Totaliser is the part of logic so I will see in next vedio to cover that point, but citect scada mai day wise shift wise point not clear please elaborate.
SIR I CONFIGURED A DNP3 COMMUNICATION BETWEEN PLANT SCADA AND BMXNOR0200. BUT THERE IS A PROBLEM BACKFILL SCADA TREND THRROUGH EVENT CAN NOT BE CONFIGURED . CAN YOU TELL ME THE CONFIGURATION SETTING FOR THIS.
Sir, ai scalling me 4-20mA pe count 0 to 16000 hai, but hp pump band hone pe 4mA pe 0 count aana chaiye bt nahi aa rha hai, 5000 count aa rhe hai. Aur current band me bhi 19Amp dikha rha hai, ye problem kaise solve hoga sir, toda bataiye sir.
raw count not controlled by you scaling block use to scale raw count into desired values. you need to check wiring .check with multimeter what ma value read in your multimeter in pump off condition if ma is 4 and plc read 500 raw count so need to check your card scaling section minimum value,if min value is zero then you need to replace card. for major issue you can mail me.
Really you are the best keep it up very good methodology and tricks
👍Super explanation sir. Thank you very much.
Please upload video continuously because your video is very helpful and better understanding
Thank you sir❤❤❤❤❤
You're my favourite CE tutorial video creator, I'm more or less able to follow along and I don't even speak your language. Well done!
Happy to hear that!
if you have any issue you can mail me sandeep.tripathi10332@gmail.com, i added subtitle in my vedios you can see that you better understanding.
Supper video
totalizer block i will provide you with dfb
@@Schneiderautomationsolution Thank you sir
I am waiting for video of totalizer block
Sir
Please explain totalizer in control expert and citec SCADA, Shift wise , day wise and month wise
Totaliser is the part of logic so I will see in next vedio to cover that point, but citect scada mai day wise shift wise point not clear please elaborate.
SIR I CONFIGURED A DNP3 COMMUNICATION BETWEEN PLANT SCADA AND BMXNOR0200. BUT THERE IS A PROBLEM
BACKFILL SCADA TREND THRROUGH EVENT CAN NOT BE CONFIGURED .
CAN YOU TELL ME THE CONFIGURATION SETTING FOR THIS.
i mailed you reply please check
BMXPRA0100 can generate stop command
pra goes in stop mode some times it happens when any issue occurs. need to check excat issue.
Sir mere vaale kaam ki bhi bnado video😂
Kya kaam hai bro aapka😅
PRA malfunction side effects on system running equipment
Sir, ai scalling me 4-20mA pe count 0 to 16000 hai, but hp pump band hone pe 4mA pe 0 count aana chaiye bt nahi aa rha hai, 5000 count aa rhe hai. Aur current band me bhi 19Amp dikha rha hai, ye problem kaise solve hoga sir, toda bataiye sir.
raw count not controlled by you scaling block use to scale raw count into desired values. you need to check wiring .check with multimeter what ma value read in your multimeter in pump off condition if ma is 4 and plc read 500 raw count so need to check your card scaling section minimum value,if min value is zero then you need to replace card. for major issue you can mail me.
Sir pls apna contact no bataye
contact me on mail sandeep.tripathi10332@gmail.com