How to Reduce Earth Resistance | Earthing Resistance | Electrical Safety| Hindi

Поделиться
HTML-код
  • Опубликовано: 25 окт 2024

Комментарии • 71

  • @vijaybhanushali1638
    @vijaybhanushali1638 10 месяцев назад +1

    Sir you have explained very good way,
    But I would like to add my views,if you connect copper plate at the bottom of earth electrode you will get better Earth

  • @VijayKumar-oq9kx
    @VijayKumar-oq9kx 6 месяцев назад +1

    Sir mujhe bataye ki agar 3 phase supply me 2 phase me tester glow kar rha hai 1 phase me glow nhi kar rha hai magar motor ke pass multimeter me voltage proper 415 aa rha hai

  • @ali-tj7zf
    @ali-tj7zf 3 года назад +4

    Nice explanation. Can we connect transformer and generator neutrals earth's together? Also can body and neutral earth points can be connected together?

  • @bhagyamishra8522
    @bhagyamishra8522 Год назад

    Kya earthing pit me Bentonite powder used karna sahi he please suggest

  • @dheerajupretiuk0691
    @dheerajupretiuk0691 Месяц назад

    Sir earthling parlal hoti hai ya series

  • @sukhwindersinghsinghboy8461
    @sukhwindersinghsinghboy8461 3 года назад

    Sir your video very informative for me

  • @pankajmishra43
    @pankajmishra43 Год назад

    Is that compulsory to measure earth resistance after shutting down of entire system??

  • @gauravpant5154
    @gauravpant5154 Год назад +1

    Sir please tell what is happening when earthing resistance is coming 6ohm but earth to neutral voltage is coming 0.3 volt

  • @kapilkalangutkar4749
    @kapilkalangutkar4749 Год назад

    How to measure Earth pit resistance using clampmeter. Abhishek joshi ji pls prepare video on this.

  • @ishwarpatel620
    @ishwarpatel620 Год назад

    Sir 1 earth pit PE kitna equipment ka earthing laga shakte hai?

  • @ourcutelittlekitchen1338
    @ourcutelittlekitchen1338 9 месяцев назад

    The standard earth practice as per IE rules.
    Copper plate of 3mm thick (2ft x 2ft) connected to Copper strip 25x5mm thick at a depth of 10 feet and put 5 kg salt and 25 kg charcoal around the plate.
    2) For GI plate earthing. Use GI plate of 6mm thick of 2ftx2ft and GI strip 25x5mm.

  • @ssinghrajput7626
    @ssinghrajput7626 3 года назад +2

    Induction motor me leading lagging power factor
    Improvement kaise hoga

  • @niranjangupta7806
    @niranjangupta7806 3 года назад

    Very well explained!

  • @HarpreetSingh-dc3dh
    @HarpreetSingh-dc3dh Год назад

    Please make a video on " how to measure step and touch potential"

  • @manjitkumarpradhan7257
    @manjitkumarpradhan7257 Год назад +2

    Sir hamara company me ekk earthing ka resistance pehele 2.something aarahatha,
    Lekin abhi 5.something aarahahe ookese

  • @prashantkharva4527
    @prashantkharva4527 3 года назад +3

    Sir phase sequence change hone pr breaker ON kyon nahi hota

  • @digitalcreator1793
    @digitalcreator1793 5 месяцев назад

    Siiir....in this May month... So hot days.....In our electrical MCC, PCC panel, R Y B N busbar all working as phase 😮😮😮...
    How ??? What to do proper details please.
    Neutral busbar became phase supply...
    Someone said daily 24 hours water 💦 filling in all earthing pit in MCC, PCC panel..
    But. Still Some times its showing phase in neutral busbar 😮😮?????
    Please suggest me

  • @wasimsharif8242
    @wasimsharif8242 2 года назад

    Excellent

  • @madansharma5201
    @madansharma5201 2 года назад +1

    Thank u so much sir

  • @sanaparveen9642
    @sanaparveen9642 7 месяцев назад

    Sir electricity bord se 3 phase and neutral supply aati hai or hamare building me single phase ki tarh use hoti hai but tino phase k wire and neutral wire same size ka hi Aisa q
    Agr har phase me 5 amp current flow ho rah hi to neutral wire me 15 amp current flow hota hoga to neutral wire mota hona chaie .
    Yahan system to single phase ki tarh use hoara hai to system to unbalance hai yahan koi 3 phase motor to nahi chal rahe hai system balance ho or neutral me koi current nahi flow horaha . To neutral wire mota q nahi hai plese help.

  • @bhaskarpakhira8253
    @bhaskarpakhira8253 Год назад +1

    How to reduce earth electrode

  • @શ્રીમારૂતિનંદન

    11kv se hum kitana. kw load use kar sakte ha

  • @ramkailashnishad5429
    @ramkailashnishad5429 2 года назад

    Sir
    Abhi mere site me transfer k pas pdb me neutral between earth below 2volt aa rha hai but aage plc panel me above 5volt ja rha hai kya reason ho skta hai vahan pe neutral ko direct earth krk dekh liye

  • @zayansiddique7308
    @zayansiddique7308 3 года назад

    Earthing bore 20 feet length hai aur Mai ghaR Ka load ChalaNa Chahta hoon Earth with phase possible hai long time k Liye.

  • @akashmuley3116
    @akashmuley3116 3 года назад

    Sir is there any standard to choose electrode length.

  • @ronirajput1366
    @ronirajput1366 3 года назад +2

    Sir aap meri ek help kardo plz muje ye bata do ki humhare liye electrical ki konsi book sahi rahegi jime hume sab mile padne ko sir plz aap comment ya koi video bana k hum sab ko bata do 🙏🙏🙏🙏🙏🙏

  • @Magicworkfast
    @Magicworkfast Год назад

    After doing 2 good earthing also my earthing value is 6.. tried all the best way for my industry.. wat to do now plz help out.. my machine need below 1V .. is it possible to bring this value by isolation transformer??

    • @prvnpareek
      @prvnpareek 11 месяцев назад

      Have found any solution.then plz share me...

  • @gauravpant5154
    @gauravpant5154 Год назад

    Sir please tell the difference between earth resistance and earth voltage

  • @sunmitraresources9641
    @sunmitraresources9641 2 года назад

    Sir
    We are working in Solar industry. As our co. directed us to keep min. distance between 2 earth pit must be equal to rod size. Why ?
    You are saying interconnect all pit will reduce earth resistance.
    Then what is meaning of keeping distance in 2 earth pit?

  • @AnilAutomation
    @AnilAutomation 3 года назад +1

    #anilautomationhindi
    Nice explan dear 👌

  • @manojku259
    @manojku259 2 года назад

    Sir can you please explain droop CT and AVR to exciter to field exciter tak..

  • @SM10170
    @SM10170 3 года назад

    Sir is there any vacancy in birla group

  • @ssinghrajput7626
    @ssinghrajput7626 3 года назад

    Sir exam ke point of view se
    Scr ke bare me btaye

  • @afaqarif9269
    @afaqarif9269 3 года назад

    Sir, please make a video on Booster transformer.

  • @hindistorylmvoice222
    @hindistorylmvoice222 Год назад

    Earth to Neutral :- Multimeter ko continuity mai rak kar check kare to earth to neutral short hona chahiye or open.

    • @magneshpatel5137
      @magneshpatel5137 10 месяцев назад

      Grounding k sathe short and earthing k sathe open

  • @lalitgolhar8689
    @lalitgolhar8689 3 года назад

    Sir different types of earthing system par video baniya TN-S , TN-C, TNC-S and TT earthing system

  • @arvindkumarpal6124
    @arvindkumarpal6124 8 месяцев назад

    If length increase resistance also increase

  • @ramansen4812
    @ramansen4812 3 года назад

    Sir Plc ya dcs se related video banao

  • @GautamSaini-o8q
    @GautamSaini-o8q Год назад

    We need to make earthing grid please help

  • @lonelyplanet9077
    @lonelyplanet9077 2 года назад

    Sir could you please elaborate causes of more voltage btw nutral to earth as I tested I found 60 volt btw nutral and earth.....

  • @dgvclgebgetco7032
    @dgvclgebgetco7032 2 года назад

    7 sr 10 relay keshe kam karti he or kahape lagatehe or konkonsh opshan aatahe

  • @zainzain8045
    @zainzain8045 2 года назад

    My 7ft copper rod is giving 140 ohms how can I down it

  • @shahlalkhan4402
    @shahlalkhan4402 2 года назад +1

    Sir jee diffetent earhing standards k nam aur us me resistance ki.max. allowable limits jo ho te hain explain please

  • @ganeshsahu5039
    @ganeshsahu5039 3 года назад

    Hello sir
    Power plant synchronize and how to work AVR
    Please sir make video on this 🙏

  • @m.l.gambhirgambhir2549
    @m.l.gambhirgambhir2549 2 месяца назад

    👍

  • @diwakardubey3003
    @diwakardubey3003 2 года назад

    👌

  • @vikashvishvakarma465
    @vikashvishvakarma465 3 года назад

    Sir drawing bhi bataye

  • @adityamaurya3678
    @adityamaurya3678 2 года назад

    Yes sir

  • @jaypatel3669
    @jaypatel3669 3 года назад

    Sir,how we find
    standard equation for choose cable size rating (amp). copper & alluminium cable.
    For example 1 mm2 cu cable take load approximately 6 amp.
    Please sir help me.🙏

  • @deeptalati3851
    @deeptalati3851 3 года назад

    One que :
    How much minimum current or voltage is required to initiate or catch a fire ???
    Any thumb rule ?

  • @safiurrahaman5836
    @safiurrahaman5836 Год назад

    Be age to bol

    • @satyajitnayak1566
      @satyajitnayak1566 6 месяцев назад +1

      Bhai Saab behave toh acha krlo free me sir knowledge de rye hain so please behave properly.

  • @akhtermahmudabadi5543
    @akhtermahmudabadi5543 2 года назад

    مجھے ارتھ کی پاور بڑھانا ہے تو کیا کروں وہ پہلے سے کم ہو گئ ہے