PAGKAIBA NG (ADDRESSABLE )SA ( CONVENTIONAL) PAGDATING SA FIRE ALARM SYSTEM..

Поделиться
HTML-код
  • Опубликовано: 11 сен 2024
  • paano ba ang pagkaiba ng ADDRESSABLE SA CONVENTIONAL pagdating sa fire alarm system pinapakita ko lang sa vedio na ito kong san ba ang maganda CONVENTIONAL BA OR ADDRESSABLE.. salamat sa panonood sa video kona ito paki like.or subscribe. pag nagustuhan nio.. ang vedio kona ito ingat kau lagi kong san kau naroroon san mang sulok ng mundo mabuhay po tayong mga OFW.
    thanks for watching please like and subscribe:
    Copyright Disclaimer under section 1
    07 of the Copyright Act of 1976 allowance is made for "fair use " for purpose such as criticism comment, news reporting ,teaching, education and research.
    Fair use is a use permitted by copyright statue that might otherwise be infringing
    this is my youtube channel link:
    👇
    ruclips.net/user/ch...
    PLEASE FOLLOW MY FACEBOOK PAGE :
    👇
    / 183081473272155

Комментарии • 197

  • @emmanuellimjoco4709
    @emmanuellimjoco4709 3 года назад +6

    Iba talaga paliwanag kapag ka may actual experience ka sa site, I salute to people like you Sir..

  • @emmanuellimjoco4709
    @emmanuellimjoco4709 3 года назад +3

    Malinaw ang paliwanag mo Sir, the best ka talaga.

  • @decalibrejunior1353
    @decalibrejunior1353 Месяц назад

    Dami ko natutunan salamat idol

  • @acdcdiycircuits7069
    @acdcdiycircuits7069 2 года назад +3

    in 4:39 mark of the video, that's what you called SELECTIVE SIGNALING. This applicable especially for high rise building where the rule fire above and below of the floor notification appliances will only be activated. This to avoid stampede during evacuation. If not for this rule, in case of fire the whole building fire alarm bell and horn strobe activated simultaenously, then tenants of the building will evacuate at once which eventually caused stampede.

  • @arielmarapao1570
    @arielmarapao1570 3 месяца назад

    Thank you sir SA pag turo

  • @mennenbarredo5276
    @mennenbarredo5276 7 месяцев назад

    Mahusay klaro ang pag babahagi ng kaalaman, salamat madaming salamat

  • @arielescamillas7180
    @arielescamillas7180 3 года назад +2

    To add more info's sir, some other addressable brand like ZETA its loop wiring to all devices should be in reverse polarity, example in the base of detector L1 and L2 is negative and the common is positive.

    • @jub.tv123
      @jub.tv123  3 года назад +2

      Magaling kapa sir...salamat sa info mo...

  • @brothamacky2281
    @brothamacky2281 2 года назад

    Salamat kuya sa iyong mga turo bagong kaalaman sakin to

  • @arielescamillas7180
    @arielescamillas7180 Год назад

    General alarm sir Ang protocol sa lahat Ng fire alarm system Lalo nat iisang building..kung magkakahiwalay Ang building pero monitored by one panel pede rin izoning Ang alarm sounder especially sa mga hospital

  • @huanfriend8857
    @huanfriend8857 3 года назад +1

    Very good tutorial💖 watching iloilo tech

  • @decalibrejunior1353
    @decalibrejunior1353 Месяц назад

    Salamat idol

  • @jenwellnieves2274
    @jenwellnieves2274 Год назад +1

    Sir wala po kayong panel configuration 😊😊😊😊

  • @arifgani5326
    @arifgani5326 3 года назад +1

    What you speak is beyond of my mind please speak in English thanks Pare

  • @thereisalwaysaway6152
    @thereisalwaysaway6152 2 года назад

    Imformative ... Ty sir

  • @rickycustodio9752
    @rickycustodio9752 2 года назад +1

    Master,, may tanung po ako
    patingin po ako ng connection ng (addressable)sa loob po ng panel!
    Kung paano mo po na connect
    Sa mga temenal

    • @jub.tv123
      @jub.tv123  2 года назад

      Pasensya na sir wala na ako ngayon sa fire alarm sa construction na ngayon ang work ko..

  • @danieltayag9862
    @danieltayag9862 5 месяцев назад

    Ang galing

  • @JhemzVtv83
    @JhemzVtv83 3 года назад +1

    Nice one Master.. May natutunan na naman po ako... Ask lng Master pag addressable ba di na need nang EOLR....

    • @jub.tv123
      @jub.tv123  3 года назад +1

      Hindi na sir

    • @JhemzVtv83
      @JhemzVtv83 3 года назад

      Nice Master
      Sana yung actual naman na pag terminate nang addressable fdas....

  • @noelespireto3891
    @noelespireto3891 3 года назад

    thanks for the tutorial idol....

  • @hoowardluckidara3826
    @hoowardluckidara3826 3 года назад

    Salamat sa pagsagot sir,,pero sir diko talaga gets,,kasi close.system diagram With four smoke detector,,salamat sa sasagot,,god blz u always

    • @jub.tv123
      @jub.tv123  3 года назад

      sir diagram... lang na apat na devices yan pero innactual pwede ka magdagdag... yan ay reference mo lng.... gobless po sir at ingat lagi

  • @lawrencepaquinol1775
    @lawrencepaquinol1775 3 года назад

    salamat po sir sa tutorial nyu.

  • @apolinarioremescal3762
    @apolinarioremescal3762 3 года назад +2

    Sir gud pm po sa adresable po may nabangit nyo po na may balik sa positive sa huling smoke detector..saan po ba nakalagay sa panel ung balik na suply..

    • @jub.tv123
      @jub.tv123  3 года назад +1

      Don din sa terminal kong san nagmula ang wiring mo simula umpisa ang return ng wiring mo don din babalik yon..sir magkapit lang sir pisitive at negative lang din yan kasi may polarity

    • @apolinarioremescal3762
      @apolinarioremescal3762 3 года назад

      A ok po kala ko sa batery...salamat po sir...

  • @ronnelcastro5031
    @ronnelcastro5031 Год назад

    nice po master napakalinaw nio magpaliwanag..newbie sa fdas and new subscriber nio po..Master tanong lang po.
    1.Sa addressable loop po tawag?sa conventional naman po is Zone?
    2.Sa addressable po master no need na po ng resistor no?thank u po master sana masagot newbie lng po sa fdas

    • @jub.tv123
      @jub.tv123  Год назад

      Depende po kong nag kaka error pwde din po lagyan ng resistor kahit addressable...sya...pero sa conventional mostly may resistor po...

  • @rolandovelasco-by6im
    @rolandovelasco-by6im 7 месяцев назад

    Sir kaya po ako ako nagtanong dahil mag take po ako ng NCII ,Sana maipaliwanag po ninyo sa susunod ninyong blog.salamat po.

  • @john23miranda
    @john23miranda 3 года назад

    Ayos boss

  • @paanovlog3296
    @paanovlog3296 Год назад

    Ang addresable sir is loop wire ang nilalagay at sa conventional ang end nya ay EOL resistor tama po ba?

  • @arielescamillas7180
    @arielescamillas7180 3 года назад

    Ang addressable system ang pinaka madaling imaintenance, alam mo agad saan ang problema di gaya ng conventional maraming gala at tingala ang gagawin mo para makita saan problema.

  • @jubelnuestro6667
    @jubelnuestro6667 3 года назад

    Salmat kabayn

  • @fireprotectionguy7943
    @fireprotectionguy7943 Год назад

    Nice. Saan ang lugar mo. Why not mag-set up ka ng a day and I will lecture sa Pinas. Visiting Lecturer. You can invite all electrician and FDAS people. My other channel "Ako Sa Sydney"

    • @jub.tv123
      @jub.tv123  Год назад +1

      Dito po ako sa ibang bansa sir...sa HUNGARY

    • @fireprotectionguy7943
      @fireprotectionguy7943 Год назад

      @@jub.tv123 hahahaha...akala ko sa Pinas. Ingat Lagi.

  • @jub.tv123
    @jub.tv123  3 года назад

    Sa mga gostong pong humingi kong pano mag address ng fire alarm DEVICE na may depth switch paki lagay na lang po ng gmail acount sa may comment section at bibigyan ko.

    • @normandavid3398
      @normandavid3398 3 года назад

      normandavid294@gmail.com

    • @rambncle8850
      @rambncle8850 3 года назад

      Hello sir, paki suyo nalang po. "bhomar.bancale@gmail.com" . Thank you

    • @marlonsaraza2335
      @marlonsaraza2335 3 года назад

      New subscriber po pa hingi rin po ako idoll.. slamat po sa video tutorial nyo po..
      marlonsarazabinuya@gmail.com

    • @accetv.amv.anime.animation
      @accetv.amv.anime.animation 3 года назад

      asiadonhadz@gmail.com . Thanks lodi .

  • @reccakarl
    @reccakarl Год назад

    sa addressable fire alarm system po ba yun Bell at strobe light kailangan bang meron sariling power supply para gumana?

  • @retselzaracla5052
    @retselzaracla5052 2 года назад

    Sir ask ko din po kung pwedi ndi kana mag return, smoke detector to panel board at sa strobe light/alarm? salamat sir..

  • @liezlianetabag3558
    @liezlianetabag3558 Год назад

    Sa coventional sir sa issng zone. Pwed ba na mglagay ng tatlo hanggang apat na strove pero nka pararel lng

  • @carlkennethflores3697
    @carlkennethflores3697 Год назад

    Good pm po sir Jub, pede po bang ipagsama sa iisang loop ang Manual Pull Station, Alarm with Strobe Lights, Bell at Smoke Detector? Salamat po sa magiging kasagutan niyo po.

    • @carlkennethflores3697
      @carlkennethflores3697 Год назад

      Pahabol po pala. Yung mga components po ba para sa addressable ay hindi pede gamitin sa conventional FACP? Or Vice versa po. Salamat po ulit.

  • @rowelljamesmartin7942
    @rowelljamesmartin7942 2 года назад

    SIR PWEDE BANG ABOUT CONTROL AND MONITOR MODULE NAMAN ANG TOPIC.SALAMAT

  • @aranilosiningan4290
    @aranilosiningan4290 Год назад

    good evening ser,,,Ang addressable alarm bell niya kailangan May return talaga ser,, salamat po..

    • @jub.tv123
      @jub.tv123  Год назад

      Opo sir kasi kong sakali maputol sir sa gitna at kong sang parte man may signal parin po.....at supply parin boo parin

    • @aranilosiningan4290
      @aranilosiningan4290 Год назад

      @@jub.tv123 salamat Po ser,,bagohan lang po...palagi akong nag sobaybay sa mga video mo

    • @aranilosiningan4290
      @aranilosiningan4290 Год назад

      @@jub.tv123 good evening ser...may video kaba sa fire alarm intercom Kong paano mag wireng niyan,,,hintay Po ako sa sagot ser.. salAmat po..

  • @johnartalferez3888
    @johnartalferez3888 2 года назад

    mga bos paano sa zone -1 tatlong kwarto tigdalawa ang smoke detictor ilan po ba ang push botton?

  • @edwinicogo5022
    @edwinicogo5022 Год назад

    Sir ano ang mga factors para piliin mo ang one over the other? Thanks

  • @hoowardluckidara3826
    @hoowardluckidara3826 3 года назад

    Boss tanong kolang po,,ano po yung close and open system.sa smoke detector,,diagram,salamat po?,,

  • @retselzaracla5052
    @retselzaracla5052 2 года назад

    Sir, Ilang minimum ng Smoke detector ang pwedi sa isang MCP?

  • @buildlastvlog6426
    @buildlastvlog6426 3 года назад

    Sir kung tama po ako sa idea ko pwede ko pong i-convert ang wiring ng addressable sa conventional need ko lng lagyan ng Resistor dun sa dulo na bumalik sa panel salamat po sa pagsagot, 2nd question ko po sir pwd ba na hindi ko na palitan yung mga smoke na ginamit sa addressable kung i-convert sa conventional nlng salamat po

    • @jub.tv123
      @jub.tv123  3 года назад

      Nagka ka error din sir sa panel pag e convert mo ang addressable wiring sa conventional sir dapT pag addressable ay naka ring circuit sya

  • @robertbasijan8991
    @robertbasijan8991 2 года назад

    Good pm, sir pag wireless po ang gagamitin need parin poba ng program ng panel para sa smoke? Salamat sir god bless

  • @sarmientopepe6154
    @sarmientopepe6154 3 года назад

    Salamat

  • @jumelnonod6849
    @jumelnonod6849 3 года назад

    mkhang 24V yan sir.dalawa e😁

  • @apollofranza4410
    @apollofranza4410 2 года назад

    Sir, halimbawa magdagdag ako ng detector sa bandang gitna ng system?? mababaho ba lahat ng configuration sa mga susunod na detector??

    • @jub.tv123
      @jub.tv123  2 года назад

      Hindi namn mag babago yan sir pero e address mo sya... halimbawa last device mo ay 100 ang idagdag mo na address ay 101 102 103

  • @sirdenstv9747
    @sirdenstv9747 2 года назад

    sir meron kami main panel sa guard house tas mag iindicate dun kung anong planta ang may alarm ..yung isang planta d nag iindicate ng alarm .. ano po possible problem at pano wiring papunta sa panel sa guard house.. san po yun nakacconnect sa panel na nasa planta kung san may alarm . aning terminal ang nagbabato ng signal sa main guard house?? salamat po

    • @jub.tv123
      @jub.tv123  2 года назад

      Sir tanong ko muna ang device nio po ba na na d nag alarm may power po ba?at anong system po ng fire alarm nio?..

    • @sirdenstv9747
      @sirdenstv9747 2 года назад

      @@jub.tv123 meron naman po sir may naginspection po kase pero d ko nakita actual sabi nya d daw po nagbabato ng signal dun sa panel na nasa guard house may possible daw po may putol na wire papunta sa guard house ..san po kaya nanakonnect yung wire nung sinasabi nya ? or aling connection terminals yung irerewire ko?

    • @jub.tv123
      @jub.tv123  2 года назад

      Bakit walA po bang tagging?..

  • @jaysontalan2932
    @jaysontalan2932 Год назад

    Sir halimbawa po sa isang unit po meron na po sya naka abang na isang smoke detector tapos po dadagdagan po sya ng smoke detector, pano po gagawin sir sa panel, addressable po sya sir

    • @jub.tv123
      @jub.tv123  Год назад

      Sir nasagot kona po ang tanong mo sa fb. Page ko..

  • @markguibo3611
    @markguibo3611 3 года назад

    Sir sa addressable fire alarm system lahat na ba ng smoke detector.. Bell. Horn with strobe light.. Naka parallel lahat NG wiring connection??

    • @jub.tv123
      @jub.tv123  3 года назад

      Yes sir naka parallet at naka ring Ckt.

    • @markguibo3611
      @markguibo3611 3 года назад

      @@jub.tv123 pero sa loop 1 smoke detector lang lahat at sa loop 2 serin with strobe light lahat. At sa loop 3 heat detector at manual call point tama ba sir?

  • @emmanuellimjoco4709
    @emmanuellimjoco4709 3 года назад

    Boss, halimbawa po ihiwalay ko na sa circuit ng mga smoke detector yung manual call point. Pagsasamahin ko nalang sila puro manual call points halimbawa sa zone4, then separate circuit puro smoke detectors sa zone 1 at zone 2, kitchen area heat detectors sa zone 3. Pwede po ba iyon. Yung wala sila manual call point smoke at heat detector circuit

    • @jub.tv123
      @jub.tv123  3 года назад +1

      Wag mo pa hiwalayin sir isama mo parin ang smoke detector mo at sa manual call point mo at heat detector mo kasi baka wala kna mailagay sa terminal mo pag may another zone ka na idadagdag....

  • @reccakarl
    @reccakarl Год назад

    anong klaseng wire size po ba ang pwede gamitin sa Addressable Fire alarm? Pwede ba gamitin sa lahat ng detector at bell at facp iisang wire size?

    • @jub.tv123
      @jub.tv123  Год назад

      Hindi po sa mcp at SD 16 AWG. belden ang brand at sa BELL AT STROBE LIGHT 14 awg.

    • @reccakarl
      @reccakarl Год назад

      @@jub.tv123 yung bell po ba kailangan pa ng sariling power supply kahit nasa loop na?

    • @jub.tv123
      @jub.tv123  Год назад +1

      Deritso napo sa FACP panel kong malayo na pero kong malayo kailangan nio ng transponder..

    • @reccakarl
      @reccakarl Год назад

      @@jub.tv123 anong aparato po sa fire alarm loop yung kailangan pa ng sariling power supply? sounder po ba?

  • @juliushobbies8858
    @juliushobbies8858 3 месяца назад

    Sir ok lng po ba kahit d magkaka sunod sunod yong numbering ng mga devices??

    • @jub.tv123
      @jub.tv123  3 месяца назад

      Dapat sir magkasunod sunod para mabilis hanapin pag mag trouble shoot,

  • @bonilyn21
    @bonilyn21 10 месяцев назад

    Ok lng Po ba kahit Anong brand Ng smoke detector, heat detector,manual push button sa addresssable salamat sa sagot

    • @jub.tv123
      @jub.tv123  10 месяцев назад

      Recommended ko lang po sir yong mganda na brand ( seimens or simplex) ang brand subok napo namin yan...

  • @reycortez4738
    @reycortez4738 3 года назад

    Sir ilang oras magagamit ang back up battery if may power supply shutdown?
    Required din ba connect sa UPS ang FACP power supply?

    • @jub.tv123
      @jub.tv123  3 года назад

      Depende sa MAH. ng battery mo sir meang MILLIAMPS PER HOUR

    • @reycortez4738
      @reycortez4738 3 года назад

      Thank u sir for your very informative presentation.

  • @jaykicks23
    @jaykicks23 2 года назад

    Sir Pg ngpalit ng smoke detector kailagan pa ng programming ng new detector?

  • @marcianojrlofranco6234
    @marcianojrlofranco6234 3 года назад

    Sa conventional at addressable sir may resistor ba ung mga sd Nila sa dulo.

    • @jub.tv123
      @jub.tv123  3 года назад +1

      Mosrly ginagamitan ng resistor sir ang Conventioanal fire alarm system lang kasi hindi naka ring ckt. Ang wiring nya, kaya may EOLR

  • @diannecoderesninja5535
    @diannecoderesninja5535 3 года назад

    Sir nka seres ho ba yung line1 at line 2 ng zone 1 papunta zone 2. At ilang devices ang maximum sa zone 1

    • @jub.tv123
      @jub.tv123  3 года назад

      hindi sir individual dapat ang wiring...every zone.. sa device dapat 20 device lang every zone... para dka mahirap kag locate pag may trouble ang device mo

  • @junelofficialvlog.6762
    @junelofficialvlog.6762 Год назад

    Ang sa convensional class b wiring

  • @joselitopilien2073
    @joselitopilien2073 2 года назад

    Sir Jub ask ko lang, pwede ba sa isang loop magkakasama ang smoke det.,heat det, mcp at strobe/bell?

  • @diannecoderesninja5535
    @diannecoderesninja5535 3 года назад

    Hi po sir tanong ko lang po may polarity po ba yung fire alarm at bell?

    • @jub.tv123
      @jub.tv123  3 года назад

      mayron po sir kasi DC po yan ang red po ay + or positive ang - po ay negative...

  • @user-cr6mu5zq8f
    @user-cr6mu5zq8f 7 месяцев назад

    Hello po tanong ko lang po kapag addressable wala po sya end of line na may resistor ?

    • @jub.tv123
      @jub.tv123  7 месяцев назад

      Pwdeng wala na kong walablng error sa FACP

  • @anniedacles433
    @anniedacles433 2 года назад

    Boss poidi makangi ng klarong daigram ng addessables fire alarm? Ty and god bless

    • @jub.tv123
      @jub.tv123  2 года назад

      Message mko sa fb. Page sir JUB.TV don ko e send sayo

  • @bloodymary6704
    @bloodymary6704 3 года назад

    In addressable Fire Alarm system, what is the purpose of isolator base?

  • @weljosem9889
    @weljosem9889 2 года назад

    Paano ba boss mag configure sa address f ever magpalit ka ng new smoke detector sa addressable type na fire alarm?

    • @jub.tv123
      @jub.tv123  2 года назад

      Kailangan sir may pang program ka sa devices mo kong may depth swicth e setting mo lang syankong anong device no. Nya

  • @jhonerequejo374
    @jhonerequejo374 3 года назад

    Idol request nman pano mag disable ng detector?

    • @jub.tv123
      @jub.tv123  3 года назад +1

      Pag gosto mo e disable sir. Ang detector tanggalin mo sa sa termination at e connect mo ulit ang cable na tinanggal mo sa device para tuloy ang flow ng current tapos e delete mo sya sa panel para walang truoble na nakalagay don...

  • @CarlitoJrBayon
    @CarlitoJrBayon 2 года назад

    JUB. TV , sir meron kabang FB? meron sana akung tanung sir salamat

    • @jub.tv123
      @jub.tv123  2 года назад

      Mayron sir send mo email mo don ko ibigay sayo..

  • @raineriorentor6110
    @raineriorentor6110 3 года назад

    Master, kada floor ba katumbas non 1 loop? Para kada floor ay halimbawa 2 bell lang gagana

    • @jub.tv123
      @jub.tv123  3 года назад

      Pwde sir kong maliit lsng ang are mo,

    • @raineriorentor6110
      @raineriorentor6110 3 года назад

      @@jub.tv123 pero sa 1 loop po ba kung 3 bell sounder sa 1 loop, lahat Ung 3 sabay2 na gagana kc Sakop siya ng 1 loop?

    • @jub.tv123
      @jub.tv123  3 года назад

      Depende sa panel at sa pag program sir at kong anong brand ng FACP. MO

    • @raineriorentor6110
      @raineriorentor6110 3 года назад

      @@jub.tv123 ah ok po, Salamat sa reply master

  • @nitzmendoza3675
    @nitzmendoza3675 3 года назад

    sir doon po sa loob ng facp,khit saan po b...pde ilagay ung sd,s,mc...o my nkagay po sa loob ng facp kung saan lng pde ilagay...ty po

    • @jub.tv123
      @jub.tv123  3 года назад

      sir may ibang module ang sd.. sa id. net card pobyan naka connect and SD.

    • @jub.tv123
      @jub.tv123  3 года назад

      ang BELL namn or strobe light ay sa MODULE ng NAC. notification appliance circuit..

  • @joy-qo9rv
    @joy-qo9rv 2 года назад

    Sir ano po ginagamit n sensor sa kitchen?

    • @jub.tv123
      @jub.tv123  2 года назад

      Heat detector sir pag sa kitchen hindi pwde ang smoke kasi mausok po ang kitchen..

  • @lueescobia4601
    @lueescobia4601 3 года назад

    Sir pg sa conventional pg ng alarm si smoke detector mg alarm dn si bell, strobe??

    • @jub.tv123
      @jub.tv123  3 года назад +2

      Sir ang smoke d nag alarm yan..ang trabaho ng smoke ay to detect lang konh may usok...para maibato nya sa FACP. tapos tataas ang current saka mag alarm si bell at strobe
      ..

  • @molobologuys6112
    @molobologuys6112 3 года назад

    Boss bakit yong call point tenest ko nag fault sa panel pero hindi nag ring ang bell,tapos tenest ko ang smoke detector na kasama nya sa circuit nag eergized naman Bell ano ang problema doon boss.salamat sa sagot

    • @jub.tv123
      @jub.tv123  3 года назад

      Sir anong ba ang system ng fire alarm nio?..at ang tenest moba na mCP. isa lng sila ng loop ng Smoke detector na tenest nong nag activate ang bell mo?..

  • @rolandovelasco-by6im
    @rolandovelasco-by6im 7 месяцев назад

    Pwede bang i splice yong wiring ng addressesable

  • @aldrinymana9147
    @aldrinymana9147 3 года назад

    Kabayan pag convetional dba dpat may resistor sa end line ?

  • @norway5306
    @norway5306 3 года назад

    Sir ask ko lang kung pwede s una ilagy ang mcp kasunod nya yung smoke

    • @jub.tv123
      @jub.tv123  3 года назад +1

      wala ang problema sir kong San sa kanila ang mauna

  • @junelofficialvlog.6762
    @junelofficialvlog.6762 Год назад

    Yan ang class A wiring

  • @dx-hd2th
    @dx-hd2th 3 года назад

    Sir , paano po malalaman sa plano Kung ,Ang fda's ay conventional o addressable?

    • @jub.tv123
      @jub.tv123  3 года назад +1

      Malalaman po yan sir sa wiring ...pag naka ring ckt. Meaning addressable yan..tapos kong hindi naka ring ckt. Meaniing conventioanal yan.

    • @aldrinymana9147
      @aldrinymana9147 3 года назад +2

      Ang addressable may supply at return. ang conventional may endline with resistor

    • @jaimeignacio1240
      @jaimeignacio1240 3 года назад +1

      brod nakapagkabit kana ba ng ganyan..kac dtu ginagamitan ko ng CC1 yung sau wala aku nakikitang CC1..kac parang kulang..sorry brod nagtatanung lang..kapag addressable kac my CC1 dahil pinoprogram lahat na device sa FAP..

    • @jub.tv123
      @jub.tv123  3 года назад

      Sa skimatic wiring diagram sir malalaman mo kong conventional or adressable

  • @hoowardluckidara3826
    @hoowardluckidara3826 3 года назад

    Sir yung addressional yun ba yung close system diagram,salamat po,,

    • @jub.tv123
      @jub.tv123  3 года назад

      Ang addressable fire alarm system sir aay ang mga devices nya ay nakaprogram sya or naka address at naka ring ckt. Connection sya..ang ring ckt connection ay pag out nya ang last wiring wiring device ay babalik yan sa FACP. may return cya ..
      ang conventional namn sir aY d naka address. Ang deviceS at d naka ring ckt. Pero ang last na wiring mo ay may END OF LINE RESISTOR SIR ..

    • @hoowardluckidara3826
      @hoowardluckidara3826 3 года назад

      San po sir sa kanila ang close system diagram sir?

    • @jub.tv123
      @jub.tv123  3 года назад +1

      Ang addressable sir

    • @hoowardluckidara3826
      @hoowardluckidara3826 3 года назад

      @@jub.tv123 thank you sir,,gud blz you sir,,

  • @bobbylubos3089
    @bobbylubos3089 3 года назад

    Sir ask ko langpo kung naka experience na po kayo ng unprogrammed device data lumalabas sa HMI. Ano po kaya problema pagganito?

    • @jub.tv123
      @jub.tv123  3 года назад

      anong klase ba ang fire alarm system nio sir at anong brand Ng device nio?

    • @bobbylubos3089
      @bobbylubos3089 3 года назад

      @@jub.tv123 sir EST3 na brand po addressable nmn po

    • @jub.tv123
      @jub.tv123  3 года назад

      sir try mo tanggalin at e re program mo ang device kong ganun parin try mo palitan and device...

    • @bobbylubos3089
      @bobbylubos3089 3 года назад

      @@jub.tv123 noted po. Reprogram meaning ulitin ko po magassign ngmga address?

    • @jub.tv123
      @jub.tv123  3 года назад

      korek po sir baka defective na po ang device at d nya nabasa pag program.. try mo palitan ... marami po ba ang device nio na ganyan... at baka ang panel mo at device mo ay mag kaiba Ng brand...

  • @user-os3su9kj8o
    @user-os3su9kj8o 11 месяцев назад

    Sir pag may module po saan po lalagay yung module?

    • @jub.tv123
      @jub.tv123  11 месяцев назад

      Sa loob po ng FACP PANEL sir..

    • @user-os3su9kj8o
      @user-os3su9kj8o 11 месяцев назад

      @@jub.tv123 sir pwde ba yun addressable yung mga module tas yung mga sd conventional?

  • @jonathantalirongan3830
    @jonathantalirongan3830 3 года назад

    Anong device ang e install sir para mag function ang splinkler ng tubig?

    • @jub.tv123
      @jub.tv123  3 года назад +1

      flow switch.. po sir mayron. po . sa springler yan na thermal operating element. normally fusible links or glass bulbs.. na kong sakaling may sunog maabot nya ang temperature yan ay mababasag ... at mag spray Ng tubig ang springker mo or foam....

    • @jonathantalirongan3830
      @jonathantalirongan3830 3 года назад

      Ahh ok boss...salamat

    • @jonathantalirongan3830
      @jonathantalirongan3830 3 года назад

      May video ka nyan boss?

    • @aldrinymana9147
      @aldrinymana9147 3 года назад

      Gamit nmin module sa supervisory ay DCM4 o duel Contact pra flow switch at tamper switch

  • @lhanlhanantonio2462
    @lhanlhanantonio2462 Год назад

    Idol ano po trabho nyo bakit pati electrical hawak mo

    • @jub.tv123
      @jub.tv123  Год назад +1

      E & P ako sir electrical at instrument po sir...

    • @lhanlhanantonio2462
      @lhanlhanantonio2462 Год назад

      Ok sir salamat andito ka ba ngayon sa saudi gusto ko Sana lumipat sa electrical nasa piping kase ako ngayon gusto maka pag experience ng instrument Sana graduate po ako ng electrical technology

  • @markangeloremot4392
    @markangeloremot4392 3 года назад

    ano boss meaning ng mcp? hehehe thanks boss

    • @jub.tv123
      @jub.tv123  3 года назад

      Manual Call point po..ang mcp...pag sa ilaw sya ang switch mo

  • @Rizwanahmad-cv4zl
    @Rizwanahmad-cv4zl 2 года назад

    Bhai aap Language translate kre Hindi ya English me ,ok plz

  • @raymondcatamora5282
    @raymondcatamora5282 3 года назад

    Nakaprogram din ba ang convincional

    • @jub.tv123
      @jub.tv123  3 года назад

      Alin ang tinatanong mo sir ang naka program ang conventional ang device ba? Kong ang device hindi... ang naka program lang kong device ay addressable na device.. lang....

  • @manuelmendez5148
    @manuelmendez5148 2 года назад

    sir bakit po nag biblink ang indicator Ng zone 3

    • @jub.tv123
      @jub.tv123  2 года назад +1

      San po nag bliblink..sa facp ba sa monitor? Ano ba ang conventiional ba or addressable?..

    • @manuelmendez5148
      @manuelmendez5148 2 года назад

      Sa monitor po.addressable po

  • @renatopat-ongay1831
    @renatopat-ongay1831 3 года назад

    Pwde po bang mas malinaw tong diagram pls...

    • @jub.tv123
      @jub.tv123  3 года назад

      drop po kau ng gmail...para mabigyan kita ng malinaw na diagram..

    • @renatopat-ongay1831
      @renatopat-ongay1831 3 года назад

      K sge po... At saka may tutorial video ba ng actual nito?

    • @jub.tv123
      @jub.tv123  3 года назад

      gagawa palang po sir....

    • @renatopat-ongay1831
      @renatopat-ongay1831 3 года назад

      Ko po abangan ko po sir...

    • @jub.tv123
      @jub.tv123  3 года назад

      cge po

  • @jezzjimez9472
    @jezzjimez9472 3 года назад

    Tadtad sa ads.. sobra namn ung ads..

  • @kawtskagid1198
    @kawtskagid1198 3 года назад

    Sir,ano po dahilan,palaging umiilaw Ang Fire Alarm Ng isang zone Ng panel, palaging mg ring Ang bell pag e switch on ko

    • @jub.tv123
      @jub.tv123  3 года назад

      Sir try mo palitan yan defective na yan sir ang device mo...

    • @kawtskagid1198
      @kawtskagid1198 3 года назад

      @@jub.tv123 Ang sign na fire alarm sa FACP Ang umiilaw,Di Ang device..pinalitan ko na Ang mga devices sa zone na Yun,nilinis kopa baka may alikabok,,mgtrigger talaga sa panel

  • @glomanpanaligan5694
    @glomanpanaligan5694 7 месяцев назад

    Sir location mo

    • @jub.tv123
      @jub.tv123  7 месяцев назад

      Nasa HUNGARY po ako sir sa ibang bansa,❤️❤️

  • @charliekurtantiquera476
    @charliekurtantiquera476 3 года назад

    Sir, paano po mag Program? Tnx

    • @jub.tv123
      @jub.tv123  3 года назад +1

      ano e program mo sir device Ng fire alarm or ang fire alarm panel

    • @charliekurtantiquera476
      @charliekurtantiquera476 3 года назад

      Yung FACP po sana sir. Hehe

    • @jub.tv123
      @jub.tv123  3 года назад +1

      kailangan Ng laptop yon sir... e connect mo sa FACP... saka mo e program... ang no. Ng devices mo at location nya at aNg looping Ng alarm... kailangan tama ang pag program Ng device mo halimba notification... kgaya Ng detector device smoke or mcp. tapos yon alarm. BELL or strobe light..

    • @charliekurtantiquera476
      @charliekurtantiquera476 3 года назад

      May ma rerefer kabang manual sir or Tutorial din po?

    • @jub.tv123
      @jub.tv123  3 года назад

      pag nag program na kmi sir... sa ngayon wala kami gawa sa fire alarm ang pag address lng Ng may depth switch ang mayron ako.....

  • @gerundionangel7293
    @gerundionangel7293 2 года назад

    Salamat sir sa pagtutoro