Giant Cold Storage Room High Temp Alarms

Поделиться
HTML-код
  • Опубликовано: 23 янв 2025

Комментарии • 10

  • @andykuehner2772
    @andykuehner2772 8 месяцев назад +7

    Looks like your at a amazon, they have undersized all there equipment here in Washington

  • @refer_insight
    @refer_insight 8 месяцев назад +1

    Do you have a subcooler on the rack? Is your head pressure transducer reading correctly? I assume your condenser vans are ramping up/down based on SCT differential but it’s running pretty high at 105* SCT. That’s pretty high & that could be causing your high suction.

    • @HVACRServiceTech
      @HVACRServiceTech  8 месяцев назад +1

      There is a subcooler on it, but that's on the Low Temp Suction Group. Transducer is reading correctly

  • @SeanMackBuffaloStyle
    @SeanMackBuffaloStyle 8 месяцев назад +2

    Sounds like Edward scissorhands at end of the video.
    Enjoy your videos bro

  • @czechmate6916
    @czechmate6916 8 месяцев назад +2

    I had a feeling you were going to either find a compressor not pumping well or not loading up. Take care in this heat brother. 🙏🙏✝️✝️