Armoured Cable Glanding and Termination process || Power Cable

Поделиться
HTML-код
  • Опубликовано: 2 авг 2024
  • Glanding and termination of Armoured cables

Комментарии • 36

  • @user-hd3yr9ym3x
    @user-hd3yr9ym3x Год назад

    Thanks master.. to share your knowledge..more power master

  • @007floppyboy
    @007floppyboy 2 года назад +1

    Great job, nice to see the inner sleeve left longer than the gland base, too many folk cut it right back and you end up with single layer of insulation next to the rough gland inner.
    That would pass a Chemical plant inspection if it was an E1FW gland.
    If you use adaptors, the inner sleeve should go past them by at least 10mm though.
    I think 3 and 4 look a bit short on the inner sleeve.

    • @CrazyMe30
      @CrazyMe30  2 года назад

      Thanks brother appreciate your suggestion

  • @sitasuthar9827
    @sitasuthar9827 2 года назад +1

    👍👍👍👍

  • @zubairalam1669
    @zubairalam1669 Год назад +1

    Nice

  • @user-gu9xu9fm1f
    @user-gu9xu9fm1f 2 года назад

    😍😍😍

  • @Zombie_Longwinger
    @Zombie_Longwinger 2 года назад +3

    I’d redo the first one get more bend on it

  • @paulharrison6408
    @paulharrison6408 2 года назад +1

    First cable too long tbh. I would advise not cutting the inner insulation off until after it's in the isolator. This avoids possible scratching of the core insulation. If you score around the inner insulation first before inserting then the inner comes off easier . Good effort though my friend . Spent over 35 years doing swa btw lol 😆

    • @CrazyMe30
      @CrazyMe30  2 года назад

      Thanks for the advice sir. Stay safe

  • @gcbbuildingproject4782
    @gcbbuildingproject4782 Год назад +1

    THIS CABLES I THINK FOR AIR HANDLING UNITE SUPPLY.

  • @zayn-mallik4168
    @zayn-mallik4168 Год назад +1

    What is the procedure for cable termination...this video all about how to gland the cable

    • @CrazyMe30
      @CrazyMe30  Год назад

      It depends on what you are going to terminate from LOw voltage to High voltage

  • @josecastillo3801
    @josecastillo3801 2 года назад +1

    Good job bosing..Ilan ang FLc mo 35mm ba Yan o 50mm..stay safe God bless

  • @closeplus1225
    @closeplus1225 2 года назад

    Pls use lug

  • @arghiegonzales8420
    @arghiegonzales8420 Год назад +1

    i think this site is in emirates hills 🙂🙂

  • @shaynemacdonald3051
    @shaynemacdonald3051 9 месяцев назад +1

    You should be using CW glands for outside.

    • @CrazyMe30
      @CrazyMe30  9 месяцев назад

      Thanks for watching!

    • @mcryptonite6948
      @mcryptonite6948 8 месяцев назад

      That is a CW gland.

    • @CrazyMe30
      @CrazyMe30  8 месяцев назад

      It is a double compression gland, CW is specially use for outdoor applications and where necessary to provide an IP66. Regards & thanks for watching

    • @shaynemacdonald3051
      @shaynemacdonald3051 8 месяцев назад +1

      That is a BW gland

    • @CrazyMe30
      @CrazyMe30  8 месяцев назад

      Single compression for indoor use

  • @paulpink9518
    @paulpink9518 Год назад +1

    Looks terrible you had loads of on the cables but you fucked the bends up totally.

    • @CrazyMe30
      @CrazyMe30  Год назад

      Thats the customers req😁

  • @lilysofficialchannel
    @lilysofficialchannel Год назад +1

    Ang hirap gawin hehe

    • @CrazyMe30
      @CrazyMe30  Год назад

      Kaya po yan basta pag aralan lng maigi. Ingat po

  • @androb.
    @androb. 2 года назад +1

    Nakakairita Ang ganyang disconnect switch master Lalo na yong selector type. Mag termination ka ng 10mm wire. Masakit sa kamay.

    • @CrazyMe30
      @CrazyMe30  2 года назад +1

      Yes boss tyaga lng hehe, salamat po

  • @shaynemacdonald3051
    @shaynemacdonald3051 9 месяцев назад

    Wrong glands and no IP washers used.

  • @litoolindo1368
    @litoolindo1368 Год назад +1

    Wrong glanding

    • @CrazyMe30
      @CrazyMe30  Год назад

      Thank you sir. Appreciate your comment. Stay safe

  • @doipardede321
    @doipardede321 Год назад

    No good....!🤭

  • @ruelolandria7758
    @ruelolandria7758 Год назад

    Dress properly your cable