Daikin tech support needs to watch this video
Thanks guys
So is it easiest to just tape/ziptie the control wire to the linesets running out of the box to the cassettes?
Hey gents if I put the system in recovery mode would the branch box eevs open automatically or do I have to hit some dip switches at the box itself?
When you put the outdoor in mode 2-21 refrigerant recovery mode, all EEV's will open (on Vrv 4 and previous) Vrv5 it will open all valves except the safety valves.