Daikin Minisplit Not Cooling Normally. Finding and Repairing a Refrigerant Leak EP92

Поделиться
HTML-код
  • Опубликовано: 25 авг 2024
  • Found a Daikin Minisplit was not cooling properly. Weighed the charge and found the unit was short 1 lb and change. I performed a nitrogen pressure test found and repaired the leak. Also how to use a CPS torque wrench.
    nighthawkhvac
    nighthawk_hvac
    Intro and Outro Music
    "Alive" by CHOIX
    #nighthawkhvac #hvac, #hvaclife, #airconditioning #maintenance, #trane #varitrac #heating, #cooling #refrigerator, #refrigeration #refrigerationcycle #airflow #refrigerant #techlife #installation, #hvachacks, #tools, #furnace, #tech, #electric, #residential, #commercial, #heat, #comfort, #ac, #hvacservice, #hvactools, #repair#toolreviews #fieldpiece #aircon #zoning #honeywell #zonedamper#packageunit #howto #VAV #exhaustfan #Ignitor #trane #TXV #expansionvalve #Intellipak #Trane #Self-contained #Boiler #Coolingtower #noisyinducer #noisyidm #failedIDM #condenserinattic #failedinducerdraftmotor #howtocleancoils #condensercoilcleaning #sparkignitor #nospark #minisplit #mitsubishi #ductless #powerboard #powerboardreplacement #short #outdoortxv #watersourceheatpump ###highpressuretrip#bloweralwayrunning #daikin #torquewrench #sparkignitor #ICM #reversingvalve #nucalgon #iwaveR#iwave

Комментарии • 16

  • @nethoncho
    @nethoncho 2 года назад +1

    Thanks for sharing your video. Nice to find an easy fix

  • @williamhawkes7194
    @williamhawkes7194 2 года назад +1

    Great looking pressure kit

  • @scottk0623
    @scottk0623 Год назад +1

    Nice job👍

  • @deanmartin1966
    @deanmartin1966 2 года назад

    Nice job. Thanks for sharing.

  • @tonydelgrego2906
    @tonydelgrego2906 2 года назад

    Nice troubleshooting and repair

  • @washinton2008
    @washinton2008 13 дней назад

    Is this a multizone mini split if so how can I recover the Freon into the unit from the main line

  • @NTalache
    @NTalache Год назад

    Do you not remove the schrader cores? The access to service valves on these units are horrible for a 5/16 Schrader core remover. Is it easier to just leave them in and use the 45 ball valves like you got here?

  • @sergiodoordie319
    @sergiodoordie319 7 месяцев назад

    My recovery machine is a home depot bucket

  • @eddiegomez3628
    @eddiegomez3628 2 года назад +1

    I have a question about vacuum and getting under 500 microns. Since you pulled under 500 micron mark, Does it matter that the micron numbers jump back up as your getting ready to charge the system?

    • @NighthawkHVAC
      @NighthawkHVAC  2 года назад +1

      As long as it stays well below 1000 microns you’re good.

    • @eddiegomez3628
      @eddiegomez3628 2 года назад

      @@NighthawkHVAC Thank you for that 😀

  • @sameermohammed3949
    @sameermohammed3949 Год назад

    What torque wrench is that that you're using ?.

  • @kellsieevans3847
    @kellsieevans3847 Год назад

    I have three daikin heads. They all connect to the compressor outside. My two bedroom heads are perfect and blow ice cold. My living room only blows ice cold when they top it off with refrigerant . A week later it goes from blowing warm air for a while then back to cool air but never ice cold like the bedrooms. They came out snd said they found a leak. But a week later here we are and the same thing is happening. What is going on !!!

    • @bolinsapark
      @bolinsapark Год назад

      probably like an electrical issue. did they fix it ?

  • @Thomas-iq8zk
    @Thomas-iq8zk 2 года назад +2

    Daikins are forever leaking

    • @jonjensen6036
      @jonjensen6036 Год назад +1

      This is clearly installation error, daikin didn’t make those flare joints..