Temperzone / More Issues With This 55kW Package Unit

Поделиться
HTML-код
  • Опубликовано: 15 янв 2025

Комментарии • 13

  • @BrannndonM
    @BrannndonM 2 месяца назад +1

    Had a horror story similar to this a few months back.
    Replaced a 25kw condenser water package unit for a comms room.
    After commissioning it would have this same issue but with the indoor fan.
    Would complete a cycle but then the indoor fan wouldn’t start up on the next 2 cycles as the thermal overloads were open causing the system to go out on LP and sometimes locking itself out.
    Had Temperzone onsite for it and even they were scratching their head.
    Was a nightmare for so many days we would rectify things and it would keep happening.
    So much sleep lost and anxiety just being close to the site.
    This head scratcher hits close to home

    • @hvacraustralia
      @hvacraustralia  2 месяца назад

      Oh man, I feel you on that one. Issues like that can drive you mad 😂 We’re Temperzone able to rectify the issue?

  • @prabhjotsidhu1207
    @prabhjotsidhu1207 2 месяца назад +1

    Hey mate
    Love your videos! Do most commercial premises have roof access or do you access by tall portable ladder?
    Thanks

    • @hvacraustralia
      @hvacraustralia  2 месяца назад +1

      Hey mate. Glad you’re enjoying the videos. Most places do have some form of roof access but I do also carry around an extension ladder just in case.

  • @jonaddison7062
    @jonaddison7062 2 месяца назад +5

    use a 9volt battery to test the fan motor. it will run at full load.

    • @Rollerguitar96
      @Rollerguitar96 2 месяца назад +1

      Insane tip

    • @hvacraustralia
      @hvacraustralia  2 месяца назад

      That’s a great tip! I’ve never thought of that. So simple. Thanks mate.

    • @frosty9206
      @frosty9206 2 месяца назад +1

      How would you determine the health of the fan motor by doing this ? Thanks

    • @hvacraustralia
      @hvacraustralia  2 месяца назад +1

      The UC8 board sends a 0-10VDC to the fan board which in turns sends AC power to the fan motor. If you have a fault control UC8 board you could send 9VDC to the fan board to get the fan to run, test amps, listen to bearings etc.

  • @michaelburns5680
    @michaelburns5680 2 месяца назад +2

    Seems like an electrical issue but also watch for oil leaking out the transducer body into the wiring loom where it clips on too.

    • @hvacraustralia
      @hvacraustralia  2 месяца назад

      I didn’t notice any oil but it will be something I’ll look out for. Cheers.

  • @damowdotnet
    @damowdotnet 2 месяца назад +2

    Killing the power corrupting some flash or other parameters causing the boards to misbehave maybe? Very odd…

    • @hvacraustralia
      @hvacraustralia  2 месяца назад

      This is my thought too. This entire site has power issues, but this is the only unit going through boards. Once they don’t need to isolate the unit to carry out testing and are no longer using a generator it will be interesting to see if the issues persists .