Basengreen EU stock 14.3Kwh 51.2V 280ah LiFePO4 Battery production process

Поделиться
HTML-код
  • Опубликовано: 27 окт 2024

Комментарии • 14

  • @francescoronca2968
    @francescoronca2968 Год назад +1

    Buona sera,

  • @cristioglice
    @cristioglice 11 месяцев назад +1

    Is it ok to be installed on an outdoor wall?
    Of course, no direct rain just the outside air humidity ...
    Thank you.

    • @Tom-BasenBattery
      @Tom-BasenBattery  11 месяцев назад +1

      Avoid the water/rain
      60% ± 25% relative humidity
      and that would be fine.

  • @benediktmaier7636
    @benediktmaier7636 10 месяцев назад

    How to connect more then one of these parallel? Inverter to CAN Port on zhe first one and then? How to connect the second, third , etc?

    • @Tom-BasenBattery
      @Tom-BasenBattery  10 месяцев назад +2

      Master: CAN to Inverter, RS 485A to RS 485B of Slave 1
      Slave1: RS485A to RS485 B of Slave 2
      ......
      ......

    • @benediktmaier7636
      @benediktmaier7636 10 месяцев назад

      @@Tom-BasenBattery thank you!

  • @benediktmaier7636
    @benediktmaier7636 9 месяцев назад

    What setting are needed for DEYE Hybrid 12kW Inverter?

    • @Tom-BasenBattery
      @Tom-BasenBattery  9 месяцев назад +2

      Connecting the 51.2V 280Ah to the DEYE inverter via BMS CAN PORT.
      As of the connections, cable "CAN H" provided with the battery) goes to the Pin 4 of the RJ45 of the inverter; cable "CAN L" goes to the Pin 5 of the inverter. No other cables are connected.
      The inverter then must be set to "00". The battery must be set to "Pylon" in the CAN field using the provided upper software (see the instructions, and the defalut setting is "Pylon" already).
      If you are using a single battery (and this is true for every inverter) the dip switches below the battery must be set all to "0" (000), this will gives to the battery the right address to operate as stand-alone.

    • @iserniamolise1731
      @iserniamolise1731 9 месяцев назад

      @@Tom-BasenBattery Se ho capito bene, se ho un voltronic e una sola batteria, devo impostare dal soft l'inverter voltronic e mettere tutti gli switches a 0? Dalla batteria all'inverter si mette una protezione o provvede già il bms? Grazie

    • @Tom-BasenBattery
      @Tom-BasenBattery  9 месяцев назад

      set all the switches to 0
      The BMS has the protection already, no worries.@@iserniamolise1731

    • @iserniamolise1731
      @iserniamolise1731 9 месяцев назад

      @@Tom-BasenBattery Ho già un box 280 e la Basen mi sta inviando un altro da 230 con le celle. La domanda è: si possono mettere in parallelo i due box?

  • @antoniocasta3625
    @antoniocasta3625 9 месяцев назад

    Ciao Tom, dove trovo il manuale del software del bms del box 280 ah? Esiste?