How to repair Schneider Electric circuit breaker simply and fast

Поделиться
HTML-код
  • Опубликовано: 8 авг 2017
  • This video will help you to repair and troubleshoot a common defect in Schneider Electric Circuit Breaker simply and fast.
    طريقه سهله لصيانه القاطع الدواير من شركه شنايىر الكتريك لحل مشكله شايعه في هذا المودیل
    روشی آسان و سریع برای تعمیر کلید بریکری شرکت اشنایدر الکتریک که از طریق آن میتوان مشکل عمده این سری از کلیدهارو حل کرد

Комментарии • 13

  • @basht5899
    @basht5899 5 лет назад +3

    Bruno is 100% correct. I primary injection test breakers for a living. Tampering with trip units is a bad idea unless you know exactly what you are doing and have the means to test it afterwards.

  • @oscaralberto1793
    @oscaralberto1793 Год назад

    Great and simple, regards from Central American

  • @brunocolin7202
    @brunocolin7202 6 лет назад +8

    Dear Ali, I am part of Schneider Electric. I strongly recommend you not to perform this operation. By turning this screw you are actually changing the magnetic trip threshold of your NSX Circuit breaker Micrologic, compromising the ability of the device to a trip in case of defect., thus to protect the installation...

    • @Ali-oh3sg
      @Ali-oh3sg  6 лет назад

      Bruno Colin , thank you very much for your answer, we use this breaker on a movable device that have lots of vibration and we see a lot of our Schneider electric breakers have this problem and the only way to overcome this problem was that.
      If you can send me an answer on my email to be in touch
      Thanks in advance
      ali0611@gmail.com

  • @yamish1868
    @yamish1868 Год назад +1

    How to repair or change internal pole

  • @mohammadnuralom5749
    @mohammadnuralom5749 4 года назад

    Nice

  • @electroelectricals6571
    @electroelectricals6571 4 года назад

    Helloo my friend

  • @ammaralyasiri4191
    @ammaralyasiri4191 4 года назад

    maintenance part of merlin gerin-nw12 thanks

  • @jabarizzat2718
    @jabarizzat2718 4 года назад

    Hello dear,, we have a mccb 40A,3p, when we set on 40A it works normally but when we wanna set on 28A, directly trip even it's not in acircuit, not at any load,, can you help us to solve this problem ?? thanks for your help

  • @eu-varna
    @eu-varna 4 года назад +1

    In my opinion, you shouldn't have shown it here! The situation is individual to you!

  • @electroelectricals6571
    @electroelectricals6571 4 года назад

    Helloo my friend