How to bypass the VFD?

Поделиться
HTML-код
  • Опубликовано: 17 окт 2024
  • Do you know how to bypass a VFD?
    Do you know what a VFD is??
    Today I show you how to bypass The vfd.
    Join this channel to get access to perks:
    / @taddydigest
    If you want to learn more about HVAC check out my playlist hvac tips for technicians...
    • How hvac technicians d...
    3 Pole Contactor
    amzn.to/3wIBpWR
    Check out these other RUclips Channels to stay up-to-date on the latest HVAC Knowledge
    @HVACR VIDEOS
    @HVAC School
    @HVAC Know It All
    @Nortek Global HVAC

Комментарии • 124

  • @cosmodog1803
    @cosmodog1803 Год назад +1

    You saved the customer a lot of money. Great fix

  • @jiffster7512
    @jiffster7512 Год назад +4

    A motor starter with overloads would have been a better choice?

  • @edlauren9434
    @edlauren9434 3 месяца назад +1

    Dude, you are my role model! I do hate these VFDs as well! I don't like EEVs on refrigeration equipment either! Converted HeatCraft (Beacon II) freezers with those EEVs to TXV/Defrost timer set ups and now it runs trouble free!

  • @HVArctiC-Monkey
    @HVArctiC-Monkey Год назад +2

    With that thermostat set to electric, is there a fan delay when (gas) heating turns on?

  • @laviejabeba809
    @laviejabeba809 Год назад +2

    Marco from New York thanks for that info now if I pass through a issue like that I can do that and still order the variable frequency it takes a couple of week🤑🤑🤑🤑

  • @danieltolfo9332
    @danieltolfo9332 Год назад +2

    Do the other ends of the wires from your 24 v coil connect to the control board harness?? I see smaller gauge from control board angle.

  • @josemgamez3613
    @josemgamez3613 3 месяца назад +2

    The cables that connect to the board terminals are those that connect to those of the thermostat

  • @soloch69
    @soloch69 2 года назад +3

    Great video brother keep them coming love them wiring videos 🙌🏻🙌🏻🙌🏻🙌🏻🛠⚙️⚒️

  • @rnava4035
    @rnava4035 10 месяцев назад +1

    VFD's can be tricky, if you have like units , I would have swapped parts to find the issue, a fix could possibly just been reconfigure a few settings?

  • @archiermx250
    @archiermx250 7 месяцев назад +1

    Have a carrier with vfds for blower fans and it gives an error of f5 fan running out of control. Would your fix work on this?

  • @JaykeSapalaran-iq3qs
    @JaykeSapalaran-iq3qs Год назад +1

    Great video tutorial 👍♥️ thank you for sharing your knowledge ♥️🇵🇭

    • @TaddyDigest
      @TaddyDigest  Год назад +1

      your welcome Glad you watched 👀 😊
      please share my video 📹 🙏

  • @godz1llaki11azzzz3
    @godz1llaki11azzzz3 2 года назад +3

    great video !! also i love those 701tstats haha

    • @TaddyDigest
      @TaddyDigest  2 года назад +1

      dude yes the T 701 is a classic
      Thank you for watching 👀 😀

  • @panagiotispsomas5611
    @panagiotispsomas5611 Год назад +4

    You can use some micro relays (finder) with the contactor combined with the VFD to make a transfer switch from vfd to contactor when the vfd fails

  • @ericbrewbaker7670
    @ericbrewbaker7670 2 года назад +1

    Eric B. East China, Michigan. Love the information. Thank you. Much appreciated.

    • @TaddyDigest
      @TaddyDigest  2 года назад

      Hey Eric glad you watched the video thank you so much for commenting

  • @Mexashop1
    @Mexashop1 Год назад +1

    You save the day brother thank you very much! 😮‍💨👌 very helpful 🫡

  • @Eddy63
    @Eddy63 2 года назад +1

    Very interesting ... Thx for sharing your knowhow ...

    • @TaddyDigest
      @TaddyDigest  2 года назад

      Hey Eddy 😊 thank you for watching the video

  • @mordeth999
    @mordeth999 2 года назад +2

    I'm not a fan of York equipment in general, but wondering if you have any tips for placing temperature probes for superheat/subcool in package equipment (especially Yorks), because it is so dang hard to reach into the compressor compartment in some of their older equipment!! Thanks in advance from Nashville!

    • @TaddyDigest
      @TaddyDigest  2 года назад

      I'm not a fan either
      They have terrible manufacturing practices
      If it wasn't for my distributor I would never sell another York again

  • @antoniocalamari
    @antoniocalamari 14 дней назад +1

    Was that a Delta (high Leg) service at the building?

    • @TaddyDigest
      @TaddyDigest  13 дней назад

      possibly but I am not sure because of how long ago

  • @ebuzek3648
    @ebuzek3648 9 месяцев назад +2

    The company I work for, our units have an Entouch thermostat. It would have to be programmed by management. I have trouble when you get a power blip and loose a leg for a second. The VFD faults out and the unit stops working. I have to drive out just to press the stop/reset button on the drive. Very aggravating.

  • @Tonyhvac
    @Tonyhvac 11 месяцев назад +2

    Good job 👍🏾

  • @fernandofrancisco3106
    @fernandofrancisco3106 2 года назад +1

    Thanks for sharing this video

    • @TaddyDigest
      @TaddyDigest  2 года назад

      Thank You for watching my friend ❤️

  • @scottowens826
    @scottowens826 2 года назад +1

    So when the part comes in will you put it back in service, since unit has multiple stages or looked like it did?

    • @TaddyDigest
      @TaddyDigest  2 года назад +1

      Absolutely
      Yes This is a Tuesday June

  • @fernandofrancisco3106
    @fernandofrancisco3106 2 месяца назад +1

    I did it to my work it’s a carrier rtu. The vfd is burnt. I follow the wire and it’s easy for carrier it plugs in I don’t have to add a relay.

  • @RB-hl3ux
    @RB-hl3ux 2 года назад +1

    Great review
    Looking Good 😉

  • @HodderHVAC
    @HodderHVAC 11 месяцев назад +6

    I just came across this video and I'm going to tell you a few things that will help you in the future. Point 1. The reason you are having a difficult time with the VFD is most likely you have a high leg. The VFD doesn't like this. It will run for a while and then decide to lock out. VFD's don't work with a high leg of power. Point 2. You didn't have to run power from the G terminal and common. You also didn't have to switch the T-stat to Electric. If you read the schematic, there is a relay in the top left side of the control panel. It's a clear relay with a normaly open set of contacts and a 24v coil. That's the low voltage power to the VFD. It's energized on a call for heat or cooling. Simply remove the 24v coil wires from the relay and put them on your contactor. Mount the contactor in the control panel. The control wires are long enough to reach the new contactor. I put a 2x4 box with cover in the blower compartment to connect the motor wires.

    • @garageink74
      @garageink74 10 месяцев назад +1

      Thanks for the info. Saved me a bit of work

    • @soulmpowered
      @soulmpowered 10 месяцев назад +1

      How do you know that it has a high leg ?

    • @HodderHVAC
      @HodderHVAC 10 месяцев назад +4

      3 phase go each leg to ground. You should have 110v at each leg. If you get one leg that is 208 volts then that is your high leg. If you have that, you will have issues with the VFD.@@soulmpowered

    • @potentialhvac6074
      @potentialhvac6074 8 месяцев назад +1

      Working on this right now in Mill Valley, CA. Couldn't thank you enough for this comment. Shout out to Taddy for the channel and initial advise!!

    • @TaddyDigest
      @TaddyDigest  8 месяцев назад

      I've got a video on how to figure out if it's a high leg.

  • @MrGuero1416
    @MrGuero1416 2 года назад +1

    What did you do to the vfd control voltage did you unplugged the black and yellow wire?

    • @TaddyDigest
      @TaddyDigest  2 года назад +1

      i disconnected the vfd control voltage

  • @jones32blessed22
    @jones32blessed22 2 года назад +1

    Thanks for the content watching from cincinnati
    So do throw the Tstat in gas or electric after?
    Is this the most common vfd?

    • @TaddyDigest
      @TaddyDigest  2 года назад

      The most common VFD is mitsubishi and Delta brand
      Yes switch the thermostat from gas to electric
      You're welcome thank you for watching I really appreciate your comment

  • @danielpelc3779
    @danielpelc3779 Год назад +2

    Looked like your vfd had an enable signal wired. I think using that for your contactor coil would have made things a little more plug and play. Did you just not notice that or was there some other factor?

    • @TaddyDigest
      @TaddyDigest  Год назад +1

      Daniel thank you so much for letting me know this knowledge I did not even notice this otherwise I would have Use that as my option for energizing my coil

    • @HVArctiC-Monkey
      @HVArctiC-Monkey Год назад +1

      Is that a 24vac signal for fan demand?

    • @danielpelc3779
      @danielpelc3779 Год назад +1

      @@HVArctiC-Monkey yes usually 24 for an enable and 0-10 for any type of modulation signal

  • @Goldstacker1972-kp2bh
    @Goldstacker1972-kp2bh 2 месяца назад

    Do you have to do anything with the control board? I was able to get it to reset but I had an.STL3 failure on it. I know the parts not available locally.So I might have to end up doing the same thing.I just know the control board.Says vfd failure when it fails.So I didn't know if you had to do something to the computer or not

  • @diazinc462
    @diazinc462 11 месяцев назад +1

    What if the Rtu is on EMS? Dont have thermostat terminals

  • @aarongray503
    @aarongray503 2 года назад +1

    You got a new member!

    • @TaddyDigest
      @TaddyDigest  2 года назад

      Awesome Aaron thank you so much for becoming a member.
      let me know what I can do to help you.
      I have some guides that I can send to you if you want to send me an email at
      tadfuller1@gmail.com..
      I can also do a videos to help you better understand what it is you need help with
      I have several videos that remember only videos that you gain access to that no one can see.
      Your questions can lead to content so let me know

  • @chadpinkston37
    @chadpinkston37 4 месяца назад +2

    Great vid

  • @nakiapringley5391
    @nakiapringley5391 2 года назад +1

    Great video brother 💯💯💯💯

    • @TaddyDigest
      @TaddyDigest  2 года назад

      Nakia thank you so much for watching I really appreciate the comment

  • @seejayfrujay
    @seejayfrujay 2 года назад +1

    Thanks for this video--it got me wondering about something I watched. I noticed quite a few HVAC units (3 phase rooftops) with VFD have contactors between it and the compressor(s) and I was wondering why. Old school when I did it, but a contactor between a VFD and its motor was a big no-no. If the motor is not always connected, features such as DC boost, soft starts, frequency ramping, etc. all or most of that is not available with a contactor in the circuit. Is the VFD limited in what it can do and needs a contactor? I watched an HVAC tech service a 3p Lennox rooftop on RUclips and I was confused. A VFD drove three compressors through three contactors. I am guessing that the VFD provides a bit of energy savings and possibly some monitoring, but little else?

    • @panagiotispsomas5611
      @panagiotispsomas5611 8 месяцев назад

      The contractors are installed between the motor and VFD in case of failure to have a backup mode. This works fine for asynchronous 3 phase induction motors. If you have a BLDC motor, which is a synchronous 3 phase permanent magnet motor, you should run it from the vfd. It is not possible to run it just from the wall it may cause damage to the windings of the motor.

    • @seejayfrujay
      @seejayfrujay 8 месяцев назад

      @@panagiotispsomas5611 Thank you!

  • @williamkaye9029
    @williamkaye9029 Год назад +1

    Dear Tad! What an incredible video. I live in South Florida and my VFD blew and my a/c tech told me they are on back order for months. My room is hot and I can not stand the heat. I have a trane variable speed 4TTV8036A1000BA. I understand what you did on this unit and wonder if I can do it on mine. I have not opened up the unit well but I wonder if it would fit the contactor within the space? Do you know this unit?
    Bill

    • @TaddyDigest
      @TaddyDigest  Год назад

      I'm not sure if it would work for yours or not I would have to do a little research
      You're welcome to click the join button become a member and let me know when you join and I will send you an email

    • @TaddyDigest
      @TaddyDigest  Год назад

      thanks for watching 👀 😀

  • @NROhvac
    @NROhvac Год назад +1

    Hey Tad did the vfd display a code when in alarm?

    • @TaddyDigest
      @TaddyDigest  Год назад +1

      No sir
      But usually the vfd will display a code

    • @NROhvac
      @NROhvac Год назад

      @@TaddyDigest yeah that’s weird, from my experience a lot of VFDs will go into “overcurrent” fault. This usually happens because the soft start up isn’t long enough, and can be fixed by increasing the ramp time on the VFD module programming

  • @WorkingManReads
    @WorkingManReads Год назад +2

    Great video man. I have a york that I can't get a replacement VFD on and york was telling me I needed and auxiliary relay on top of the contactor. So this was dope to see you just ran it to g and c on the UCB 🤘

  • @sheldon8115
    @sheldon8115 2 года назад +1

    Good stuff

    • @TaddyDigest
      @TaddyDigest  2 года назад

      Thank you Sheldon
      Really appreciate You watching
      Please hit the like button
      And smash the notification bell
      I've also got a
      HVAC Equipment sizing video
      duckwork sizing video
      pricing video and a
      sales video that are super good
      Members only click the join button
      If you need it
      Thank you

  • @chriswilson4094
    @chriswilson4094 Месяц назад +1

    It seems that York VFD’s lock out for no reason. No high leg issue and we have changed most of the York units over to a contactor. York does not have an answer for the issue so far that I am aware of. Just say to install a contactor. York units only so far. They are all on back order if you try to get a replacement. If there is any other info. Please share.

    • @TaddyDigest
      @TaddyDigest  Месяц назад

      I am not sure why I just know its super inconvenient in the field

  • @keenanwalker6597
    @keenanwalker6597 Месяц назад +1

    Saved my ass thank you!

  • @brandonr5388
    @brandonr5388 2 года назад +1

    Thanks for explaining switch gas to electric I was thinking how to do it before you explained

  • @bluesfan2222
    @bluesfan2222 7 месяцев назад +1

    I doubt if that motor has internal protection ; protection is through the VFD so the contactor leaves it with no overload . An IEC style with an overload block would be much better even though it’s 250 vs 40 ; finding the problem ( probably high or unbalanced voltage ) would be lots better than treating the symptom. Had to do this in places where voltage was 480-490 and drive on smaller equipment was only configureed for 460. Not being negative , just practical.

  • @jaysingh-ho7eb
    @jaysingh-ho7eb Год назад +1

    what happens when the thermostat calls for heat?

  • @Kman-hw9pf
    @Kman-hw9pf 2 года назад +1

    Instead of changing setting on thermostat from gas to electric, could you have left it on gas and simply put a jumper between w and g?

    • @TaddyDigest
      @TaddyDigest  2 года назад +1

      good idea you could have

    • @akatsuki10pein10
      @akatsuki10pein10 2 года назад +1

      A lot of T-stats, you can go in the installation setup and have the thermostat control the fan in heating mode opposed to having the unit control the fan in heating mode.

    • @TaddyDigest
      @TaddyDigest  2 года назад

      that is correct 👌 👏 👍

    • @markcantrell2470
      @markcantrell2470 2 года назад +5

      and then they turn the fan to continuous and the unit begins to heat... dont do the jumper

    • @Kman-hw9pf
      @Kman-hw9pf 2 года назад +1

      @@markcantrell2470 lol, you're right

  • @rmirgard6255
    @rmirgard6255 10 месяцев назад +1

    Looks nice but i would have added a motorprotection after the contactor

    • @TaddyDigest
      @TaddyDigest  10 месяцев назад

      Good advice. Thank you for looking out brother.

  • @potentialhvac6074
    @potentialhvac6074 8 месяцев назад +1

    Thanks!

  • @potentialhvac6074
    @potentialhvac6074 8 месяцев назад +1

    Taddy helping me make money and my customer save money/heartach

    • @TaddyDigest
      @TaddyDigest  8 месяцев назад

      Thank you so much for watching you are awesome

    • @potentialhvac6074
      @potentialhvac6074 8 месяцев назад +1

      Wait up. How do I switch the board to tell it's single speed vs vfd?

    • @TaddyDigest
      @TaddyDigest  8 месяцев назад

      Yes
      But you don't have to if you are installing a Contactor like I did

    • @potentialhvac6074
      @potentialhvac6074 8 месяцев назад

      @@TaddyDigestwell that certainly gives me some piece of mind. thanks dude 👍🏾👍🏾 . 3 hrs later I'm finally done. Had to go get tarps for the ☔

    • @potentialhvac6074
      @potentialhvac6074 8 месяцев назад

      Always feel tons pressure be faster and sharper but I usually seem to get it done so 🤷🏾

  • @MTknives
    @MTknives 2 года назад +1

    Nice 💪

  • @boduke2299
    @boduke2299 3 месяца назад +1

    Shouldn't the fan run at about 25 hz when there is no call for cooling for fresh air requirements and when compressors come on in cooling mode the vfd should ramp up to 60hz i thought, with the contactor installed it appears to only turn the fan on in cooling mode.

    • @TaddyDigest
      @TaddyDigest  3 месяца назад +1

      What if there's no fresh air

    • @boduke2299
      @boduke2299 3 месяца назад

      @@TaddyDigest then I guess it would be off and then full throttle when it is on where I live they have I believe a 15 percent minimum outside air requirement for buildings it might be different in other areas I am working on a York rtu unit right now and I can't get the hz to change at all it is locked at 25hz I have power coming off the board and power at the Mitsubishi vfd that is in it when the cooling kicks in it doesn't ramp up to 60hz so I figure it's either the control board issue not telling the vfd to increase fan speed or an internal vfd problem have you ever had an issue like this before on a York rtu unit where the hz is locked on low speed.

  • @USA-GreedyMenOfNoIntegrity
    @USA-GreedyMenOfNoIntegrity 2 года назад +1

    I keep a 3/4 & 1 hp 230V blower motor, relay, cap for my 4 & 5 ton vs ah's.

    • @TaddyDigest
      @TaddyDigest  2 года назад +2

      That's a good idea you are prepared my friend

  • @marcorecinos8629
    @marcorecinos8629 2 года назад +1

    Some times fvd fail cause the belt is too tigth or too loose. That is the situations that I have seen

  • @Jackhvac_R
    @Jackhvac_R 2 года назад

    A beautiful York 👀

  • @nilsiogonzalez4797
    @nilsiogonzalez4797 2 года назад +1

    saludos amigo

  • @dannyrichardson9247
    @dannyrichardson9247 Год назад +1

    We're is black and brown is connected to, coming out the 24v plug????

  • @jongrenfell5227
    @jongrenfell5227 9 месяцев назад +1

    Hold on. The thermostat doesn't send the signal in heat. That is done by the blower limit. You have to wire the relay in. Setting the stat to the electric heat, the blower shuts down immediately after the call for heat. Also, you gotta let the board know that it is single speed instead of vfd

    • @TaddyDigest
      @TaddyDigest  9 месяцев назад +1

      That is correct you know your stuff. Thank you for this comment very good.

    • @jongrenfell5227
      @jongrenfell5227 9 месяцев назад

      @@TaddyDigest I had to do this the other day.

  • @bmworange
    @bmworange 28 дней назад

    I am having the system problem on a unit

  • @rewernan
    @rewernan 8 месяцев назад +1

    I don't understand why would you do that, if the vfd is failing just replace it. Its an electronic device at last

    • @TaddyDigest
      @TaddyDigest  8 месяцев назад +1

      they need the unit to work and the VFD is out of stock atm

  • @doctorhvacr5869
    @doctorhvacr5869 11 месяцев назад +2

    I did learn something don't buy York with micro coils.... or vfd garbage

  • @craigewing1844
    @craigewing1844 2 года назад +1

    What was wrong with the VFD? What error codes did it give you?

    • @TaddyDigest
      @TaddyDigest  2 года назад +1

      The problem was not with the vfd
      The problem was with the control board
      No error on vfd
      error on SSE board was fan vfd failure

    • @craigewing1844
      @craigewing1844 2 года назад +1

      @@TaddyDigest just curious, did you hook map gateway up? If so was fan set for VFD or fixed variable?

    • @TaddyDigest
      @TaddyDigest  2 года назад +1

      yes I did Fan was set to vfd

  • @carsonbowles9302
    @carsonbowles9302 Год назад +1

    This'll work for any vfd?