Distribution db box wiring diagram

Поделиться
HTML-код
  • Опубликовано: 18 сен 2020
  • A distribution board DB is where the electrical supply is distributed from within the building home. The main supply cable comes into the board and is then distributed to the breakers and from there to all the circuits lights fan plugs etc. various sizes of distribution boards are available.
    Miniature Circuit Breaker (MCB) automatically switches off electrical circuit during an abnormal condition of the network. means in overload condition as well as faulty condition. nowadays we use an MCB in low voltage electrical network instead of a fuse MCB is much more sensitive to over current than fuse.
    Residual Current Breaker (RCB) works on the assumption that the current going to the electronics device must come out from the neutral wire if there is no other way for current flow. In simple words RCB measures the current going inside the connected device and coming out from the device.
    THANK`S FOR WATCHING THIS VIDEO
    PLEASE LIKE COMMENT SHARE AND
    SUBSCRIBE THIS CHANNLE
    / @jrelectricschool
    intermediate 3 way switch wiring diagram
    • intermediate 3 way swi...
    how to control a fan from two places
    • how to control a fan f...
    godown wiring connection diagram video
    • godown wiring connecti...
    solar inverter connection diagram
    • solar inverter connect...
    three phase motor run single phase line
    • three phase motor run ...
    single phase motor control from two places
    • single phase motor con...
    star delta starter control wiring diagram
    • star delta starter con...
    inverter wiring connection
    • inverter wiring connec...
    float switch connection auto & manual
    single phase water pump
    • float switch connectio...
    automatic changeover switch for generator
    • automatic changeover s...
    reverse forward dol starter control wiring
    • reverse forward dol st...
    electrical hand tools
    • electrical hand tools
    electrical house wiring full video
    • electrical house wirin...
    full house wiring diagram gang switch
    • full house wiring diag...
    float switch wiring diagram for water pump
    • float switch wiring di...
    split ac wiring diagram indoor outdoor single phase
    • split ac wiring diagra...
    star delta connection 3 phase motor diagram
    • star delta power wirin...
    complete electrical house wiring diagram
    • complete electrical ho...
    house wiring single phase energy
    meter with light fan connection
    • house wiring single ph...
    3 phase distribution DB box wiring diagram
    • 3 phase distribution D...
    ELECTRICAL HOUSE WIRING WITH
    SWITCH BOARD CONNECTION
    • ELECTRICAL HOUSE WIRIN...
    Two Way switch Connection with light
    electric animation video
    • Two Way switch Connect...
    house wiring electrical switch
    board connection diagram
    • house wiring electrica...
    Submersible Motor Control Box Connection
    • Submersible Motor Cont...
    DOOR BELL WIRING DIAGRAM MULTIPLE
    SWITCH AND SERIES LAMP
    • DOOR BELL WIRING DIAGR...
    reverse forward dol starter power wiring
    • reverse forward dol st...
    single phase mcb distribution
    db box connection diagram
    • single phase mcb distr...
    Music in this video
    Song: Erik Lund - Tokyo Sunset (Vlog No Copyright Music)
    Music promoted by Vlog No Copyright Music.
    Video Link: • Video
    Keyword:
    Distribution db box wiring diagram
    single pole mcb connection
    mcb fitting in box
    mcb box connection
    3 pole mcb connection
    4 pole changeover switch wiring
    single phase changeover connection
    3 phase distribution db box wiring diagram
    mcb box connection in bangla
    mcb connection in tamil
    legrand distribution board
    circuit breaker
    rccb wiring connection
    rccb wiring connection
    schneider electric contactor
    contactor working animation
    contactor no nc connection
  • НаукаНаука

Комментарии • 94

  • @tayssirnassar8113
    @tayssirnassar8113 Год назад

    ottimo lavoro complimenti grazie 🌹🙋‍♂️💯👍

  • @EvergreenJSR
    @EvergreenJSR 3 года назад +5

    Wow,,,excellent teaching quality 👌

  • @danielteyehuago1633
    @danielteyehuago1633 3 года назад +2

    Thanks for sharing it with us

  • @t.is.m5470
    @t.is.m5470 Год назад

    I encourage you

  • @electrician-80000k
    @electrician-80000k 9 месяцев назад

    Mein Dharmendra Kumar electrician aapka video bahut achcha Laga abhi message likh khuda se bhejiye

  • @Frank-vs4op
    @Frank-vs4op 2 года назад +6

    Thank you but where is the E-earth?

  • @hassanmuaaz7518
    @hassanmuaaz7518 Год назад

    So every room again can put db

  • @sachinmagdum
    @sachinmagdum 27 дней назад

    Which diagraming tool do you use?

  • @Pgan803
    @Pgan803 Год назад +2

    Good Video but some items missing like Earth Bar/Cable. Can you do another similar Video using Single Pole MCB, as a comparative DB settings

  • @ashrafkarjiker6888
    @ashrafkarjiker6888 8 месяцев назад

    Where do you get this software simulator

  • @eliasgomespereira5711
    @eliasgomespereira5711 3 года назад +3

    Top

  • @ziyanshaikh2968
    @ziyanshaikh2968 2 года назад +1

    Very good and funny videos bring a great sense of entertainment!

  • @ShoukatAli-qi5gy
    @ShoukatAli-qi5gy 2 года назад +1

    Good job

  • @gamingwithsoul9475
    @gamingwithsoul9475 4 месяца назад

    Sir will you give materials required for this

  • @shefalyrahman2648
    @shefalyrahman2648 3 года назад +2

    ❤❤

  • @user-zv6tb3xn2i
    @user-zv6tb3xn2i 2 года назад +1

    Super🤘😝🤘 fantastic🤘😝🤘

  • @Ajitbabusurya
    @Ajitbabusurya Месяц назад

    Good bhai

  • @user-cj5ls4wx3z
    @user-cj5ls4wx3z Год назад

    احسنت

  • @adriatikmerko9110
    @adriatikmerko9110 2 года назад

    have a look again the main swich

  • @OMELECTRIC
    @OMELECTRIC 3 года назад +1

    Super sir

  • @sreejithsreekumar5958
    @sreejithsreekumar5958 3 года назад +5

    Which software are you using to draw the electrical diagrams?

  • @stinky2202
    @stinky2202 10 месяцев назад

    Is this guy for real? 😂

  • @ovieoyegwa6153
    @ovieoyegwa6153 5 месяцев назад +2

    Connection from input MCB to RCBO is not correct. This is a reverse connection. The correct connection should be from MCB output below to the 1 position on the top of the RCBO which is the Line in and N above which is the Neutral in, then 2 position on the RCBO which is the Line out and N below for Neutral out. Connection from RCBO should be from 2,N position to the input of the 20A breakers from top position and output from below the breakers to Load

  • @JackRipper8881
    @JackRipper8881 2 года назад +7

    Three 20 amp RCB's fed through a 40 amp RCBO? Nope. That's a total of 60 amps. RCBO's need to be wired correctly and this is wired in reverse. You will damage the RCBO. There is a reason they numbered it 1 and 2 on the L connection.

    • @Pgan803
      @Pgan803 Год назад +2

      I see only 1 Main Switch, 1 RCD and 3 nos - 2 pole MCB. No RCBO.

  • @patelhbk7580
    @patelhbk7580 Год назад

    Mcb me niche se input ate hai...mere kyal se...or rccb me input upr se hote hai...

  • @ghazanfarabbas5927
    @ghazanfarabbas5927 3 года назад +1

    Brother kindly share standard method because we are learning from your channel a lot and we don't want any time pass wiring

  • @lookatsaudiarabia1393
    @lookatsaudiarabia1393 Год назад +1

    ধন্যবাদ

  • @MikeTuason
    @MikeTuason 3 года назад +1

    What is the Hyundai breaker for?

    • @JrElectricSchool
      @JrElectricSchool  3 года назад +2

      for electrical safety

    • @MikeTuason
      @MikeTuason 3 года назад

      @@JrElectricSchool Could you please be more specific as I am not familiar with this set up. What kind of breaker is it?

  • @rahmanatish5608
    @rahmanatish5608 3 месяца назад

    You made good vedio
    but you miss some point such bright light Nbb and not give the name to every one

  • @my.1filp706
    @my.1filp706 2 года назад +1

    My dear sir you have to explain vocally the connection of db box wiring

    • @JrElectricSchool
      @JrElectricSchool  2 года назад +1

      i will try to make video on your topic.
      Thank you.

  • @RajeshKumar-ih6og
    @RajeshKumar-ih6og 2 года назад

    Sir kya singal phase se out put 3 load le skte h kya

  • @elsogoncalves5345
    @elsogoncalves5345 3 года назад +1

    Good night
    whats user software

  • @jawardjususaffa3572
    @jawardjususaffa3572 3 года назад +1

    I love

  • @muhdhamdi2054
    @muhdhamdi2054 2 года назад +3

    why don’t you connect the neutral wire to the terminal busbar ?

    • @Pgan803
      @Pgan803 Год назад

      He uses 2 poles MCB so no Neutral Bar needed. I did not see an earth bar/cable though

  • @MrDefour
    @MrDefour 2 года назад +1

    Is it no problem if the input RCCB from bottom ?

    • @Pgan803
      @Pgan803 Год назад

      I understand input and output can be either bottom or top to suit.

  • @madspiritgaming6132
    @madspiritgaming6132 Год назад +2

    This is wrong connection...phase always right...and connect input to the bottom...

  • @snsumonmondol8121
    @snsumonmondol8121 Год назад

    সার্কিট ব্রেকার এর আউটপুট উপর দিয়ে হবে

  • @mpalikurikkalthamarasseri3541
    @mpalikurikkalthamarasseri3541 Год назад +1

    മ്യൂസിക് ഒഴിവാക്കികൂടെ ?

  • @patelhbk7580
    @patelhbk7580 Год назад

    Mcn input on bottom output top
    Rccb input on top and output in bottom...

    • @IAmThe_RA
      @IAmThe_RA Год назад

      Different countries different electrical codes

  • @sathviks7805
    @sathviks7805 3 года назад +1

    First mccb or rccb ????

  • @evilgenius4368
    @evilgenius4368 Месяц назад

    SIS

  • @sumudurasanjana3633
    @sumudurasanjana3633 2 месяца назад

    1 no shows Inputs... you conected the input line to no 2 of RCCB

  • @umerumerfarooq3769
    @umerumerfarooq3769 2 года назад

    room ke mean ha

  • @evilgenius4368
    @evilgenius4368 Месяц назад

    Sis

  • @Fr.VeniceLAI
    @Fr.VeniceLAI Год назад

    Hey, this is incorrect. What country standard is this ??

  • @user-yd5we5oq1v
    @user-yd5we5oq1v 2 года назад

    Не правильно. В УЗО вход сверху . А снизу идёт на нагрузку

  • @tommylobaton977
    @tommylobaton977 3 года назад +1

    Pano naging wrong connection yan brod
    Paliwanag moh nga

    • @JrElectricSchool
      @JrElectricSchool  3 года назад +1

      sorry i am not understand your language
      please tell me Bangla Hindi English.
      Thanks for watching

  • @madath123
    @madath123 8 месяцев назад

    where is earth?

  • @AshishSrivastav1
    @AshishSrivastav1 3 года назад

    RCCB 40 amp ki kyu jab Mains 63 ka hai? Aur MCB total 60 amps ki.

    • @patelhbk7580
      @patelhbk7580 Год назад

      Jo load hai wo mcb me hota hai is liye

    • @AshishSrivastav1
      @AshishSrivastav1 Год назад

      @@patelhbk7580 Galat.. agar ampere rating hai to iska matlab load bhi utna hi hoga. Ye galat Calculation lagai bhai ne.

    • @patelhbk7580
      @patelhbk7580 Год назад

      @@AshishSrivastav1
      Apki bat 100% sahi but cost me jyada fark nhi hoga so 40a or 63a so best is 63a

  • @jaikumarcr7153
    @jaikumarcr7153 2 года назад +1

    🙄

  • @luckyshangase429
    @luckyshangase429 Год назад

    P

  • @shaikjanpasha9435
    @shaikjanpasha9435 3 года назад +1

    Wrong connections anna ?

  • @blueheart3987
    @blueheart3987 3 года назад +1

    This is wrong connection .

  • @gouthamchine449
    @gouthamchine449 3 года назад +1

    Wrong connection

    • @JrElectricSchool
      @JrElectricSchool  3 года назад +1

      why?

    • @super-z8943
      @super-z8943 3 года назад

      @@JrElectricSchool 1 is primary (line) and 2 is secondary ( load). Never defy convention in electrical works, unless of course it is your pet project and not a client job.

  • @shedtime_au
    @shedtime_au 3 года назад +1

    Pointless.

  • @francielbasan3753
    @francielbasan3753 3 года назад

    Worst video ever , red and black both are live wire , you cannot distinct guish neutral from live

    • @jetgeorge8774
      @jetgeorge8774 Год назад

      Some rccb the input in bottom or top it depends on the manufacturer..some mcb also is reversible..

  • @denisodhiambo1217
    @denisodhiambo1217 10 месяцев назад +1

    This is totally wrong I wouldn't advice a beginner to watch this video because it could mislead them.

  • @vaibhav23319
    @vaibhav23319 Год назад

    Rccb me 1 me se out kyu diya hai jabki 1 me se in hona chahiye tha ??