I have a hunting problem on a k19 generator also PT pump, what did you find? Was you getting air in line? My problem is reduced engine under load, bad on cold start up no load
Tengo un generador similar. Presenta problemas con el turbo al rojo vivo... La carga del generador no llega ni al 75%, cuál sería la falla en este caso....
Hola como estas mi planta eléctrica mod dfcc 350 kv me presenta esta alarma coolant eder 213 cua do le doy reset se quita y de una vez aparece de nuevo y no enciende
I have a generator of same size when I start is it runs for 30 minutes or more than 30 minutes then it's rpm goes very high and generator goes off can you guide me please?
Hello sir I have same engine and I have a problem that engine doesn't run starter works but engine not I am sure that fuel line is good and I connected fuel pump directly with fuel and engine not ...what do you think of this problem?
Hello sir, I am a great fan of your content, so knowledgeable. I have a question sir- I have purchased a second hand 125kva Cummins DG and I wanted to reset the working hours, please help me in this. Thanks in advance sir🙏
Depends on the panel on the generator, 3100 panels can only be reset by replacing the digital board(very pricey$$$) or rolling over the hour meter (10000 hours). All other panels(other then the detector panel) need Inpower pro to be reset but I doubt you will find many people who would be willing to reset a hour meter just because.
Maybe I'm one of the few people who absolutely love that "hunting sound" of a Diesel Engine, also quite partial to a nice lope tune 😁
It does sound cool. But not the sound you want in a genset.
Increase your governor ramp time in the setup menu, engine that size should be set 3-5 sec to help it stabilize faster.
How can i contact you , plz help?
isme filters kaun kaun se number ke parte hai sir...by pass filter, coolant filter, lube filter, oil filter and etc ?
What was the fix for this problem?
Did you found the problem tall me please i have like this problem
I have a hunting problem on a k19 generator also PT pump, what did you find? Was you getting air in line?
My problem is reduced engine under load, bad on cold start up no load
What is your governor gain set at? Air in the fuel line can cause this issue.
Tengo un generador similar. Presenta problemas con el turbo al rojo vivo... La carga del generador no llega ni al 75%, cuál sería la falla en este caso....
Hola como estas mi planta eléctrica mod dfcc 350 kv me presenta esta alarma coolant eder 213 cua do le doy reset se quita y de una vez aparece de nuevo y no enciende
Good pm Sir, What cause of Alarm List BOC.thank
I have a generator of same size when I start is it runs for 30 minutes or more than 30 minutes then it's rpm goes very high and generator goes off can you guide me please?
contact whatsup 00447850013649
Replace the speed govonor
Most of the engine hunt at least the kta 450-600
Hello sir I have same engine and I have a problem that engine doesn't run starter works but engine not I am sure that fuel line is good and I connected fuel pump directly with fuel and engine not ...what do you think of this problem?
Helo sar aap hame 500 kva dg ka timing batao
Hello sir, I am a great fan of your content, so knowledgeable. I have a question sir- I have purchased a second hand 125kva Cummins DG and I wanted to reset the working hours, please help me in this. Thanks in advance sir🙏
You directly cannot do that, its only possible through a laptop using cummins software.
Depends on the panel on the generator, 3100 panels can only be reset by replacing the digital board(very pricey$$$) or rolling over the hour meter (10000 hours). All other panels(other then the detector panel) need Inpower pro to be reset but I doubt you will find many people who would be willing to reset a hour meter just because.
Laptop needed bro
Can't do it impossible in manually laptop needed
Did you fix problem ?
I have the same problem sir. cummins kta19 hunting. can you give a solution?
how to solve haunting of KTA 19-M3 Engine ?
Tell me what oil is poured into this unit from the factory?
15w-40 Valvoline Premium Blue
@@mrdiesel6303 Thanks
Mau tanya pak klw penyebab manifold n turbocharger membara apa ya
Injector nya dan sirkulasi udara ngak normal lae
Bhai display me voltage 422 hai or basbar me 376 dikhata hai
kia problem hai
Cummins 1250 kva please help
Y tiene su nivel de coolant normal
how to solve the hunting problem K 19 cummins DG set
Where is its thermostat
Mpu problem or Actuator. Governor problems
👍
La planta es onan mod dfcc 350 kv
Ye electronic gorvener he
clean the magnetic pick up
For sale??
No
It's got a bad thingamee.
Turn up the stability on your voltage regulator till that hunting levels out problem solved
Hunting is in engine not in voltage
Aap ke content nombar chay sar