Samsung DVM Compressor Inverter Board Repair! E361, E461 and E277
HTML-код
- Опубликовано: 24 апр 2024
- Samsung DVM Training VRF Low Charge
• Samsung DVM Training: ...
I found the leak Video
• Uncovering the Heat Pu...
DVM Pro 2.0 software is required to properly design Samsung DVM and DVM Chiller systems.
www.samsunghvac.com/Software-...
Check out the Samsung HVAC Website
www.samsunghvac.com/
Wanna Learn more about hvac? Check out my hvac tips for technicians playlist.
• HVAC Tips for Technicians
Join this channel to get access to perks:
/ @taddydigest
Videos you may like to Watch...
How and Why to Use Samsung HVAC SNET Pro Software Video
• How and Why to Use Sam...
Samsung Chiller Error Code E425 Video
• Samsung Chiller Error ...
To gain access to option codes go visit www.vrfcoder.com
Taddy Digest Website
taddydigest.com/
@samsunghvacAmerica
when replacing an inverter compressor , its a wise idea to replace the inverter board.
Oh the life of a Samsung compressor replacement and then you have the awful discharge temp sensor failure. I also, saw the distain in your face when you found two bad compressors. FYI I learned you must check for oil in the old compressors and also weigh old compressors versus new compressors. Oh the Samsung Fun never ends. Great video!!
You saw that
I was pretty upset
Glad to get it fixed though
@@TaddyDigest inverter PCB
@@TaddyDigestSumsung DVM 12 hp
This was a good video nightmare job but good info one been changing capacitors and adding hard starts but the compressor wasn’t grounded yet but bad windings checked with ohmeter
I am from INDIA, just curious to know how these systems work. Good work. Kudos
Thanks sir 🎉very helpful ❤
good show
Thanks!
Awesome video your so smart
Great video Your Tadness
Glad you enjoyed it
Sooo much funner when you understand what you’re doing 😂
Yes sir I agree brother
The resistance readings were in megahohms, see the uppercase "M" displayed on the screen. So if it says 24.1, that's 24,100,000 ohms. Those compressors were fine.
Thanks for the video! I’m in HVAC school and it’s hard to imagine that’ll I’ll be as sharp as you are but that’s my goal lol I’m in crossville, TN. Your content is very helpful!
Really nice video! You're a great technician and teacher. Retired industrial electrician here, Tampa Florida area.
Thank you, brother. I'm glad you enjoyed the video
I'll be in Sarasota, Florida next month. I am ready
Rocket 1 to earth. Could you check the output serial port 3. It is really warm in here. Command center to rocket 1. It appears we have lost both boostets and the computer control boards are toast. We are ordering those now. Stand by Rocket 1. Its air conditioning for goodness sakes.
VRF Baby!!!!!! Let's go!!!!!!
nice
Great job, i learn a lot
Repair is different than installation. These units looks like you can get to the boards easily versus the residential units which are absolute nightmare. On the other hand I think you have worked on these units several times to include several major repairs now you have two compressors down I'm pretty sure the owner is like WTF is going on this thing isn't worth a shit. Nothing beats conventional. On the other hand nothing beats the flexibility of mini split that's if it lasts
Did u have to go to training thru samsung on them units. Our trade is sure getting complicated lol. Feel bad for all the new guys coming into it. Im glad im at my peak 😂
I did do a 2 day training to learn 💪 before ever installing a dvm unit
Great video, vrf rocks
I just replaced two compressors on my first vrf's. LG
We need video know how PCB is not work properly
Wow, I have soooo much to learn
Taddy good work but i didn't see you doing a flushing process for the system because it's very important before installing new compressor.
Take a guess how many of my systems got flushed in 27 years. Zero. I’ve had one compressor fail again 5 yrs later. Suction drier if it can fit, liquid drier, new refrigerant if needed, acid neutralizer if needed, new contactor and capacitor if needed.
Hello good work
But i have a question what is the S NET I'm from London uk thanks
The s net converter box is a tool that is utilized to convert the transmission signal into a readable signal by the s. Net software
Do you always replace the inverter boards when the compressor is grounded.
I’m from Connecticut
Hi Taddy. If the issue was caused by the compressors bieng shorted to ground why did you replace the inverted boards too?. Thank you.
I replaced the inverter board to make sure that I don't have any callbacks.
Hi, Teddy. Do you think 14Volt DC when compressor started to was abnormal? You measured 14vDC on inverter board
yes
Had that same issue thought it was the inverter boards, but it turned out to be the compressors, and also what tool do you have to have to hook up to the Samsung units?
snet converter box
Why you change the card if issue is compressor
I ordered the inverter boards first. The compressors did not check short to ground. So I already had the boards
Might as well replace them
why do u have to use thermal paste?
I use it so that the board does not overheat
@giveaway - Thanks Taddy!
Most of these vrv vrf break down frequently, and working on them is not easy
I have a unit that’s 41 years old and it’s still running. Should I buy a new one cause every one in my family is saying all the new stuff is garbage, is that true?
Run it until it breaks. Buy the simplest unit you can from the best contractor.
Or consider the fact that 40 years of innovation means waaayyy better efficiency and better refrigerants, you could be pleasantly surprised at the power savings
Been doing hvac going on almost 30yrs. ABSOLUTELY the new stuff is garbage. And it's going to get worse now that the government is sticking their nose in the hvac trades.
I hate seeing any 400 codes.
Samsung? More like Sam-suck!
But good for us in the feild, just like our “wonderful” daikin units we get here in Australia 🇦🇺- garbage units of late but great for business
Also why does the new compressor look like it came off the back of a truck 😅
Those units are pure junk
Pure junk! I had an American standard compressor fail after two months last summer. Puts a dent in your profits, doesn’t it.
Warranty supposed cover for that?
@@ebfsystem they give you the part after 1-3 weeks and may cover shipping. That’s it. Add $750 for each 1 ton portable cooling unit, refrigerant, vacuum pump oil, torch supplies, two trips out, 8 hrs labor, disappointed customer.
Cut apart the old compressor do a autopsy