Question... in the diagram you have the inverter connected to terminal 1 and 3 on the meter. 2 and 4 connected to grid. But then u say you connected 1 and 3 to grid. Can u clear me up? Thanks
I have a sun-6k-sg05lp1-eu inverter, I connected an estron sdm230 modbus V2, but nothing works. I used both the orange white pair, and then the blue white pair, the speed is 9600 bd. I used the meter port. I configured the inverter with the Eastron 1p meter. Do you have a suggestion for me?
...and 8 or so minutes in, i spot the detail i've been chasing for hours. The meter must be set to 9600 baud, mine was set to 38k4. Sure would've been nice if that was in the dang manual!
Good detailed video! I want to use a CT sensor because its complicated and dangerous to in-line the smart meter directly into house's main line. Does that Eastron SDM230-ModBus model (at 1:42) also accept CT sensor?
Very useful video thankyou.
Question... in the diagram you have the inverter connected to terminal 1 and 3 on the meter. 2 and 4 connected to grid. But then u say you connected 1 and 3 to grid. Can u clear me up? Thanks
Hello,
Can you tell me which SDM 230 configuration is recommended for communicating with the inverter?
Add ?
Baud?
Etc...
Thank you!
I have Sun-5k-g model, no RS485 port.
Recently installed a SDM120, how should I connect it to inverter to calculate exported and imported energy?
I have an acrel meter r485 from an existing Solis install. Would this need to be replaced?
Yes needs to be replaced
I have a sun-6k-sg05lp1-eu inverter, I connected an estron sdm230 modbus V2, but nothing works. I used both the orange white pair, and then the blue white pair, the speed is 9600 bd. I used the meter port. I configured the inverter with the Eastron 1p meter. Do you have a suggestion for me?
I have the same problem
My inverter is Sun5K SG03LP1 EU
Eastron meter exactly the same as in the video
but it didn't work
+1 here, te SDM230 V2 wont work even you match the baud rate.
Can I use single eastron to connect to 2 or 3 deye hybrid inverter? like the 3 phase deye grid tie inverter..
Hi you can't
when we use the Eastron smart meter, we dont need the CT Coils? Thank you!
yes. don't need
How much power can the sun-6k hybrid inverter take on a single MPPT?
One MPPT can carry 6kw.
@@DeyeInverter_official thank you for the answer
Will Eastron SDM630MCT-MOD-MID Meter work on Deye 5kW EU Hybrid inverter. I cannot get the 230 model in Ireland.
I got mine from the UK.
any benefits of using a Eastron meter instead of the ct clamps?
The purpose is the same, but the meter can record data more intuitively
@@DeyeInverter_official I hear the CT reacts faster, is that true? (+ who can I contact to update fw for my 12kw Deye?)
Can you use other rs485 meters too?
Chint can be used
...and 8 or so minutes in, i spot the detail i've been chasing for hours. The meter must be set to 9600 baud, mine was set to 38k4. Sure would've been nice if that was in the dang manual!
Good detailed video! I want to use a CT sensor because its complicated and dangerous to in-line the smart meter directly into house's main line. Does that Eastron SDM230-ModBus model (at 1:42) also accept CT sensor?
Hi, not support currently
@@DeyeInverter_official SDM630MCT uses external CT
Is there a way to use a wireless meter? To send information from the meter through wifi or Zigbee to the Deye inverter?
My brother uses a pair of Waveshare RS485 bridges with his Growatt inverter. I imagine it would work just as well with the Deye.
deye 8k sg01 produced in 2021 support meter? Thanks!
support
@@DeyeInverter_official So why did the company inform dealers in Vietnam that SG01 8k produced in 2021 is not supported? admin can help me
On what Adress number should the Modbus meter be installed (you can;t select an adress for the meter in the Deye)
Default selection 1
nice can that work with Solis grid tie inverter 1P4K-4G-US
Can this work with SKY-MV01-8048 Hybrid inverter?
We are not sure, you need to ask your inverter manufacturer
Поддерживает DEYE 8kWt работу с CHINT DTSU666 Single Phase?
yes
Good vídeo, can i use a hiking dds238-2 zn/s?
Hi, not support currently
Thanks 👍
I forget the data logger password of deye 5kw inverter, have any solution how to reset logger password
Hi,you can seek help from solarman or contact the email
Heloooo
Helooooo……attention,in+ out ,mistaking😂😂😂
You do completely opposite way what's the diagram saying. 5:40 min connect the inverter into 1 and 3 , but you connect the inverter into 2 and 4.....