Fresh Air CFM, ASHRAE 62.1 ventilation rate

Поделиться
HTML-код
  • Опубликовано: 30 янв 2025

Комментарии • 22

  • @serverg79
    @serverg79 Год назад +2

    Great video!

  • @reasmeingor1962
    @reasmeingor1962 2 года назад +2

    Great videos. I have a question. When we provide fresh air for fcu, does it effect to fcu capacity?

    • @hvaceasymath
      @hvaceasymath  2 года назад +2

      Thanks!. The capacity would be same but the cfm splits into OA (outside air) and RA (return air). For example: 2 ton unit @ rule of thumb 400cfm/ton we have a supply cfm of 800cfm. So if we need 30cfm of OA and the return is 770cfm. Hope this helps

    • @reasmeingor1962
      @reasmeingor1962 2 года назад +1

      @@hvaceasymath thanks you're advice

    • @imtiazshinwari4527
      @imtiazshinwari4527 7 месяцев назад +1

      Well done ​@@hvaceasymath

    • @rembertomendoza3902
      @rembertomendoza3902 7 месяцев назад

      @@imtiazshinwari4527thank you!

  • @viniciusbraga5846
    @viniciusbraga5846 Год назад

    I have a question related to this. Usually when you have OA ducts passing through fire rated walls, either a FSD or FD is required. Do they vary depending upon the ASHRAE picked for the calculation ?

    • @hvaceasymath
      @hvaceasymath  Год назад +1

      Not really. Ventilation remains the same but we just want to make sure we provide FD in fire rates walls. The architect will provide with the life safety plan where it indicated which walls are 1 or 2hr rated walls.

    • @viniciusbraga5846
      @viniciusbraga5846 Год назад +1

      @@hvaceasymath thanks for the response. The reason I’m asking is that I have seen both (fsd and fd) being used in nyc for OA systems in nyc. So I was just wondering which one should be used for them

    • @hvaceasymath
      @hvaceasymath  Год назад +1

      @@viniciusbraga5846 FD, FSD and combination depends on the penetrations and fire wall rating provided in sections 717.5.1, through 717.5.7 and 717.6 of Chapter 7 of NYC Building Code 2022 (link: www.nyc.gov/assets/buildings/apps/pdf_viewer/viewer.html?file=2022BC_Chapter07_FireResistanceWBwm.pdf§ion=conscode_2022). Every state and city have different regulations. I hope this helps.

  • @tongilchang9663
    @tongilchang9663 5 месяцев назад

    Could you explain about Ez as well?

    • @hvaceasymath
      @hvaceasymath  5 месяцев назад

      Thanks for your comment! I will make a video in the future about Zone Air distribution Effectiveness. This basically indicates how efficiently a system delivers air to the breathing zone. There are different configurations depending on the diffuser locations.

    • @tongilchang9663
      @tongilchang9663 5 месяцев назад

      @@hvaceasymath Thank you so much for your kind responses.

  • @elvismelo2337
    @elvismelo2337 2 года назад

    ¿Acaso esas 3 personas no están necesitando 15 cfm X 3 =45 cfm ?

    • @hvaceasymath
      @hvaceasymath  2 года назад

      Gracias por el comentario. Es correcto lo que indica, pero además de los 15cfm debemos añadir OA debido a la superficie (área) lo cual es 0.06*146=8.76cfm. entonces (15cfm + 8.76cfm)/0.8 = 29.7cfm
      Thanks for the comment. it is correct but besides 15cfm we add OA due to area which is 0.06*146=8.76cfm. Then (15cfm + 8.76cfm)/0.8 = 29.7cfm.

  • @adamjuszczak4106
    @adamjuszczak4106 2 года назад

    Awesome

  • @imtiazshinwari4527
    @imtiazshinwari4527 7 месяцев назад

  • @viniciusbraga5846
    @viniciusbraga5846 Год назад

    Great video !