Complete design and diagram with demonstration plus clear explanation equals very nice and good teaching...that's the best sharing knowledge...thumps up Sir !!
Pang NCII a tlga boss,, graduated din ako ja ,, pinahirapan kami sa trouble yan,,,mga nkikita sa panel.na trouble shoot normal lng yan,, pero kakaiba gnwa sa amin,, di tutunog,, iniba wiring input,output, sira resistor,, sira fuse, tingal contact line battry,, los wiring connection,, SMOKE DETECTOR,, contact line s loob binalutan tape,,, nagputol sila wire akala mo.nakadugtong dipala😂 DAPAT MARUNONG KA GUMAMIT TESTER👍
Sir sana po magawan nyo ng video yung wiring installation yung 24volts DC niya kung paano na convert yun fron 220 volts. At yung lahat ng connection sa panel. At sir saan po nyo nilagay yung "end of the line resistor" salamat po and godbless sir 😊
May tanong lang ako halimbawa operated na ang FDAS nyo gusto ko mag dag2 ng isa pang device na crush alarm button at gusto kung pag push sa crush alarm button tutunog lahat ng bell sa bawat zone saan mag interconnect
Ang Linis Mo Mag Demo Sir. Galing Naman. Wala Pa Yan Sir Nung Nag Aaral Ako Kaya Wala Ako Knowledge Sa Fdas. Boss May Diagram Bang Ibibigay Pag Mag Take Ng Assisment Sa Tesda? Pa Help Naman Po Sir Hehe. Gusto Ko Kc Mapag Aralan Yan. Tas Maka Kuha Ng Nc2
Meron po ibibigay yung SINGLE LINE DIAGRAM NG lang po .Panuorin nyo po yung PART-2:(EIM NC2) FIRE DETECTOR ALARM SYSTEM..meron dyan sa RUclips VIDEO ko po.kasama na pati yung Three Way Switch Installation po...e TYPE nyo PANGALAN ko Amon Lubiano sa RUclips CHANNEL ko po.ty.
Sir napaka ganda ng inyong video training tungkol sa FDAS. Dati po akong Bumpero, Maaari po ba akong mag walk-in sa inyong Training Center or Shop upang magpaturo sa inyo ng personal tungkol sa EIM NC2 FDAS Installation, Inspection Testing and Maintenance?
pwede po kaya lang bawal pa sng face to face sa ngayon ang School ko po ay NATIONAL POLYTECHNIC COLLEGE OF SCIENCE SND TECHNOLOGY sa Quezon City Lagro po.....sa
sa ngayon Panuorin nyo lang muna mga Tutorial Video ko po ginagamit ko rin yan sa ONLINE CLASS ko po..e type nyo lang Pangalan ko sa RUclips Amon Lubiano Motor Control.para ma refresh po kayo.ty
sir salamagt po s information,salute,,ask ko lng po sa isang zone pede b ikabit ung dalawang detector at push alarm bell, thanks EE elexer galvan batch 1989
Ang Smoke Detector ay Electronic Device na Sensor ng Usok at ito ay Ginagamit ng mga Industrial ,Commercial at Residential Building para Maiwasan ang Sunog kasi pag Na Sense na yung Usok Automatic na Tutunog Yung Alarm system, at SWITCH naman po yung Push Button at yung Strobe Light i Research mo nalang Sa mga Electronics books para alam mo kung saan palagi ginagamit cge idol
salamat malinaw po. tanong ko lang po. pag nagkabit na sa building. ano po standard na size ng wires, kailangan ba ipasok sa pvc pipe or metal tube. ano ba requiremnt ni BF?
Sir lahat po ng pinakikita nyo mga alarm at smoke detector nais ko po bilhin ng aking ma-install (DIY) saan PO lahat nabibili iyan sir? Tnx po Dan Tala chamba-chamba electrician ng pampanga
eto po.CONVENTIONAL FIRE ALARM CONTROL PANEL,,MODEL (YF-3) (YY/TYY) sa Santa Cruz Manila namin binili bandang kanan ng avenida diko po matandaan pangalan ng puwesto cge po
Panuorin mo yung Residential House Design (single dwelling) para magkaroon ka ng idea tungkol sa mga Sizes of Wire, Breakers at Conduit na gagamitin mo pagdating sa mga Electrical Loads ty idol
hindi po pwede ang Design nyan ay yung Smoke Detector nasa Zone st yung Fire Alarm Bell ay nass Sounder Sundin po natin yun standard Wiring Installation ty po
opo kasama sa design nyan..Panuorin nyo yung PART-2(EIM-NC2)FIRE DETECTOR ALARM SYSTEM.....Type nyo pangalan ko Amon Lubiano sa RUclips Channel ko para mapanuod nyo lahat.ty po.
Pa add na rin ng request po kung paano mag address sa mga addressable na devices po. Maraming salamat po at akoy natututo sa mga videos nyo po. Gusto ko po kasi matuto ng fdas kaya nun napanuod ko yung video nyo po eh akoy napahanga at nasabik matuto ng fdas.
Hi sir hanggang ilang bell , heat detector , smoke detctor, and push botton switch ang kayang ilagay sa ganyang classe po ng fdas at kung ilang floor po ang kya if iaaply po sa house or building salamt po
Hi sir good day po ,,sir kailangan bang lagyan ng resistor bawat end of line?halimbawa po zone 1 po is smoke detector po may resistor po ba na ikakabit po? At sa SNDR po sir kailangan din ba laguan ng resistor? Salamat po sir....
Last August 9 2024 po pala Eim Nc2 Assesment po namin sa written Exam at sa oral lang po ako nakapasa nyun po hindi po ako nakapasa nyun po sa actual dahil naabutan po ako ng oras dahil may timelimit po kasi ang pag install hindi ko po na tapos young ibang electrical devices sa pag install po reassesment po ako ulit young actual lang daw po e retake ko yun daw po sabi ng assesor at sana po makapasa na po ako sa aking reassesment!🙏
SIR SAAN PO MABIBILI ANG FDAS? PARA MAPAG ARALAN KO NANG MATUTO PO AKO... I WILL FOLLOW UR RUclips DISCUSSING ABOUT FDAS (PART 1 & PART2) TNX PO DAN TALA CHAMBA-CHAMBA ELECTRICIAN NG PAMPANGA
Tnx...po Kung avenida lng nabili salamat po soon din po ako buy screw sa Tuesoy and some personal materials sa pagka chamba-chamba electrician ko, Subukan ko rin sa Mabalacat or Henson St. Angeles City salamat po sir
Pwede po pero pag dalawa o kaya tatlo, apat halimbawa sa ALARM duon mo ikakabit sa Pinakadulo na ALARM yung Resistor. Kaya ang Tawag dun EOL RESISTOR ty idol
Sir may resistors rin po bang naka parallel sa lahat ng sounder terminals? Pati na rin po ba sa mga zones na hindi ginagamit kailangan lagyan ng resistors? Thank you po sa pagsagot sir.
Tay pag may zone1,zone2 at zone3 po ako tas zone1 lang po ginamit ko pinarallel ko yung smoke detector at manual call point..kailanga poba may resistor lang talaga ang zone 2 at zone 3 kahit hnd naman nagamit or walang device na ginamit sa zone 2 at zone 3 nilalagyan papo ba talaga yan ng resitor yung dalawa
Kahit wala nang resistor yung mga Zone na hindi mo ginamit at walang naka kabit na device Yung meron lang Resistor ay yung Ginamit mong Zone at nakakabit sa Eol yung Resistor sa Pinaka Dulo ng ikinabit mong device ty idol
Salamat po tay napaka husay nyo po.... final asssessment kona po sa august 9,2023 sa e.i.m ilang beses kopo kau pinapanood ng paulit ulit napakahusay nyo po kuhang kuha po lahat turo nyo maliwanag po pagkakapaliwanag nyo po... salamat po sa inyo kahit papaano nakakuha ako ng another kaalaman
@@likha7528 pag nag dagdag ka ng smoke i dugtong naka Parallel Connection tapos tanggalin mo yung Resistor sa Terminal tapos Ikabit mo sa Pinakadulo na Smoke Detector naka Parallel Connection cge idol
sir... tanong kolang po... bagohan lang po ako... ganyan din yung panel nmin sir kaso hang 3 lang na detector ang kaya nga system nmin every zone... nkaparallel connection poh... ano poh male don... salamat sa sagot...
wala naman mali dun nasa specification naman kung ilan ang pwedeng ikabit......baka yung resistor mo nasa panel parin...kapag 2 o mas marami kapang ikabit sa isang zone ilagay mo sa pinakadulo detector yung resistor po...
sir wla kasi stock dito saamin na batry na 24 ginawa nmin nlagyan nlang nmin na 24v transformer pang replace ng bat. kaso pag testing ko sa volts eh 34v yong out ng transformer eh makaapikto kaya yon?
@@lykamarieclairenemil7101 opo makaka apekto po gagana yung panel pero madaling uminit dahil sobra sa voltahe yan ang cause ng pagkakasira ng panel nyo po....sundin nyo nalang po yung specification nya.cge po
@@amonlubiano1161 sir pwede poba mangyari na hindi compatible yong panel atsaka smoke detector... kasi sa amin ytt yung panel nmin atsaka hindi ytt yong aming smoke detector... pag tenetest kona isa lang na smoke detectore ang kaya nya pag ginawa kong dalawang parallel ih mag alarm agad cxa...
additional lang po...ang PANEL MUTE is pag off ng alarm sa panel....ang BELL MUTE is pag off sa alarm ng sounder. yun po ang kaibahan ng 2 mute...kapag ang SIGNAL HOLD DISABLE ay naka off or walang ilaw sa panel, kahit naka clear na po ang mga detectors at manual call point, tuloy tuloy pa rin ang alarm sa panel at sounder...at pag naka-on naman po ang ilaw ng SIGNAL HOLD DISABLE, once na mag-clear ang mga detector at manual call point, titigil na po ang alarm ng panel at sounder...ang DELAY DISABLE naman po ay ginagamit upang sa unang signal pa lang ng detector ay mag trigger na ng alarm ang panel at sounder. by default po, kasi hindi agad magti-trigger ng alarm ang panel upang ma-verify muna ng panel kung false alarm ang signal o hindi. after po ng ilang segundo, sa pangalawang signal ng detector sa panel, saka pa lang po tutunog ang alarm ng panel at sounder... sa ganyan pong klase ng panel. Since conventional FDAS yan, gumagamit po yan ng CLASS B wiring at kailangan ng 10K ohms na resistor na pang END OF LINE at naka parallel connection sa dulong detector per zone. Pagwalang resistor, open circuit po ang lalabas sa panel…ganun din po sa mga sounder na nasa sounder terminal. In addition, kailangan din po ng IN4001 diode na naka series connection sa bawat sounder or bell upang hindi mag open circuit ang bell. May DIP SWITCH po sa loob ng panel…during wiring and testing, kailangan naka ON po ang dip switch upang makakapag test kayo ng panel ng walang fault or error…and during operational na, kailangan i-off na ang dip switch upang makaka-detect automatic na ang panel kung sakaling may short circuit or open circuit bawat zone…
@@amonlubiano1161 Salamat po sa pagbibigay nyo ng kaalaman sa FDAS...yung company po na pinapasukan ko ngayon ang distributor dito sa Pilipinas ng FDAS panel na ginagamit nyo...Ini-import po namin yan from Taiwan at ibinibenta dito...Kaya po nung napanood ko yung video nyo, natuwa po ako at nag-share na din ng info para dagdag kaalaman sa ibang viewers...salamat po at sana mas marami pa kayong maturuan na kababayan natin...
opo dapat lahat ng zone meron eol resistor...yung PART-2. FDAS. na video ko (Actual demo) nasa loob ng PANEL (FDAS) yung Mga Resistor Nakakabit sa mga Terminal bawat Zone,,ty idol sa panunuod.God Bless
Thank you for great sharing : Like for you : God bless you
Thanks again for coming buddy
Complete design and diagram with demonstration plus clear explanation equals very nice and good teaching...that's the best sharing knowledge...thumps up Sir !!
thanks for watching God Bless
Napaka linaw mag explain ni master thank you po gusto ko po sana matuto nyan sa actual din master papano po kya? Salamat po sir
@@migueldelosreyes233 thanks for watching sir God bless..andyan napo yung video ng PART-2 FDAS actual installation sir.
Maraming salamat po sir god bless po.
ruclips.net/video/1ouZWEILyJQ/видео.html
Sir ang galing mo mag turo swabe wala paring kupas
Batch 2015-2017 ♥️
thanks eng'r..saan school ka dati..Bpc ba?
Galing tlaga ni sir mag discuss.maiintindihan mo tlaga.proud to be cit electrical batch 2010.mga engineer chaggg
ty engr.tanagon keep safe and God Bless..hayaan mo e sbout out ko ang batch mo pag nag video ulit ako.
Chaaaag
Nice, naiintindihan talaga kahit wala pang idea. Ma gegets mo din dahil maayos ang pag explain.. thanks sir
maraming salamat po panuorin nyo yung Part2 para mas maliwanag po maam.ty
ruclips.net/video/m7awvd6EJWY/видео.html
ruclips.net/video/m7awvd6EJWY/видео.html
galing mag turo, complete and clear explanation thank you po sir.
Maraming salamat din idol para sa lahat yan video ko sa Industrial Electricity na gustong matuto.
Sir napakalinaw mo mag turo salamat.more video pa po.
salamat sir...e type nyo lang pangalan ko sa RUclips Amon Lubiano kung gusto pa manuod ng tutorial video ko po..cge po good pm.
Salamat Sir the best ang explain nyo. Sana all
maraming salamat din po.
Wow sir galing mo Po mag explain good job Dito ako nag review sa mga vlog mo sir madali ako Maka intinde
maraming salamat sa panunuod idol God Bless
nice sir, laking tulong nato sa akin...
maraming salamat din sir sa panunuod ng mga tutorial video ko po.
ang linaw sir thank you full support sayo!
Nice bossq.. Sudah shering
Thanks for coming
You have interesting content. Great system. Like 223 👍
thank you for watching my friend
ruclips.net/video/m7awvd6EJWY/видео.html
New subscriber watching from Al Khafji Saudi Arabia 💪
Many thanks for watching idol
Thank you sa mga itinuturo nyo po sir..
welcome and thank you din sa panunuod sa mga video ko idol God Bless
Thank you sir very informative.. dami kung natutunan..
Salamat din po sa panunuod idol
npkalinaw mong mgturo sir thank you po and god bless
thanks sir
Maraning salamat boss dami ko natutunan
@@decalibrejunior1353 welcome and many thanks din...
Maraming maraming salamat po sir, napakalinaw po ang paliwanag mo.
maraming salamat sa dalaw idol God Bless
Pang NCII a tlga boss,, graduated din ako ja ,, pinahirapan kami sa trouble yan,,,mga nkikita sa panel.na trouble shoot normal lng yan,, pero kakaiba gnwa sa amin,, di tutunog,, iniba wiring input,output, sira resistor,, sira fuse, tingal contact line battry,, los wiring connection,, SMOKE DETECTOR,, contact line s loob binalutan tape,,, nagputol sila wire akala mo.nakadugtong dipala😂 DAPAT MARUNONG KA GUMAMIT TESTER👍
@@josephfollante7200 maraming salamat din idol
Ang mo mag explain Sir God bless po
Salamat sayo Sir dami kuna natutunan sayo God bless po Sir
Interesting System of Fire detector alarm Amon! Well done!
many thanks sir again God Bless
Keep watching and support especially 90sec. Ads from Al Khafji Saudi Arabia Support Filipino Vlogger 👍
Many thanks for all your support God Bless
thanks for reviewing the fire alarm system sir!
Napakahusay, watching iloilo tech💖
thanks for watching
Thank u rin po💖
stay safe sir.. nice tutorial.. God bless po..
salamat kaw din ingat lagi engr.
Gud job sir gud lock s tutorial God bless you....
thanks for watching
ruclips.net/video/m7awvd6EJWY/видео.html
Best sharing.......💪💪👍👍
thank you for wstching
Napakaliwanag, maraming salamat po sa pagshare
maraming salamat sa dalaw idol God Bless
nice topic sir...more knowledge to share...matsala...
thanks for watching
Sir napaka linaw mo magturo...
many thanks sir for watching
Magaling magturo, malakas ang boses at magaling magpaliwanag
thank you for watching
Excelente vídeo parabéns
thanks for watching
@Dakari Jabari thanks for watching
ruclips.net/video/m7awvd6EJWY/видео.html
Thank you sir nice tutorial
Welcome salamat din idol
Very thankful ser on your knowledge...ser poydi pa explain..gass detector to fire alarm connection...I watching from bronie....
thanks for watching God Bless....hayaan mo e research muna natin ang gaas derector sir.thanks ulit
@@amonlubiano1161
Okay ser GOD BLESS YOU ALL SO...
sir ano gusto mo mangyari pag pinagsama natin ang gass detector at fire alarm ..gasoline ba o crude oil yung gaas.ty
maraming salamat po sir ❤️ studyante nyo pa po ako sa st.john gang ngaun dala2 ko pa po ang turo nyo ☺️☺️☺️
ah ok musta na engr'.asan ka ngayon i add moko friend sa messenger ha para magbalitaan tayo
@@amonlubiano1161 copy sir iadd kita.. 😊😊😊
@@arwincalma5809 ok
Sir sana po magawan nyo ng video yung wiring installation yung 24volts DC niya kung paano na convert yun fron 220 volts. At yung lahat ng connection sa panel. At sir saan po nyo nilagay yung "end of the line resistor" salamat po and godbless sir 😊
thanks friendruclips.net/video/m7awvd6EJWY/видео.html
Sir, may alarm system na po kau, Ruel Mapesos , batch 2000. Good luck po, 👍👍👍
kaw pala engr..sa EIM NC2 kasama na pati CCTV.musta kana...e message moko sa messenger para maging friend tayo.
Prof namen yan mahusay talaga yan boss gagalain ka namen minsan hahaha i love you sr. Dahil sayo batang republic cement na ko salamat sr. Sa lahat
many thanks din engr..Stay Safe and God Bless
@@amonlubiano1161 salamat sr. Ingat din lagi sr. Dalaw kame minsan.
Okay kayo galing mopo ser
marming salamat din sa panunuod ng mga tutorial video ko sir.
GOOD teacher
thanks again for coming my friend
Sir sana sa susunod actuall wiring nmn Ng fdas ,galing mo po salamat
Sir nc2 nc3 na po holder ko Jaya lng ung nc2 ko wlang fdas...invalid na gusto ko po makakuha idea sa inyo po. Salamat more power,
thank you sa panunuod mo sa video ko sir...andyan napo sa youtube channel yung actual connection.PART-2(EIM NC2)FIRE DETECTOR ALARM SYSTEM....
punta ka sa youtube channel ko e type mo pangalan ko Amon Lubiano..ty sir.
Thank you sir for teaching
salamat idol
Pa Shout out idol Reymond Roño personal Vlog
thanks for sharing master
thank you for watching
Happy sunday sir, puede ba maglagay ng 6 na exclusive manual push switch sa zone 2?
good morning pwede sir basta ilagay mo yung resistor sa PINAKADULO ng manual push switch.
Magandang hapon sir salamat sa pag turo, puede rin ba sir ilagay ko sa zone 2, bale 10 na smoke detector at dalawang manual push?
pwede rin po sir.
Salamat sir, god bless.
Good mrng sir, ilang ampers ba ang circuit breaker kdalasan gamitin galing s Ac current papunta ss Facp po?
Done subscribe nako idol
Salamat sir
Sir gd pm ung smoke b pwd doon ilagay ung manual call point po.
Lupit mo master
Maraming salamat din idol
Good job po sir.
thanks sir
welcome, wala po akong video p.maintenance.ty
👍👍👍
Thanks for watching sorry for late response
Sir !!!!! pa shout out !! 😁😁😁😁 student mo ko sa BPC , class 2015-2017
cge pag nag video ulit ako engr...thanks for viewing....
Ser. Pwde ba magkapalit ang zoning? Hal. Ang smoke detector ilagay sa zone 3?
opo pwede po sir
Sana ikaw nalang prof ko❤
Maraming salamat...Alam mo magaling din ang Prof.mo basta focus kalang sa pag aaral mo mag kaiba lang kami siguro ng strategy si Prof.mo.
May tanong lang ako halimbawa operated na ang FDAS nyo gusto ko mag dag2 ng isa pang device na crush alarm button at gusto kung pag push sa crush alarm button tutunog lahat ng bell sa bawat zone saan mag interconnect
ok po basta nakasama lahat ng bell dun naka parallel po cge.
Thanks po sa reply
Sir . Yung smoke detector ba . Dapat ba nasa zone 1 lang o pwd kahit saang zone . Pati na rin heat detector at manual push
kahit saan zone sir..salamat sa panunuod sa tutorial video ko po.
Ang Linis Mo Mag Demo Sir. Galing Naman. Wala Pa Yan Sir Nung Nag Aaral Ako Kaya Wala Ako Knowledge Sa Fdas. Boss May Diagram Bang Ibibigay Pag Mag Take Ng Assisment Sa Tesda? Pa Help Naman Po Sir Hehe. Gusto Ko Kc Mapag Aralan Yan. Tas Maka Kuha Ng Nc2
Meron po ibibigay yung SINGLE LINE DIAGRAM NG lang po .Panuorin nyo po yung PART-2:(EIM NC2) FIRE DETECTOR ALARM SYSTEM..meron dyan sa RUclips VIDEO ko po.kasama na pati yung Three Way Switch Installation po...e TYPE nyo PANGALAN ko Amon Lubiano sa RUclips CHANNEL ko po.ty.
@@amonlubiano1161 pano po yung diagram ng single line sir?
Panuorin mo yung mga video ko sa Building Wiring para malaman mo.Kung Ano ang SINGLE LINE DIAGRAM.
Sir napaka ganda ng inyong video training tungkol sa FDAS. Dati po akong Bumpero, Maaari po ba akong mag walk-in sa inyong Training Center or Shop upang magpaturo sa inyo ng personal tungkol sa EIM NC2 FDAS Installation, Inspection Testing and Maintenance?
pwede po kaya lang bawal pa sng face to face sa ngayon ang School ko po ay NATIONAL POLYTECHNIC COLLEGE OF SCIENCE SND TECHNOLOGY sa Quezon City Lagro po.....sa
sa ngayon Panuorin nyo lang muna mga Tutorial Video ko po ginagamit ko rin yan sa ONLINE CLASS ko po..e type nyo lang Pangalan ko sa RUclips Amon Lubiano Motor Control.para ma refresh po kayo.ty
Sir I really like your teaching could you please add English translation as your teaching is very practical
thanks for watching..yes wait for the translation.
@@amonlubiano1161 thank you soo much many appreciated
Salamat master may natutunan nanaman ako sayo sana po ma shot out moko salamat master
good sunday morning sir! musta po?bagong subscriber niyo po ako sir.
anong batch ka at school sakin engr..ok lang.
@@amonlubiano1161 St. john sir Batch 1997 night setion.
@@josenelsondelossantos3613 ah ok naalala ko na engr. mga working students kayo dati..sa GEMECO diba.
opo sir.. 5 kami ako sa battery group company, dalawa kami isa sa gemeco sir.
@@josenelsondelossantos3613 ah ok.saan ka ngayon engr.
Good day Sir, yung conventional fdas need ba ng configuration?
sir salamagt po s information,salute,,ask ko lng po sa isang zone pede b ikabit ung dalawang detector at push alarm bell, thanks EE elexer galvan batch 1989
pwede rin sir pero mas maganda parin kung susundin natin yung specificafion nya na bawat zone ay kanya2 detector ty po engr.
Tatay pwede po magtanong ano po purpose ng smoke detector.Saka strobe lights saka po push button.
Ang Smoke Detector ay Electronic Device na Sensor ng Usok at ito ay Ginagamit ng mga Industrial ,Commercial at Residential Building para Maiwasan ang Sunog kasi pag Na Sense na yung Usok Automatic na Tutunog Yung Alarm system, at SWITCH naman po yung Push Button at yung Strobe Light i Research mo nalang Sa mga Electronics books para alam mo kung saan palagi ginagamit cge idol
Sir may video kayo paano mag wiring ng conventional FALCON model EN54-2&4..saka SD na ang model ay ZEOS-C-S
@@tapowan wala pa idol cge
sana gawa ka po ng video sir...kung paano mag wiring at mag configure..
@@tapowan cge pag me time at yung equipments gamit dko dala cge
salamat malinaw po. tanong ko lang po. pag nagkabit na sa building. ano po standard na size ng wires, kailangan ba ipasok sa pvc pipe or metal tube. ano ba requiremnt ni BF?
Ang ginagamit ko #16 Stranded Dapat naka pvc pipe or metal tubing idol
@@amonlubiano1161 salamat sir.
Good Explanation Sir but can we have translation in English class
Thanks for viewing my friend wait for my English version explanation sir
Sir lahat po ng pinakikita nyo mga alarm at smoke detector nais ko po bilhin ng aking ma-install (DIY) saan PO lahat nabibili iyan sir? Tnx po Dan Tala chamba-chamba electrician ng pampanga
eto po.CONVENTIONAL FIRE ALARM CONTROL PANEL,,MODEL (YF-3) (YY/TYY) sa Santa Cruz Manila namin binili bandang kanan ng avenida diko po matandaan pangalan ng puwesto cge po
Kng kumpleto yn 5zone san mo llgy ang manual call point saka bell mg every zone?
Mag set up ka ulit ng ibang Panel engr.'ty
ilang smoke or heat detector at sounder po kaya ang kaya ng per zone ng fdas na dinedemo nyo po?
nasa specification naman per unit ng FDAS po kung ilan dapat ilagay ty.
Good day sir yung lahat pba Ng detector ay obligado pba na may end of line resistor
opo lahat ng zone meron po.
Sir pwede po na un breaker 60 amps sa 7000 watts.at ano po ang wire na ilalagay papunta sa unit na
Papunta sa computer mahine
Panuorin mo yung Residential House Design (single dwelling) para magkaroon ka ng idea tungkol sa mga Sizes of Wire, Breakers at Conduit na gagamitin mo pagdating sa mga Electrical Loads ty idol
Sir pwede bang pagsamahin Ang device sa fire alarm bell at smoke detector
hindi po pwede ang Design nyan ay yung Smoke Detector nasa Zone st yung Fire Alarm Bell ay nass Sounder Sundin po natin yun standard Wiring Installation ty po
Ser kahit walang resistor ok Lang sa conventional
hindi pwede kelangan meron resistor idol
Sir pag e on mo yung zone 3 manual call point tutunog ba yang sounder kahit di naka jumper sa sounder 3 kasi hangang sounder 1 lang ehh
opo kasama sa design nyan..Panuorin nyo yung PART-2(EIM-NC2)FIRE DETECTOR ALARM SYSTEM.....Type nyo pangalan ko Amon Lubiano sa RUclips Channel ko para mapanuod nyo lahat.ty po.
Pwd po mag request ng wiring connection din ng TYY brand na fdas yung addressable naman po
cge pag tapos na yung mga ginagawa natin ty
Pa add na rin ng request po kung paano mag address sa mga addressable na devices po. Maraming salamat po at akoy natututo sa mga videos nyo po. Gusto ko po kasi matuto ng fdas kaya nun napanuod ko yung video nyo po eh akoy napahanga at nasabik matuto ng fdas.
Sir good pm anu pong brand ng fire alarm yan salamat po?
CONVENTIONAL PO MODEL(YF-3) (YY/TYY) cge po sir
Hi sir hanggang ilang bell , heat detector , smoke detctor, and push botton switch ang kayang ilagay sa ganyang classe po ng fdas at kung ilang floor po ang kya if iaaply po sa house or building salamt po
kahit ilan basta yung pinakadulo dunmo ilalagay yung Resistor
Hi sir good day po ,,sir kailangan bang lagyan ng resistor bawat end of line?halimbawa po zone 1 po is smoke detector po may resistor po ba na ikakabit po? At sa SNDR po sir kailangan din ba laguan ng resistor? Salamat po sir....
opo kailangan meron lahat resistor kasama sa design nyan.ty idol
Last August 9 2024 po pala Eim Nc2 Assesment po namin sa written Exam at sa oral lang po ako nakapasa nyun po hindi po ako nakapasa nyun po sa actual dahil naabutan po ako ng oras dahil may timelimit po kasi ang pag install hindi ko po na tapos young ibang electrical devices sa pag install po reassesment po ako ulit young actual lang daw po e retake ko yun daw po sabi ng assesor at sana po makapasa na po ako sa aking reassesment!🙏
@@CyrilNoelFabracuer kaya mo nang ipasa yan kasi meron kna idea cge mag re exam kna habang fresh pa mind mo good luck idol
Thankyou po!🙏
I love your explanation sir.
* Ilang po ba Ang kaya sa isang zone sir? Salamat 😊
kahit ilan meron naman espicification bawat FDAS PANEL sir....
e type nyo lang Pangalan ko Amon Lubiano saYT channel ko kung gusto nyo mapanuod lahat video ko sir ty
Thanks sa reply sir. I appreciate it! Isasaulo ko po tong kaalaman galing sayo sir. Baka sa tesda meron course na ganito. Hehehe
Naka subscribe na po ako sir
Sir Yung lahat ba Ng zone ay pwedeng gamitin ang Isang sounder salamat po
pwede po.. pwede mo rin dagdagan ng sounder 2 kung gusto mo.
pwede pa i parallel sir ung alarm switch sa smoke detector?thankyou
pwede po sir mag parallel yung Manual push sw.at smoke detector..ilagay nalang po yung resistor sa eol cge po
Sir anong size sa resistor dapat gamitin nyan sa panel
Pag bumili po kayo ng unit ng FDAS andun po lahat ng SPECIFICATION po
SIR SAAN PO MABIBILI ANG FDAS? PARA MAPAG ARALAN KO NANG MATUTO PO AKO... I WILL FOLLOW UR RUclips DISCUSSING ABOUT FDAS (PART 1 & PART2) TNX PO DAN TALA CHAMBA-CHAMBA ELECTRICIAN NG PAMPANGA
salamat sa panunuod ng aking tutorial video sir.
Tnx...po Kung avenida lng nabili salamat po soon din po ako buy screw sa Tuesoy and some personal materials sa pagka chamba-chamba electrician ko, Subukan ko rin sa Mabalacat or Henson St. Angeles City salamat po sir
Pwede pala sa mismong terminal block ilagay ang mga resistor.
Pwede po pero pag dalawa o kaya tatlo, apat halimbawa sa ALARM duon mo ikakabit sa Pinakadulo na ALARM yung Resistor. Kaya ang Tawag dun EOL RESISTOR ty idol
Sir saan ikabit yong diode? Sa mcp o sa sdnr?
SDNR sa buzzer idol maraming salamat
Sir may resistors rin po bang naka parallel sa lahat ng sounder terminals? Pati na rin po ba sa mga zones na hindi ginagamit kailangan lagyan ng resistors? Thank you po sa pagsagot sir.
opo meron po lahat bawat Terminals salamat idol sa panunuod
May nabili akong alarm light na 12 Volts. Pwede po ba sa Panel na ganyan?
Basta mag ka parehas sa rated Voltage dc yan Unit Fdas mo idol
Tay pag may zone1,zone2 at zone3 po ako tas zone1 lang po ginamit ko pinarallel ko yung smoke detector at manual call point..kailanga poba may resistor lang talaga ang zone 2 at zone 3 kahit hnd naman nagamit or walang device na ginamit sa zone 2 at zone 3 nilalagyan papo ba talaga yan ng resitor yung dalawa
Kahit wala nang resistor yung mga Zone na hindi mo ginamit at walang naka kabit na device Yung meron lang Resistor ay yung Ginamit mong Zone at nakakabit sa Eol yung Resistor sa Pinaka Dulo ng ikinabit mong device ty idol
Salamat po tay napaka husay nyo po.... final asssessment kona po sa august 9,2023 sa e.i.m ilang beses kopo kau pinapanood ng paulit ulit napakahusay nyo po kuhang kuha po lahat turo nyo maliwanag po pagkakapaliwanag nyo po... salamat po sa inyo kahit papaano nakakuha ako ng another kaalaman
Maraming salamat din idol sa tiwala mo sakin kayang kaya mo yan practice kalang at mag dasal ka sa Panginoon makakapasa ka nyan Good Luck idol
Paano mag dag dag ng soke detector po sa isang zone
@@likha7528 pag nag dagdag ka ng smoke i dugtong naka Parallel Connection tapos tanggalin mo yung Resistor sa Terminal tapos Ikabit mo sa Pinakadulo na Smoke Detector naka Parallel Connection cge idol
Pwede ba yan pagsamasamahin sa isang zone ang mga device sir tulad ng hd sd mcp at iba pa?
pwede rin po.mas maganda parin kung sundin natin yung tamang standard wiring.ty
✌️✌️
thank you engr.
sir... tanong kolang po... bagohan lang po ako... ganyan din yung panel nmin sir kaso hang 3 lang na detector ang kaya nga system nmin every zone... nkaparallel connection poh... ano poh male don... salamat sa sagot...
wala naman mali dun nasa specification naman kung ilan ang pwedeng ikabit......baka yung resistor mo nasa panel parin...kapag 2 o mas marami kapang ikabit sa isang zone ilagay mo sa pinakadulo detector yung resistor po...
sir wla kasi stock dito saamin na batry na 24 ginawa nmin nlagyan nlang nmin na 24v transformer pang replace ng bat. kaso pag testing ko sa volts eh 34v yong out ng transformer eh makaapikto kaya yon?
@@lykamarieclairenemil7101 opo makaka apekto po gagana yung panel pero madaling uminit dahil sobra sa voltahe yan ang cause ng pagkakasira ng panel nyo po....sundin nyo nalang po yung specification nya.cge po
@@amonlubiano1161 sir pwede poba mangyari na hindi compatible yong panel atsaka smoke detector... kasi sa amin ytt yung panel nmin atsaka hindi ytt yong aming smoke detector... pag tenetest kona isa lang na smoke detectore ang kaya nya pag ginawa kong dalawang parallel ih mag alarm agad cxa...
possible po mangyari yun mas maganda kung iisang brand nalang gamitin nyo maam.
additional lang po...ang PANEL MUTE is pag off ng alarm sa panel....ang BELL MUTE is pag off sa alarm ng sounder. yun po ang kaibahan ng 2 mute...kapag ang SIGNAL HOLD DISABLE ay naka off or walang ilaw sa panel, kahit naka clear na po ang mga detectors at manual call point, tuloy tuloy pa rin ang alarm sa panel at sounder...at pag naka-on naman po ang ilaw ng SIGNAL HOLD DISABLE, once na mag-clear ang mga detector at manual call point, titigil na po ang alarm ng panel at sounder...ang DELAY DISABLE naman po ay ginagamit upang sa unang signal pa lang ng detector ay mag trigger na ng alarm ang panel at sounder. by default po, kasi hindi agad magti-trigger ng alarm ang panel upang ma-verify muna ng panel kung false alarm ang signal o hindi. after po ng ilang segundo, sa pangalawang signal ng detector sa panel, saka pa lang po tutunog ang alarm ng panel at sounder...
sa ganyan pong klase ng panel. Since conventional FDAS yan, gumagamit po yan ng CLASS B wiring at kailangan ng 10K ohms na resistor na pang END OF LINE at naka parallel connection sa dulong detector per zone. Pagwalang resistor, open circuit po ang lalabas sa panel…ganun din po sa mga sounder na nasa sounder terminal. In addition, kailangan din po ng IN4001 diode na naka series connection sa bawat sounder or bell upang hindi mag open circuit ang bell.
May DIP SWITCH po sa loob ng panel…during wiring and testing, kailangan naka ON po ang dip switch upang makakapag test kayo ng panel ng walang fault or error…and during operational na, kailangan i-off na ang dip switch upang makaka-detect automatic na ang panel kung sakaling may short circuit or open circuit bawat zone…
v.good detalyadong detalyado po klaro po salamat po sir.
@@amonlubiano1161 Salamat po sa pagbibigay nyo ng kaalaman sa FDAS...yung company po na pinapasukan ko ngayon ang distributor dito sa Pilipinas ng FDAS panel na ginagamit nyo...Ini-import po namin yan from Taiwan at ibinibenta dito...Kaya po nung napanood ko yung video nyo, natuwa po ako at nag-share na din ng info para dagdag kaalaman sa ibang viewers...salamat po at sana mas marami pa kayong maturuan na kababayan natin...
@@hyetechmaster maraming salamat din po sa additional info.sir.God Bless.
Sir tanong lang po pwede kaya mag splicing sa gitna kung magdagdag ng SD sa Z1
@@tapowan Pwede pag 2 SD na ang naka kabit ilagay mo yung Resistor sa Pinaka dulo SD. cge idol
Salamat sir
Sir ask ko lng po, pano po ang wiring diagram ng fdas kng ang mag,alarm po ay ung area lng na nka detect.
Ayan parin ang standard wiring or connection po idol
Sir anong wire po ang ginagamit mo ? Ty po!
size no.#18 po stranded po.
Nilalagyan po rin bah ng resistor ang end of line sir?
opo dapat lahat ng zone meron eol resistor...yung PART-2. FDAS. na video ko (Actual demo) nasa loob ng PANEL (FDAS) yung Mga Resistor Nakakabit sa mga Terminal bawat Zone,,ty idol sa panunuod.God Bless
kung gusto mo Mapanuod lahat ng Video ko i Type mo lang Pangalan ko Amon Lubiano sa RUclips Channel ko..ty ulit idol
Elow sir magkno po panel na yan
Meron po akong tanong, pwedi bang pagsamahin sa isang zone ang tatlong devices, smoke/heat/manual switch ano ang implekasyon nito sa panel.?
pwede naman po sir kaya lang mas maganda parin kung susundin natin yung Standard Specification ng FDAS po.thanks for watching
Sir tanung lang Po kung Ang zone 1 divece ay para lang ba sa sounder 1 device