CIRCUIT BREAKER TRIP SETTINGS

Поделиться
HTML-код
  • Опубликовано: 10 сен 2024
  • 6 Adjustable Trip Settings of a Circuit Breaker
    1. Continuous Amps (Ir)
    2. Long-Time Delay
    3. Short-Time Pickup
    4.Short-Time Delay
    5. Instantaneous Pickup
    6.Ground Fault Pickup
    In compliance with NEC® 230-95 (A), no trip point setting exceeds 1200 amps.

Комментарии • 18

  • @praveenkumar-te6wp
    @praveenkumar-te6wp Месяц назад +1

    thanks very much sir

  • @murugesan574
    @murugesan574 2 года назад

    Supper excellent explanation sir

  • @sathishkrishnanasolar1339
    @sathishkrishnanasolar1339 2 года назад

    Thank you

  • @DNR3380
    @DNR3380 3 года назад

    Nice update boss

  • @magathms4417
    @magathms4417 3 года назад

    Thanks for your information

  • @sankarmuthukumar4495
    @sankarmuthukumar4495 3 года назад

    Good information thank you

  • @thameemos3492
    @thameemos3492 6 месяцев назад

    Bro trip test pathi soluga

  • @vickytwentythree
    @vickytwentythree 3 года назад

    Sir what is the use of reactors in Capacitor bank?

    • @allinone.4you
      @allinone.4you  3 года назад +1

      Thanks a lot brother for your response..
      When a capacitor bank is a switch on in uncharged condition there may be a high inrush current flowing through it. To limit this inrush current reactor is connected in series with each phase of the capacitor bank.
      This damps the transient condition of the capacitor. It also helps to suppress the harmonics present in the system. These reactors are typically rated with their highest inrush current in addition to its continuous current carrying capacity.

    • @vickytwentythree
      @vickytwentythree 3 года назад

      @@allinone.4you ok thank u sirr

  • @nallavar1
    @nallavar1 2 года назад

    Ir 20% set panirukom.. Short time delay la 6×ir nu sonninga apo short time deleay evlo set pananum

    • @allinone.4you
      @allinone.4you  2 года назад

      Brother, Short-time delay, used in conjunction with short-time pickup, controls the time involved in postponing a short-time pickup trip..(Time Setting is adjustable between 0.05 to 0.5 seconds based on application)
      Short-time pickup is used for selective tripping.
      The short-time pickup function determines the amount of current the breaker will carry for a short period of time, allowing downstream protective devices to clear short-circuits without tripping the upstream device
      Short-time pickup is adjustable from 1.5 to 10 times the trip unit ampere setting (Ir)