IET Acts Over Consumer Unit Ratings

Поделиться
HTML-код
  • Опубликовано: 13 янв 2025

Комментарии • 75

  • @anthonyjones5711
    @anthonyjones5711 21 час назад +12

    Perhaps if the manufacturer had not cut materials down of the main switch and bus bar to the absolute minimum a few Amps over the optimistic rated current wouldn’t be an issue.

  • @AAaa-wu3el
    @AAaa-wu3el День назад +17

    Consumer units also could become rusty. We need new regulations about it. What about making consumer units from pure gold?
    Sorry, but ever increasing number of "electrical safety" regulations making any electrical work prohibitorily expensive for the end client from general public. It leads to the even worse situation with most of the home electrical installations.

    • @andrewsb4633
      @andrewsb4633 20 часов назад +3

      Its a tricky one and all about balance. I have been a spark for 40 years and I do agree that work now is incredibly expensive for customers. Every year just more and more regulation. I plan to give it up in a couple of years. I think they just don`t want sole trader sparks anymore. It has become just so much more difficult to trade now. I am seeing a lot more DIY work around and jobs not done because of cost.

    • @gavinminion8515
      @gavinminion8515 17 часов назад +3

      I'm tempted to agree. I'm sure if I went right now and tried to pull 116A from my 100A consumer unit (I have no microgeneration), it would deliver that for several hours without any chance of the main fuse rupturing - It would probably also do so without becoming unsafe. The idea that the busbar in a 100A consumer unit would become unsafe at 116A is unrealistic. The idea that a household might consume this much current for a long period even more so.
      I get that this could be a problem where the microgeneration is 32A or more, but for 16A it does appear to be a hair-splitting thing.

    • @georgemcdonnell5147
      @georgemcdonnell5147 10 часов назад

      Completely agree

    • @efixx
      @efixx  10 часов назад

      Imagine the mark up on 24ct consumer unit... 😂🪙🪙🪙 Seriously though it's a tricky balance between anarchy and safety.

    • @Mark1024MAK
      @Mark1024MAK 6 часов назад

      Safety has to be paid for. Safety is normally a compromise taking into account practicality. If you really wanted to improve the safety of consumer units, the DNO service fuse should be *supplemented* by a 100A (or other suitable rating as appropriate) circuit breaker for every domestic installation. But that’s not gonna happen. If the bus bar in the CU is really only capable of safety handling 100A, then the extra CB should be down rated to 80A for example.

  • @barrieshepherd7694
    @barrieshepherd7694 3 часа назад +1

    What normal house has a load approaching 100 (or even 80) Amps for anything other than a few seconds? TBH perhaps the approach of a second connection between the main consumer unit and the solar system should be mandated? It would be a lot cheaper than messing around in the existing CU and possibly causing more mayhem.
    Circumstances mean that is my installation - the meter / incomer is in the garage connected by SWA to the house CU so the solar / battery install connects at the meter in the garage. No CU was harmed in the installation! 😂😂

  • @bernardcharlesworth9860
    @bernardcharlesworth9860 19 часов назад +4

    This is nonsense as taking diversity plus 16amps does not equal 116amps.

  • @Mircea007
    @Mircea007 22 часа назад +8

    Solar inverters all have CT clamps on the incoming supply, why not limit generation based on import from grid + generation from solar PV? Easy software update.

    • @Monkeh616
      @Monkeh616 19 часов назад

      They do? Mine certainly doesn't. What function does it serve for a simple inverter?

    • @Mircea007
      @Mircea007 18 часов назад

      @Monkeh616 the inverter needs to know where the current flows, to load or grid. Reasons could be: monitoring on the app and statistics, no export mode, limit export to 3.7kW to comply with DNO requirements.

    • @Monkeh616
      @Monkeh616 18 часов назад

      @@Mircea007 Ah. So.. optional features. With the sole exception of limiting export to account for poor infrastructure, all unnecessary. So, they don't all have CTs.

    • @Mircea007
      @Mircea007 18 часов назад

      @Monkeh616 and limiting the current thru your consumer unit could be another use more simpler to implement that fuses and switchgear.

  • @johnwarwick4105
    @johnwarwick4105 9 часов назад +2

    I know I know but 16 extra amps on a busbar come on people get real. It’s not even affecting the rating of the main switch as that can’t increase due to solar. Bearing in mind you could draw 150 amps through your 100A dno fuse for a considerable amount of time and 125 for many hours. So many people think a 100a fuse blows at 110a
    Who pays the electrician to go replace the time switch and how are they expected to know where they have fitted one 🤷‍♂️. This sort of recall is garbage, who even knows about it🤷‍♂️ time people could sign up to some sort of database that emails you or something from the wholesaler

  • @jamesmillward6286
    @jamesmillward6286 21 час назад +3

    If the house is using 100A, and the solar is generating 16A, surely only 84A is coming from the grid?

    • @AintBigAintClever
      @AintBigAintClever 21 час назад

      Issue is that the house could use 116A, exceeding the rating of the busbar without exceeding the rating of the two overcurrent devices supplying it.

    • @MrOpenGL
      @MrOpenGL 21 час назад

      Yes, but the problem is that the bus bar and other components inside the consumer unit are rated for, say, 100 A. But then you can draw 100A from the grid without blowing the fuse, and also get an extra 16A from the solar, so the total current you can draw can exceed the capacity of the consumer unit.

    • @jamesmillward6286
      @jamesmillward6286 21 час назад +2

      I see, makes sense. Maybe the PV should always be on its own dedicated CU then to avoid this issue.

    • @AintBigAintClever
      @AintBigAintClever 21 час назад

      ​@@jamesmillward6286 it should be doable with an upstream CU with 125A busbar if that works out cheaper than replacing the whole CU. Feed the main CU from a 63A MCB, PV from a 16A RCBO, possibly put another "heavy hitter" like an EV charger on its own RCBO in there too, leaving the original CU and 63A MCB to deal with everything else. Schneider have a 125A single-phase board range, I don't know who else does. It'd be nice of course if the suppliers were able to get their boards re-certified for 125A, even if it means a busbar upgrade.

    • @AndyK.1
      @AndyK.1 20 часов назад

      @@MrOpenGLJust put the solar mcb at the opposite end to the main switch. Bus bar won’t be overloaded then. (Or devices. )

  • @ardenuf7586
    @ardenuf7586 3 часа назад

    Hard to see how adding pv, which reduces the current from the grid, can exceed ratings.

  • @simoncroft9792
    @simoncroft9792 19 часов назад

    Re your Torque Calibrated Arm, do all of your sponsors specify torque settings for all their products?

  • @ElliottVeares
    @ElliottVeares 23 часа назад

    2:05 Can someone explain why the consumer unit could not draw/pull 100A from the DNO whilst the Solar PV also exports 16A on top of the 100A load, meaning there would be 116A going through the DNO's cut out fuse? Would the solar PV always be used locally for what it can provide before any excess is exported to the DNO?

    • @AintBigAintClever
      @AintBigAintClever 21 час назад

      I believe the issue is not that 116A could go through the service cutout, rather that 116A could be drawn through the busbar (16A from the solar plus 100A from the service cutout) by customer circuits, exceeding the 100A manufacturer's rating of that bar.

    • @Ino-z2m
      @Ino-z2m 21 час назад

      Er... yes! I have recently been wondering this, in fact the rating of a DB is almost academic nowadays because there can be so many sources, thinking through the weakest link is not easy, particularly due to direct offsetting as opposed to export you mentioned. Personally (and I know everyones going to shoot me!) the days of traditional CU's are dissapearing for this very reason. I always start with a giant 3-phase DB, this contains the current limiting MCBs to/from the grid, the feeds to/from all the inverters/chargers, the heat pump feeds, the aircon DB feed and EV feeds together with more traditional feeds to the conventional CU's. This initial DB has no internals or junction strips etc so its purely wire size / module limited in current capacity. But... you have to have unlimited time, unlimited budget, have unreasonable skills and tools and access to a decent workshop. So I wont be upset if you reply 'what a crap solution!'

    • @xxwookey
      @xxwookey 18 часов назад +1

      If the PV is generating 16A, and 100A is coming into the CU through the DNO fuse then 116A (~27kW) is being consumed locally and there is only 100A in the DNO fuse. If the PV export is going back through the fuse to the grid then there is only 100A being consumed in the house and only 84A going back though the cutout. The inverter causes export by raising the local voltage so the power flows the other way. But essentially yes, PV power is always used locally unless more is being generated than is being used locally. At that point it is possible for the excess to go back into the grid.

  • @retrozmachine1189
    @retrozmachine1189 13 часов назад

    MCB mainswitch, that sounds oddly familiar.

  • @demonkey123
    @demonkey123 7 часов назад +1

    Bus bar, not buzz bar 🙄

  • @BROOMEngineeringTMIET
    @BROOMEngineeringTMIET День назад +1

    What is this diversity you mention, when energy suppliers are incentivising people to pull 20+ kW for a couple of hours at a time, and rewarding them for consuming well above their in usual demand?
    It looks a bit reckless to me!

    • @AintBigAintClever
      @AintBigAintClever 19 часов назад

      They'll only get to do that with a three-phase supply, in any case they've been doing that for decades, remember the Heat Electric campaign?

    • @BROOMEngineeringTMIET
      @BROOMEngineeringTMIET 10 часов назад

      @@AintBigAintClever how do you know this?
      There are people putting pictures on social media of 25 or 26 kW and boasting about having as much on as possible, and their windows open, because they are being paid to consume.
      Back in September, the only house in a street near me with an EV, had National Grid digging up the drive, one Sunday afternoon / evening, to do a cable repair.
      Guess what? It was low demand, and high generation period, with lots of wind and solar, and energy suppliers paying for excess consumption. The NG engineer told me the likely cause on a cable which is around 70 years old.
      As I said.......... reckless!

    • @efixx
      @efixx  10 часов назад

      Interesting point. 😊

    • @AintBigAintClever
      @AintBigAintClever 10 часов назад

      @@BROOMEngineeringTMIET ah, I was thinking of off-peak EV charging (where 7kW would be the maximum unless on a 3-phase supply), I forgot about the flexi tariffs where they plug the hot tubs in and stuff.
      I suppose it depends on whether those on flexi tariffs get individual offers (which could - or at least should - be distributed so as not to overload particular roads or areas) or whether it's a blanket offering to all customers simultaneously which could cause problems.

    • @BROOMEngineeringTMIET
      @BROOMEngineeringTMIET 20 минут назад

      @@AintBigAintClever yep - on a local level it could be a bigger issue, as you could have people loading up phases, well out of balance on a street / area level, depending on their energy suppliers, and the tariffs those people have chosen.

  • @Hauntedguy27
    @Hauntedguy27 День назад

    Love your content, one day after I have gotten and a apprenticeship and eventually become a electrician. I would like to start my own business too any advice to starting your own business?

  • @andyhodchild8
    @andyhodchild8 День назад +1

    Thanks

    • @efixx
      @efixx  10 часов назад

      You're welcome! 😊

  • @davefrizelle3882
    @davefrizelle3882 День назад +1

    Hello there, glad to have the weekly news back again :) My guess this week for the hidden words - "techspeak" and "gotcha". Cheers!

  • @clivepierce1816
    @clivepierce1816 День назад +3

    Nissan Leafs have been capable of bi-directional charging for more than a decade.

  • @Dog-whisperer7494
    @Dog-whisperer7494 День назад +2

    Bilingual and face
    Happy new year Joe and a great first news weekly of 2025 👍

    • @efixx
      @efixx  День назад +1

      Good to be back, thanks Sean! 😃

  • @mark_just_mark
    @mark_just_mark 51 минуту назад

    Bilingual and Gotcha

  • @davemyers77
    @davemyers77 22 часа назад

    Bilingual cusp

  • @Mircea007
    @Mircea007 21 час назад

    nuggets and gotcha

  • @oninbridders
    @oninbridders 19 часов назад

    5:14 Was he wearing a Hat, with a chin strap?

  • @Jasonf-km5mq
    @Jasonf-km5mq 23 часа назад

    Bilingual, nuggets

  • @harryscrimshaw6654
    @harryscrimshaw6654 23 часа назад

    bi-lingual and gotcha

  • @kopspijker3515
    @kopspijker3515 День назад

    I am going for "Spate" & "Gotcha".

  • @metalaardvark4165
    @metalaardvark4165 23 часа назад +4

    Brilliant more Ev chargers - more black outs and no travel #Net Zero
    Klaus’s dream is soon to be a reality!

  • @chriswright6558
    @chriswright6558 День назад +1

    Bilingual and gotcha

    • @efixx
      @efixx  10 часов назад

      Nice guesses, listen to next week's show to see if you got it! 😃

  • @adriantopor9015
    @adriantopor9015 19 часов назад

    BS what you expect?

  • @hasan2471
    @hasan2471 День назад +1

    bilingual and hats

    • @efixx
      @efixx  День назад

      I honestly don't remember saying hats but I'll take your word for it! 😂 Tune in next week to see if you're right and my memory is that bad... 😊

    • @hasan2471
      @hasan2471 23 часа назад

      @@efixx hmm I don't fancy my chances then 🤣

  • @gabor.nadudvari
    @gabor.nadudvari День назад +1

    sorceress and baklava

    • @efixx
      @efixx  10 часов назад

      Everything OK at home mate? 🤔😂

  • @martinsimpson92
    @martinsimpson92 22 часа назад

    Bilingual, nuggets

  • @peterwollaston9556
    @peterwollaston9556 День назад +1

    Bilingual and gotcha

    • @efixx
      @efixx  10 часов назад

      Nice guesses Peter, listen to next Monday's show to see if you're right. 😊

  • @Dog-whisperer7494
    @Dog-whisperer7494 День назад

    Bilingual and gotcha

  • @DMosley7671
    @DMosley7671 22 часа назад

    Bilingual and gotcha