L&T APFC (etaSMART 12R) Programming , Alarm & Troubleshoot

Поделиться
HTML-код
  • Опубликовано: 30 янв 2025

Комментарии • 35

  • @akkikatify
    @akkikatify Год назад +2

    👏👏

  • @ravimahato9353
    @ravimahato9353 9 месяцев назад +1

    Etasmart8t k common me ac volt denge ya dc volt

    • @eeebackbenchers
      @eeebackbenchers  9 месяцев назад +2

      Brother 8R - means you have to use normal cap duty Contactor
      And 8T means it’s designed for thyristor
      Use only when you have thuristor

  • @Arunkumar-id5iy
    @Arunkumar-id5iy Год назад

    Nice ❤

  • @sudh304kapoor
    @sudh304kapoor Год назад

    Sir
    Default setting is : 0.015 of In hai.
    Aap default setting rakh sakte h koi problem ni h

  • @skylabreddymaddikunta7170
    @skylabreddymaddikunta7170 2 месяца назад +1

    SIR,WHEN WE KEPT THE AUTO MODE IMMEDIATELY 2NO CAPACITOR RUNNING.NO LOAD PURPOSE.BUT I HAVE NO NEEC.HOW CAN REMOVE THIS ONE

    • @eeebackbenchers
      @eeebackbenchers  2 месяца назад +1

      Bhai ,message is not clear to me but as I understand you taking about when you put auto mode selection from panel selector switch when 02 contactor ON immediately.
      If this case , then wiring problem is confirm . In this case you also verify that when contactor ON and Apfc respective LED should not ON

  • @irfanshah9690
    @irfanshah9690 3 месяца назад +1

    Really me pf velu settings karne K bad pf velu display per km btarahi he.is lie koi solutions btaen plz site per phasa hoa hon

    • @eeebackbenchers
      @eeebackbenchers  3 месяца назад

      Pf value kam Kaha Bata raha hai Matlab setting main enter karne ke baad ya view setting main ya , actual of kam dikka raha hai

    • @sudh304kapoor
      @sudh304kapoor 3 месяца назад

      Share your number if still there is problem I will call you

  • @aryanffarmy2684
    @aryanffarmy2684 Месяц назад +1

    RMC current keshe set kare

    • @eeebackbenchers
      @eeebackbenchers  Месяц назад

      Set Nahi kar sakte it’s real time measurement

  • @abhiboby
    @abhiboby Год назад +1

    🎉

  • @Raosahabproject
    @Raosahabproject 3 месяца назад +1

    Mera APFC panel EK MINUT KE ANDAR UNDC aa rha hai phir undc off ho rha hai yani bar bar on ho rha hai capacitor . 5 amp current me

    • @eeebackbenchers
      @eeebackbenchers  3 месяца назад

      It seems like some ct connections are loose , also check ct current output it should be higher then min. Requirement .
      You can also also refit the ct connector of apfc

  • @ShairAliDar
    @ShairAliDar 10 месяцев назад +1

    OCOM aur UNDC alarm ki setting kaise karna hai. Kaunse menu main Jana hai

    • @eeebackbenchers
      @eeebackbenchers  10 месяцев назад

      As per my best knowledge , I think there is NO option in AFPC Menu to change UNDC(under current ) setting .
      Secondly this is mandatory protection which update you that there is some issue in current input.

    • @ShairAliDar
      @ShairAliDar 10 месяцев назад

      mujhe UNDC ka threshold change karna hai. kya aapke pass apfcr ki koi manual hai? @@eeebackbenchers

  • @fazlasarfaraz2627
    @fazlasarfaraz2627 3 месяца назад +1

    Undc aa raha etasmart 6r me how to solve this problem

    • @eeebackbenchers
      @eeebackbenchers  3 месяца назад

      Bhai Undc ( under current) Matlab ct se sufficient current nahi aa raha . Check ct output at Apfc end

  • @bhabadattamishra4475
    @bhabadattamishra4475 11 месяцев назад +2

    How to solve UNDV (alarm) problem

    • @eeebackbenchers
      @eeebackbenchers  11 месяцев назад +1

      Simply means undervoltage : check voltage level and ensure the rated voltage at defined terminals

  • @jaiparkashvashist
    @jaiparkashvashist Год назад

    2500/5 ki ct h undc fault h to 0.015---0.5 me se kya seting hogi

  • @jagadeshyerra2483
    @jagadeshyerra2483 9 месяцев назад +1

    Hello sir
    how to slove UNDC

    • @eeebackbenchers
      @eeebackbenchers  9 месяцев назад +1

      Sir
      Undc means under current , means there is no sufficient current from ct
      Check ct output secondary current at Apfc ct terminals and car polarity

  • @mvvdprasad6691
    @mvvdprasad6691 Год назад

    RMS line to line voltage worg voltage show disply why problem

    • @eeebackbenchers
      @eeebackbenchers  Год назад

      Verify voltage level at APFC terminals & ensure connection should be done as per manufacturer recommendation.

  • @aryanffarmy2684
    @aryanffarmy2684 Месяц назад +1

    RMS current nahi aye toh

    • @eeebackbenchers
      @eeebackbenchers  Месяц назад

      Matlab Jis CT se Apfc main sensing aa raha h ausmain load nahi hai

  • @vickyrajput6602
    @vickyrajput6602 5 месяцев назад +1

    Ithd alarm aa raha hai

    • @eeebackbenchers
      @eeebackbenchers  5 месяцев назад

      Current harmonics is higher than 25%
      You should you detuned reactor or do harmonics study on your plan for better result