes every body who are in this refrigeration field they will never makes damages 💯(vecum, Air purging and specially moisture removal) operation is must, their will be no any blast nor damages INSHAALLAH.
AOA. Farman bhai AC newly install hua hai. Non inverter hai. Hr baar jb compressor start hota hai tu indoor se high pitch whistling sound aata hai or phir 1 min me chala jata hai. Reason kya hai iski?
Maine new Haier AC liya inverter box packed es Mai R32 gas hy ... Compnay k bande agaye laga liya piples connect kiye... Koi vacuum nai kiya... Unho ne kaha es Mai company k taraf se gas filled ata hy... 5 month se use kr raha hun... Is it safe ?
Dear brother, Vacuum hona lazmi hai, Agar vacuum nhi kiya hai, to ye 20% dangerous hosakta hai... Matlab 80% safe hai... Kyunke koyi bhi AC yun hi nhi dhamaka karta hai balke JB AC me koyi unbalanced conditions paida ho jaye tab blast ke chances paida ho jate hain
@@FKmechofficial Jab se yeh blast ka news aya tabse maine us dealer KO call kiya.. Usne kaha k ap fikar na karo. Maine 3000 ac sold kiye sab yahi company wale lagatay hy.. Aj tak koi masla nahe aya hy... Khair mai kal wo Mechanic se call pe bat karta hun wo kya kehta hy.... Mai UAE mai tha waha non inverter Ac LAga tha .. Ek din pipe leak howa Ac wala agaya pipe theek kiya gas dala.. Vacuum kiya nai. 2 saal se 24 hours on rehta hy... Confused hun
@@FKmechofficial Jab se yeh blast ka news aya tabse maine us dealer KO call kiya.. Usne kaha k ap fikar na karo. Maine 3000 ac sold kiye sab yahi company wale lagatay hy.. Aj tak koi masla nahe aya hy... Khair mai kal wo Mechanic se call pe bat karta hun wo kya kehta hy.... Mai UAE mai tha waha non inverter Ac LAga tha .. Ek din pipe leak howa Ac wala agaya pipe theek kiya gas dala.. Vacuum kiya nai. 2 saal se 24 hours on rehta hy... Confused hun
Sir mene new ac liya hai midea ka r32 gas wala or 6 feet pipe extend kiya hai, technician vacuum nahi koya bas 1 side open kar k run kiya hai or pipe thanda honay k baad gas on ki hai. Ab main kia karon guide kardain qk jesa apnay kaha ye explosive hai tou kiya main gas change karsakta hon r32 ki jagah r410 dalwadon qk compressor tou t3 hai
Brother technician ko vacuum karna chahye the, but ab unit ko service, maintenance carefully proper time se karte rahen. Taaake unit me koyi unbalanced conditions na baaaane
@@FKmechofficial I didn't get it clearly. I can run but technically theek nahi hai means mujhe nahi karna chahiye? Can you please explain the technical reason? it would help me a lot since it is explosive and the technician didn't vacuum it so it's become a very big concern for me. I appreciate your prompt response sir.
Can u tell me why casette / VRF AC comes with R410A and not R32. For eg : O general 1.5 TON and 2 ton comes with r32 gas but 2.5 ton and 3 ton is coming with R410A... Mitsubishi heavy duty are generally coming with R410A.
R32 is not yet applicable in higher capacity air conditioner units, Because it has explosiveness character whenever It is miss calculated by a technician during cycle assembling. While R410A is safe
Dear sir r22 capillary pressure drop is 65 and r410a capillary pressure drop is i think 52 ?? , please tell us what is Capillary pressure drop of r32???
Dear Engr Sb, I am buying new AC from Market.. Looking forward to Purchase Non.Inverter heat and cool as I will put this AC in Drawing room.. Do you recommend buying non.inverter 2 tons or should I go for 1.5tons inverter? is my investment future safe with Non.inverter? my room size is 15x27.. mazeed ye k non.inverter brand new k andar i have only R32 options whereas inverter options may R410a mil rahi hai abhi bhi... please help as it is lot of money alomst 200k..
Sir mera non inverter ac hai hair company ka 2 saal phelay liya tha is may r32 gas dali huhi hai...kiya main is may r410a gas dalwado koi masla tu nahi hoga..plz ap batadey
@@hammadusman9436 brother charge kr sakte ho leken charge Karni nhi chahye,,, Issslie ke cooling effect me bhi tora sa faraq Aajata hai Awr compressor life pe bhi effect parta hai
@@FKmechofficialtu main is may r32 ka compressor nikalkay r410a ka compressor dalwado...ya ap koi dosra solution batadey takay cooling bhi achi ho..compreesor ki life ko bhi nuqsan na ho
technician usually purge kr k install krtay hen. woh vacuum nhi krtay so air inside reh janay ka imkan rehta hah. this is very very bad of our technicians.
Can u tell me why R32 machine outdoor is lighter and smaller but R410A outdoor unit much bigger and heavier ? Is it due to heat absorption capabilities?
R32 is more capable than R410A, that's why little bit smaller R32 unit is equal in capacity to little bit bigger R410A. The components in R32 are little bit lighter than R410A
بہت خوب ۔ مفید انفرمیشن ہے ۔
کل آر 32 کے یونٹ کے دھماکہ حوالہ سے دو وڈیو دیکھیں ۔ دونوں کی آراء مختلف تھیں۔ لیکن انداز صرف ریٹنگ بڑھانے والا تھا۔ میں تعلق ایچ وی اے سی سے رہا ہے۔ اس لیے ان کے ہنگامہ خیز بیان سے مطمئن نہیں ہوا ۔ آج آپ کی وڈیو دیکھ کر حقیقت عیاں ہو گئی
@@shuaibgul247 shukarya Janab ❤️
I agreed, very much informative vedio, bcz which information has given may check from Google. In this case every technician should have this much knowledge, bcz mostly technicians are such practical knowledge don't have, and day to day changes every body who are in this refrigeration field they will never makes damages 💯(vecum, Air purging and specially moisture removal) operation is must, their will be no any blast nor damages INSHAALLAH.
Thanks Dear brother ❤️
Dear sir I hope you are doing well today, my Allah bless you, 🎉🎉🎉🎉🎉
Alhamdolellah,
Amin
Mashallah very informative video.
Shukarya Bhai ❤️
Brother agar install kerte hue R410 wale AC ko vacuum na kerain to dangerous to nai?
R410a dangerous to nhi, Leken Achi cooling result Lene kelie acha vacuum zaroori hai
Good job
AOA. Farman bhai AC newly install hua hai. Non inverter hai. Hr baar jb compressor start hota hai tu indoor se high pitch whistling sound aata hai or phir 1 min me chala jata hai. Reason kya hai iski?
Wa Alaikumussalam, Dear ho sakta hai ke ye sound fan motor bearings ka ho
@@FKmechofficial Sir jb gas travel krti hai tb aati hai sound almost 30 sec k liay bas.
@@aunkhan3985 agar sound gas travel karte waqt hota hai, to pir ye indoor me distributer me koyi capillary tube partially block hai
Zabardast sir bht acha btaya apne
Shukarya Bhai ❤️
Liquid behtar rahega ya Ave per
Liquid
Sir indoor 32 ka and outdoor 410 ka use ho ra haii and r 410 use karke system ok ho saktaya
Use ho sakte hain, per aisa kana nhi chahye
Ok sir ji
Maine new Haier AC liya inverter box packed es Mai R32 gas hy ... Compnay k bande agaye laga liya piples connect kiye... Koi vacuum nai kiya... Unho ne kaha es Mai company k taraf se gas filled ata hy... 5 month se use kr raha hun... Is it safe ?
Dear brother,
Vacuum hona lazmi hai,
Agar vacuum nhi kiya hai, to ye 20% dangerous hosakta hai...
Matlab 80% safe hai...
Kyunke koyi bhi AC yun hi nhi dhamaka karta hai balke JB AC me koyi unbalanced conditions paida ho jaye tab blast ke chances paida ho jate hain
@@FKmechofficial Pata nahe Haier Company k Mechanic Kyun vacuum nahe karte new installation mai... Kpk mai sab logo aise lagate hai
@@FKmechofficial Jab se yeh blast ka news aya tabse maine us dealer KO call kiya.. Usne kaha k ap fikar na karo. Maine 3000 ac sold kiye sab yahi company wale lagatay hy.. Aj tak koi masla nahe aya hy... Khair mai kal wo Mechanic se call pe bat karta hun wo kya kehta hy.... Mai UAE mai tha waha non inverter Ac LAga tha .. Ek din pipe leak howa Ac wala agaya pipe theek kiya gas dala.. Vacuum kiya nai. 2 saal se 24 hours on rehta hy... Confused hun
@@FKmechofficial Jab se yeh blast ka news aya tabse maine us dealer KO call kiya.. Usne kaha k ap fikar na karo. Maine 3000 ac sold kiye sab yahi company wale lagatay hy.. Aj tak koi masla nahe aya hy... Khair mai kal wo Mechanic se call pe bat karta hun wo kya kehta hy.... Mai UAE mai tha waha non inverter Ac LAga tha .. Ek din pipe leak howa Ac wala agaya pipe theek kiya gas dala.. Vacuum kiya nai. 2 saal se 24 hours on rehta hy... Confused hun
Sir mene new ac liya hai midea ka r32 gas wala or 6 feet pipe extend kiya hai, technician vacuum nahi koya bas 1 side open kar k run kiya hai or pipe thanda honay k baad gas on ki hai. Ab main kia karon guide kardain qk jesa apnay kaha ye explosive hai tou kiya main gas change karsakta hon r32 ki jagah r410 dalwadon qk compressor tou t3 hai
Brother technician ko vacuum karna chahye the, but ab unit ko service, maintenance carefully proper time se karte rahen. Taaake unit me koyi unbalanced conditions na baaaane
@@FKmechofficial kiya main r410 dalwa sakta hon??
@@umairanwaar174 yes of course, but technically teek nhi hai
@@FKmechofficial I didn't get it clearly. I can run but technically theek nahi hai means mujhe nahi karna chahiye? Can you please explain the technical reason? it would help me a lot since it is explosive and the technician didn't vacuum it so it's become a very big concern for me. I appreciate your prompt response sir.
@@umairanwaar174same problem facing
Can u tell me why casette / VRF AC comes with R410A and not R32.
For eg :
O general 1.5 TON and 2 ton comes with r32 gas but 2.5 ton and 3 ton is coming with R410A...
Mitsubishi heavy duty are generally coming with R410A.
R32 is not yet applicable in higher capacity air conditioner units,
Because it has explosiveness character whenever It is miss calculated by a technician during cycle assembling.
While R410A is safe
@@FKmechofficial asked many technicians nobody could answer this. Thnx for the info
@@dipanjanroy5469 here you will get every answer Insha Allah
Dear sir r22 capillary pressure drop is 65 and r410a capillary pressure drop is i think 52 ?? , please tell us what is Capillary pressure drop of r32???
R22 drop is 50 ~ to 60 Psi,
R410A drop is 75 to 80 psi,
R32 is 65 to 70 Psi
Dear Engr Sb, I am buying new AC from Market.. Looking forward to Purchase Non.Inverter heat and cool as I will put this AC in Drawing room.. Do you recommend buying non.inverter 2 tons or should I go for 1.5tons inverter? is my investment future safe with Non.inverter? my room size is 15x27.. mazeed ye k non.inverter brand new k andar i have only R32 options whereas inverter options may R410a mil rahi hai abhi bhi... please help as it is lot of money alomst 200k..
Dear where is your location ?
Your AC type & capacity depends location's climate ?
❤very use full information bro
Thanks Dear
Sir main na 5 din pehla haier ka thunder model lia hai us ma r32 ha ab guide krain sir
Kisi ache professional technician se install karo bhai
Jis dealer se liya hy Haier company wala banda install karega
Mashallah lndia Mohammad Nadeem Beylim
Thanks Dear
Dear Sir, Ager R410A leak ho rahi ho to iska koi nuqsan to nahi? Is main koi blast hone ka khatra to nahi hota? Please zaror bta dain. Jazakallah
@@zainalimughal10 agar bahut zyada leak ho awr room ait tight band ho pir sans lene ka masla Aasakta hai,
Leken blast ka issue nhi Aasakta
@@FKmechofficial Jazakallah
@@zainalimughal10 Barak Allah
Well done good job sir, please tell us sir compressor data sheet kaise nikaalte hain
Note to next video
Very informative in simple manner. All the best brother from India
@casforindia Thanks Dear
Subscribed your channel.
@@shuaibgul247 jazak Allah
Brother agar R32 ki leak ho to blast possible he?
@@84zuba no brother,
Leken R32 Leak hone ki surat me fire/ flame nhi chalna chahye...
Main ne utube pe dekha hai, kuch log fire lighter se R32 ko flame de rahe hain, but wo fire nai pakar rahi
A a jinab
Meri softy machin _4 ke aagay temprature show nhi kr rahi aur ratio 65 ke aagay jati nhi ...ap meharbani kr k solution bataye( R410A)
Come to WhatsApp +92 3059126576
Sir mera non inverter ac hai hair company ka 2 saal phelay liya tha is may r32 gas dali huhi hai...kiya main is may r410a gas dalwado koi masla tu nahi hoga..plz ap batadey
@@hammadusman9436 brother charge kr sakte ho leken charge Karni nhi chahye,,,
Issslie ke cooling effect me bhi tora sa faraq Aajata hai Awr compressor life pe bhi effect parta hai
@@FKmechofficialtu main is may r32 ka compressor nikalkay r410a ka compressor dalwado...ya ap koi dosra solution batadey takay cooling bhi achi ho..compreesor ki life ko bhi nuqsan na ho
Please bataday solution😊
????
No you can't fill R410 in R32 unit because that compresur is made for r32... Not for r410...
Aslam u alykum sir aksr log bolty ah R32 khtrnak ha khin blast huwa ah ac ma qk ma ny Kenwood liya ha us ma R32 gas h plz reply
Yes dangerous hai, leken agar care ke sath install awr use kiya jaye...
Pir no problem
@@FKmechofficialcare kaisa care?
Awesome
Thanks Dear
technician usually purge kr k install krtay hen. woh vacuum nhi krtay so air inside reh janay ka imkan rehta hah. this is very very bad of our technicians.
@@muzammalbaig of course yes, you are right brother ❤️
Can u tell me why R32 machine outdoor is lighter and smaller but R410A outdoor unit much bigger and heavier ?
Is it due to heat absorption capabilities?
R32 is more capable than R410A, that's why little bit smaller R32 unit is equal in capacity to little bit bigger R410A.
The components in R32 are little bit lighter than R410A
@@FKmechofficial thnx for the info... U r quite knowledgeable sir.
@@dipanjanroy5469 you are welcome Dear ❣️
❤❤❤❤❤❤
❣️❣️
Dear teacher g apne ye ni btaya ke r32 ko or 410 ko kese charg krna he
Thanks for highlighting,
R32 ko ap vapor ya liquid dono halat me charge kar sakte ho, jabke
R410A ko only liquid halat me...
Ustad g or jo r600a he usko frig me liquid charge karna chahie ya avepar
@@DanishAli-mf4ly R600A liquid charge
👌👍
Thanks