Assalamualaikum sir meny apny inverter 48 volt ki setting phoenix 3500 ki setting k hissab se rkhi hai Mery system me JB 45 to 40 percentage tk charging rhti hai to wo DC low voltage ka error dekr system shut down krdeta hai or battery 0% hojati hai kindly mujhe bta dain kia problem hai
I understand; thank you. In my case during grid feed when the feed goes more than 5 kw the voltages also increased to 260V..263V and invertor tripped and reconnect. I cant able to increase the grid feed. To avoid tripping I set the grid feed on 5.5 kw, if you have any idea about wiring or other grid trnsfarmer issue please suggest.
inverex nitrox 6kw Girid se Battery 100% charging ke bad bhi charging 2.1 kw leta he ? Girid per 100% charging ke bad charging kesy cut off hogi ? Is ki setting bata den . Thanks. Waheed soomro
My Inverix Nitrox 6kW inverter is not able to run the smart load from the grid at night.(grid voltage at the monent 186-187). Although the "always grid on" option is checked in the smart load settings, it still doesn't work. Previously, it was working fine, but now, when we switch on heavy load devices like the split ACs, the grid automatically shuts down.I found a workaround, but it’s not a complete solution. I unchecked the "always grid on" option, and now the grid starts working. However, it still doesn't switch on the heavy voltage devices; it only supports normal load. This is very strange because if I disable the "always grid on" option in the smart load settings, the grid works but still doesn't power the heavy devices. During the day, when the grid is off and the power comes from solar, everything works fine.Can you please tell me what's wrong here?
that is is the only 1 battery. i can provide the screenshots of my configuration from SolarApp. or i can share my credentials of Solarman app..it will be very kind of you if u can help in this matter! Shukria
@@eqabelectrician8980 thank you for respònse. But I found out the issue was due to low voltage. So, I set the grid to keep the low voltage at 165. Now, it's working fine. The problem was because of the low voltage in our area.
Bhai mera msla haal karde please bht marishan hon Me ne recently nitrox 3kw ka install kiya hai white color ka Problem ye hai k jab bhi me inverter ko off karta hon tu charging bhi cutoff ho jati hai grid aur solar duno ki Please koi haal bata de
Hi Sir I am facing an issue. My Nitrox 6.0kw increase voltage to 270 while feeding to grid. It happens when there is no load at home and selling totally to grid. Or even using load at home and production is around 4.6kw. I have watch hour video and increase voltage to 280 but problem is there. Please help me
Brother Output pr wohi voltages atay hain jo ap k Grid k voltages hain. Ap grid ko agr cut off karain ge to ye puray voltage dega but batteries hona bhi must hai.
@@arfatakhtar3940 mera nitrox rat ko theak chalta hai, mai ny 150 Low voltage rahka howa hai and stabilizer lagya howa taky inverter ko full voltage mily albata din ko wapda disconnect karta rehta hai jub wapda ho.
You told in yr this video that high range is recommended upto 275 amd 280 but you cant tell for the low voltage recommendation, plz let me know the recommended low voltage. Thanks
My Nitrox hibird unit have a recent problem, it is selling extra voltages to grid, but if excess voltage increase from 3.5 kW then it disconnect grid, before it was working fine then reconnect again, if we increase the using load then excess voltage decrease, so it sell to grid properly
@@EnonTraders no issue with load shutdown, in peak hours there are enough extra power for selling to grid, in those hours it disconnect the grid, then we switch on some ACs to increase the load, which decrease excess power then it supply back to grid in the limit of 3kw
Actually it seems that in peak production hours Grid Votlages increases and it exceed Inverters upper voltage range so you need to increase Maximum Grid Voltage range. ruclips.net/video/W5pwOy5bxuk/видео.htmlsi=mFGtX0qrbIeQCEv- Watch this video to increase Grid Voltage range.
Me ny inverex nitrox 8kva inverter install kia ha. Rat ko jb wapda pe shift hojata ha. Tu heavy load nhe leta. AC wagera laga k Trip hojata ha. Wapda se voltage 180 to 195 aata ha.
Bhai, F47 over frequency fault error aa raha ha jaisay he 2.40kw pe jata ha load, breaker output wala bar bar trip hota ha.. kya jo settings ap ne ki hen, exactly ya he ker lon to kya F47 resolve hoga? If not, please guide me. My installation company said braker fault ha. They're such a stupid people, meri doren lagwa rahy hen , please help
بھائی میرا ناٹروکس انورٹر دن کے وقت واپڈا کو بلاک کر دیتا ہے اور سولر کے ساتھ بیٹری استعمال کرتا ہے جس سے بیٹری مکمل چارج نھیں ہو پاتی ۔ میں نے ہواوے لیتھیئم بیٹری لگائی ہے ۔ پلیز اس مسلئے کا حل بتائیں ۔ بھت پریشان ہو اس سے
Sar kitne empier Ke Upar ke charging kar sakte hain
Assalamualaikum
Sir kia lo votag par grid off ka esambal ata hin?
Inverex nitrox 6kw hybrid system installed he.
Kya 6kw me b high voltage 270v rakh sakte hen ?
Assalamualaikum sir meny apny inverter 48 volt ki setting phoenix 3500 ki setting k hissab se rkhi hai Mery system me JB 45 to 40 percentage tk charging rhti hai to wo DC low voltage ka error dekr system shut down krdeta hai or battery 0% hojati hai kindly mujhe bta dain kia problem hai
46.
47.
48 ka foult araha hey konsi setting per rakhen.
Bhai growatt 10000 Ki settings bata saktay hn?
what is the setting to run load without utility(wapda) and battery ?
I understand; thank you. In my case during grid feed when the feed goes more than 5 kw the voltages also increased to 260V..263V and invertor tripped and reconnect. I cant able to increase the grid feed. To avoid tripping I set the grid feed on 5.5 kw, if you have any idea about wiring or other grid trnsfarmer issue please suggest.
Only way is to increase grid voltage range of Inverter.
Bahi mara gahr ka low voltage 175 h inverter on hu tha he ni h kiya kr hum
inverex nitrox 6kw
Girid se Battery 100% charging ke bad bhi charging 2.1 kw leta he ?
Girid per 100% charging ke bad charging kesy cut off hogi ?
Is ki setting bata den .
Thanks.
Waheed soomro
Sir ye nitrox pure sine wave hota hai ?
Ji bhai
AoA brother no batteries 20 plats 11500PV Inverx 575 Topcon N type but AJB light jati invertor starts beeping again and again
Plz jawab de ma kecs s charge krna nhi chahta apni batery uska lya koi seting btai
ruclips.net/video/tLQR8Ajgi3c/видео.html
Watch the above video to turn off grid charging.
Sar mere netrox 12kw inverter din me lod pe solar se wapda zyada estemal krti he
Mery ghr pe 2 wapda line hain aek voltage ati hain 165 aur dosry ke aty hain 270 transformer me kuch masla hain tu kia karo
Ye dono volt level kis time hote hain?
My Inverix Nitrox 6kW inverter is not able to run the smart load from the grid at night.(grid voltage at the monent 186-187). Although the "always grid on" option is checked in the smart load settings, it still doesn't work. Previously, it was working fine, but now, when we switch on heavy load devices like the split ACs, the grid automatically shuts down.I found a workaround, but it’s not a complete solution. I unchecked the "always grid on" option, and now the grid starts working. However, it still doesn't switch on the heavy voltage devices; it only supports normal load. This is very strange because if I disable the "always grid on" option in the smart load settings, the grid works but still doesn't power the heavy devices. During the day, when the grid is off and the power comes from solar, everything works fine.Can you please tell me what's wrong here?
Do you have connected batteries?
@@EnonTraders yes lithium battery - Inverex Power wall 5.2 KW
that is is the only 1 battery. i can provide the screenshots of my configuration from SolarApp. or i can share my credentials of Solarman app..it will be very kind of you if u can help in this matter! Shukria
Split ac 220 pai chalta hai is waja sai invrtr ka voltge aur b down hota hai so ap. night shift pai haevy load bye pass rakhly. To easy run hoga
@@eqabelectrician8980 thank you for respònse.
But I found out the issue was due to low voltage. So, I set the grid to keep the low voltage at 165. Now, it's working fine. The problem was because of the low voltage in our area.
Bhai mera msla haal karde please bht marishan hon
Me ne recently nitrox 3kw ka install kiya hai white color ka
Problem ye hai k jab bhi me inverter ko off karta hon tu charging bhi cutoff ho jati hai grid aur solar duno ki
Please koi haal bata de
Hi Sir
I am facing an issue. My Nitrox 6.0kw increase voltage to 270 while feeding to grid. It happens when there is no load at home and selling totally to grid. Or even using load at home and production is around 4.6kw. I have watch hour video and increase voltage to 280 but problem is there. Please help me
Brother kuch setting mili tu batana mera bh yahi issue hai
Sir inverex nitrox 6kw ki output 190 viktage a rahe hai. Ye 220 kasay i ge?
Brother Output pr wohi voltages atay hain jo ap k Grid k voltages hain. Ap grid ko agr cut off karain ge to ye puray voltage dega but batteries hona bhi must hai.
@sunectricenergy4668 thanks brother
Sir mera inverex nitrox 6kw F56 DC_Voltlow Fault da raha ha raat ka time ma iska koi solution bata da
ruclips.net/video/TAWyA3bGQDU/видео.html
Explained in detail
AOA!!
Bhai mera inverter nitrox 8KW h wapda sharing leta h or sath hi trip kr deta h, kbi 20, 25 mint chal jta h kbi bilkul wapda sharing nhe leta,
@@arfatakhtar3940 Bhai mera bhe same masla hai, 8kw hybrid nitrox inverter. If you find any solution to it please do tell me
@@zaramziyar company ko bejha h inverter fault aa gya h relay mein jo current shift krti h wapda to battery n solar
@@zaramziyar ap ka hua thk ya nhe abhi?
@@arfatakhtar3940 mera nitrox rat ko theak chalta hai, mai ny 150 Low voltage rahka howa hai and stabilizer lagya howa taky inverter ko full voltage mily albata din ko wapda disconnect karta rehta hai jub wapda ho.
You told in yr this video that high range is recommended upto 275 amd 280 but you cant tell for the low voltage recommendation, plz let me know the recommended low voltage. Thanks
165 Volts
Thanks for reply
JazakaAllah khair
JazakaAllah khair
jazak allah
My Nitrox hibird unit have a recent problem, it is selling extra voltages to grid, but if excess voltage increase from 3.5 kW then it disconnect grid, before it was working fine then reconnect again, if we increase the using load then excess voltage decrease, so it sell to grid properly
Do you have net meter installed?
Kindly clear your problem.
Your problem is with feedback to grid
Or
Shutting down of load?
@@EnonTraders no issue with load shutdown, in peak hours there are enough extra power for selling to grid, in those hours it disconnect the grid, then we switch on some ACs to increase the load, which decrease excess power then it supply back to grid in the limit of 3kw
Actually it seems that in peak production hours Grid Votlages increases and it exceed Inverters upper voltage range so you need to increase Maximum Grid Voltage range.
ruclips.net/video/W5pwOy5bxuk/видео.htmlsi=mFGtX0qrbIeQCEv-
Watch this video to increase Grid Voltage range.
Jazakallah bhai bohat tention the high voltage k baray may apki video say bohat help mili❤❤
Me ny inverex nitrox 8kva inverter install kia ha.
Rat ko jb wapda pe shift hojata ha. Tu heavy load nhe leta. AC wagera laga k Trip hojata ha. Wapda se voltage 180 to 195 aata ha.
Batteries lgain hain ap ne?
@@EnonTraders G lagai ha. Lithium
Rat k time jb wapda aaty ha.
load dalta ho.tu trip hojata ha
0344-4447745
Is number pe system 1 video bhej dain. WhatsApp number per
Bhai, F47 over frequency fault error aa raha ha jaisay he 2.40kw pe jata ha load, breaker output wala bar bar trip hota ha.. kya jo settings ap ne ki hen, exactly ya he ker lon to kya F47 resolve hoga? If not, please guide me. My installation company said braker fault ha. They're such a stupid people, meri doren lagwa rahy hen , please help
بھائی میرا ناٹروکس انورٹر دن کے وقت واپڈا کو بلاک کر دیتا ہے اور سولر کے ساتھ بیٹری استعمال کرتا ہے جس سے بیٹری مکمل چارج نھیں ہو پاتی ۔ میں نے ہواوے لیتھیئم بیٹری لگائی ہے ۔ پلیز اس مسلئے کا حل بتائیں ۔ بھت پریشان ہو اس سے
Ap battery k symbol pe touch karain. Wahan Li-BMS likha aa rha hoga. Btain k wahan values 0 hain ya voltages ya percentage me data show ho rha hai?
@@EnonTraders BMS cable nahi attached,
@zaramziyar attach karain bhaj
Bhai jb inverter ziada units green meter ki export karna shoro karta ha to voltage increase ho jaey hn jis ki waja sa inverter bnd ho jata ha
nitrox 6kw inveter laga hy grid hey par off grid show kr rha hy low and high volts setting b ki hy aur isi waja se charge nhi kr rha
Apki Grid side pe agr voltages thek hain to phr kahin termination loose hai