Excellent, unique info
Thanku
well done sir keep continue
Thank you for your feedback sir, i hope you have like my video and i expect some valuable suggestion for the same
superb explainTion
pls also mention precaution to be followed during test in upcoming video of testing
SUNIL SHAW thanks your suggestion i will upload new video as per your suggestion
please explain 3rd harmonic and what should be the value of 3rd harmonic?
Ok on Sunday
Is this test performed while the LA is in online or during off line conditions
Yes
Yes it was on live condition
Sir 11 Kv or 33 Kv k lighting arrester kaise check kre magger se
Megher se
We have doubt that our lightning arrester counter (132kv) not change its counter reading , so how i can verify it or this counter are ok or not.(3ex5050 siemens)
Take it out from ckt and provide the one plus of 415volt for mili second.if counter increase than ok,
@@sarojgarhwal23 230 volt phase at connection terminal and neutral at body of monitor, if counter changed then ok
Send Kit name and cost of the kit please
Sir please make a video on tan delta test of lightning arrester
TUFAIL ALAM Soon i will uplaod
cost of this instrument?
thanks
This product comes under which Indian Standard
Testing standards
setting me 'Ir Max.' me kya daalna h sir for different voltage level LA
No need to put any value
Just put the voltage lavel
Sir plzzz400kv ct testing ka video send kare
What is the accepted value (thumb rule)?
Please tell me L.A leakage current in mA safe value like 0.1 to 2,3,4,5 mA
0-3 mA green valu.3-5 mA red valu.
Thanks sir
Sir ap k pass to old system hai ajkal to wireless system agia hain
Old video sir
Isme harmonic yes or no ka kyaa mtlb rehtha hai
ji app voltech engineerya kiya appka report may amaara company ka nam likavuva
Sir Circuit breaker Timeing and DCRM Video in Hindhi
dcrm already made
ruclips.net/video/kvOszPZzglA/видео.html
AT 1:58 YOU TOLD THAT VALUE SHOULD BE
pankaj singh jiGood observation . I have told about resistive leakage current should be within 100 micro amp.
And result show Total leakage current (ir+ic) 785microamp.just befoe this he also asked about third harmonic 19microampi will also attached result
What is the applied voltage
@@sarojgarhwal23 so ,it should be replaced ? bcoz value is exceed than 100 micro amp.
✌✌👍✌
🙂✌✌👍👍
Please tell me
sir .25 milliamp is the safe working limit on counter ameter
Excellent, unique info
Thanku
well done sir keep continue
Thank you for your feedback sir, i hope you have like my video and i expect some valuable suggestion for the same
superb explainTion
pls also mention precaution to be followed during test in upcoming video of testing
SUNIL SHAW thanks your suggestion i will upload new video as per your suggestion
please explain 3rd harmonic and what should be the value of 3rd harmonic?
Ok on Sunday
Is this test performed while the LA is in online or during off line conditions
Yes
Yes it was on live condition
Sir 11 Kv or 33 Kv k lighting arrester kaise check kre magger se
Megher se
We have doubt that our lightning arrester counter (132kv) not change its counter reading , so how i can verify it or this counter are ok or not.(3ex5050 siemens)
Take it out from ckt and provide the one plus of 415volt for mili second.if counter increase than ok,
@@sarojgarhwal23 230 volt phase at connection terminal and neutral at body of monitor, if counter changed then ok
Yes
Send Kit name and cost of the kit please
Sir please make a video on tan delta test of lightning arrester
TUFAIL ALAM
Soon i will uplaod
cost of this instrument?
thanks
This product comes under which Indian Standard
Testing standards
setting me 'Ir Max.' me kya daalna h sir for different voltage level LA
No need to put any value
Just put the voltage lavel
Sir plzzz
400kv ct testing ka video send kare
What is the accepted value (thumb rule)?
Please tell me L.A leakage current in mA safe value like 0.1 to 2,3,4,5 mA
0-3 mA green valu.
3-5 mA red valu.
Thanks sir
Sir ap k pass to old system hai ajkal to wireless system agia hain
Old video sir
Isme harmonic yes or no ka kyaa mtlb rehtha hai
ji app voltech engineerya kiya appka report may amaara company ka nam likavuva
Sir Circuit breaker Timeing and DCRM Video in Hindhi
dcrm already made
ruclips.net/video/kvOszPZzglA/видео.html
AT 1:58 YOU TOLD THAT VALUE SHOULD BE
pankaj singh ji
Good observation . I have told about resistive leakage current should be within 100 micro amp.
And result show Total leakage current (ir+ic) 785microamp.just befoe this he also asked about third harmonic 19microamp
i will also attached result
What is the applied voltage
@@sarojgarhwal23 so ,it should be replaced ? bcoz value is exceed than 100 micro amp.
✌✌👍✌
🙂✌✌👍👍
Please tell me
sir .25 milliamp is the safe working limit on counter ameter