Feed-Through Conductors 2023 NEC 312.8 (A) and (B)

Поделиться
HTML-код
  • Опубликовано: 20 окт 2024
  • How to Bond Neutral and Ground With 2023 NEC Code Book and Handbook: • How to Bond Neutral an...
    IDEAL National Championship Pro Finals 2021 $60K for 1st Place, $25K for 2nd and $10K for 3rd!: • IDEAL National Champio...
    Also see: Bonding Screws vs Bonding Straps (NEC 250.24 (B) Main Bonding Jumper: • Bonding Screws vs Bond...
    Also see: What's the Difference Between an EGC and a GEC?: • What's the Difference ...
    For apprentice electricians: To compete to enter the contest next year: www.idealind.com
    IDEAL INDUSTRIES INC. 61-534 Digital Circuit Breaker Finder with Digital Receiver and GFCI Circuit Tester: Amazon: amzn.to/2oW56Ds
    IDEAL Electrical 35-056 Ratcheting Cable Cutter - 400 MCM, Wire Cutting Tool w/ Steel Rounded Blade, Quick Release Handle: Amazon: amzn.to/3GRRwEr
    Ideal Industries Inc 44-103 - Pre-Printed Cable & Wire Label or Marker, Color Black, Material: Vinyl Coated Cloth, Book: Amazon: amzn.to/3qDGmNP
    IDEAL INDUSTRIES INC. SureTrace 61-955 Circuit Tracer Open/Closed Circuit Capability. RED multi segment Display: Amazon: amzn.to/3qH13s6
    IDEAL 61-164 SureTest Circuit Analyzer, CATIII for 300v: Amazon: amzn.to/3KB2z7k
    Siemens SN4040B1200 SN Series 200 Amp Space 40-Circuit Main Breaker Plug-On Neutral Indoor Load Center, Grey: Amazon: amzn.to/3q7JS2R
    Siemens PN3048L1200C PN Series 200 Amp 30-Space 48-Circuit Main Lug Plug-On Neutral Load Center Indoor with Copper Bus, Grey: Amazon: amzn.to/3qYMdME
    Orbit DSC-38 Double Snap Cable Connector, Insulated: Amazon: amzn.to/3JNXYhx
    Minerallac 115 Pre-Galvanized Steel 1 Hole Strap 3/8 Inch Jiffy Clip Pack of 100: Amazon: amzn.to/3JR3vEi
    IDEAL Electrical 36-311 TKO 4 Pcs Hole Cutter Kit - Carbide Hole Cutter Set, Smooth Start Pilot Bit, Carry Case: Amazon: amzn.to/3EVynzC
    IDEAL Electrical 35-782 Sir Nickless Armored Cable Cutter - Metal Rotary Cable Cutter with Handle Knob. Power Tools and Accessories: Amazon: amzn.to/3F92DHy
    Playlist: Electrical Wiring by Sparky Channel: www.youtube.co....
    Playlist: EMT Bending by Sparky Channel: www.youtube.co....
    IDEAL 30-1047 Box Of 50 Twister Proflex Wire Connectors: Amazon: amzn.to/2tz6AGv
    IDEAL 74-027 3/4" EMT ductile iron Bender With Handle: Amazon: amzn.to/2SmCduC
    IDEAL 74-026 1/2" EMT ductile iron Bender w/Handle : Amazon: amzn.to/2CI9pXZ
    Ideal 74-028 BENDER 74-003 W/HANDLE 1": Amazon: amzn.to/2QQdnoD
    IDEAL 74-046 Aluminum Bender with Handle for 1/2" EMT Conduit: Amazon: amzn.to/2SkAMg9
    IDEAL 74-047 Aluminum Bender with Handle for 3/4" EMT Conduit: Amazon: amzn.to/2EK7B3e
    IDEAL 35-409 18" TOOL BACKPACK, BLACK: Amazon: amzn.to/35NOT3l
    IDEAL Industries Smart-Grip Side-Cutting Plier, Plier Handles, 9-1/4" Length, New England Nose High-Leverage with Crimping Die: Amazon: amzn.to/36ixjpB
    IDEAL 35-741 Electrician's Champion 6-Piece Screwdriver Set: Amazon: amzn.to/2qGAlAh
    Ideal Industries 35-936 Adjustable Torque Screwdriver: Amazon: amzn.to/2s1tsO1
    Ideal 44-104 Wire Marker Booklets-Legend-46-90 10 each): Amazon: amzn.to/2KKcaes
    IDEAL 45-621 Dual NM Reflex Super T-Stripper: Amazon: amzn.to/2rqWYJl
    IDEAL 35-238 Magnetic-Tip Measuring Tape, 30-Foot: Amazon: amzn.to/2E7HJwr
    IDEAL 4635 7 Mil Wire Armour Red Professional Vinyl Electrical Tape: Amazon: amzn.to/2rxAq9H
    IDEAL 4635 7 Mil Wire Armour White Professional Vinyl Electrical Tape: Amazon: amzn.to/2LcZ090
    IDEAL 45-605 Preppro Coaxial UTP Cable Stripper: Amazon: amzn.to/2ynmtAQ
    IDEAL 33-793 Compression Hip Kit: Amazon: amzn.to/2xedj4E
    Ideal Industries 33-856 VDV Multimedia Cable Tester: Amazon: amzn.to/3bdvn49
    Ideal Industries 33-866 Test-Tone-Trace VDV Tester Kit Network: Amazon: amzn.to/376evsF
    VDV Multimedia Cable Tester Kit (33-856-A): Amazon: amzn.to/2SrrJe3
    IDEAL 35743 Electrician's Champion 4-Piece Tool Kit: Amazon: amzn.to/2T1tVJ1
    IDEAL Electrician's Champion 12-In-1 Screwdriver: idealnationals...
    IDEAL 35-208 9" Torpedo Level With 5 Vials: Amazon: amzn.to/2yA6y0q
    IDEAL 35-206 3.5" Electrician Level With 2 Vials And Magnetic Jaw: Amazon: amzn.to/2CIgCXX
    IDEAL Industries 31-061 Blue Nylon Jacketed Fiberglass Fish Tape 3/16 Inch x 100 ft S-Class Tuff-Grip™ Pro : Amazon: amzn.to/2RiiB9z
    IDEAL 31-064 Tuff-Grip Pro S-Class Fish Tapes with Leader End Type, 200' Length: Amazon: amzn.to/2SjXWU5
    Amazon Prime Free for 6 months for students. Then, enjoy Prime at half the price, just $7.49/month: amzn.to/3NsFy7Q
    Audible Plus Free for 1 month + 2 free books: amzn.to/3Do6Qrr
    As an Amazon Associate I earn from qualifying purchases.

Комментарии • 51

  • @Bluesman57
    @Bluesman57 Год назад +2

    Another great explanation.

  • @theoisaac9948
    @theoisaac9948 Год назад +3

    Thanks 👍👍

  • @Eddy63
    @Eddy63 Год назад +1

    Good answer Bill ... Thx ...

  • @dwreed63
    @dwreed63 Год назад +1

    GREAT information, thank you! 👍💪👌

  • @AO2007US
    @AO2007US Год назад

    Thanks for explaining this!

  • @undaya
    @undaya 7 месяцев назад

    Looks ok now but how about after you get breakers and wires in panel?

  • @undaya
    @undaya 7 месяцев назад

    Install change over to right of meter.

  • @donl1410
    @donl1410 Год назад

    Good video, Bill!

  • @mrscoot1
    @mrscoot1 Год назад

    If you have main panel outside 7ft away from tiny home on pole 200 amp breaker panel ( bonded neutral and ground, its 1st panel) 2 -8ft. Grounding rods over 6ft. Apart #4 bare copper connects to main panel quadra plex 4 wires 4/4/2/4 connect to inside 200amp breaker panel 7ft away does inside panel seperate neutral and ground. Will be connected by #4 green insulated wire back to main panel 7 ft. Away at bonded neutral/ground bar ( which is connected to 2 grounding rods) does inside panel need seperate grounding rod or rods, would it not interfere with mainpanel rods so close to house unless 2nd panel grounding rods are
    at least 2×8ft. Grounding rods 16ft. Or what distance. Is recommended! Because green wire connects to main panel outside neutral/ground bar and goes underground in PvC conduit to inside sub panel ground bar and seperate ground wire for sub also connects to ground bar( if installed) would interfere by causing alternet loop unless it is installed min. 16ft.= (2× 8ft. Grounding rods ? Remember 2 grounding rods are 7ft. away from each other and only 2-3ft from house where service enters house. Gotten conflicting answers orthe you can never have enough grounding rods( but with the short distance 7ft. they would interfere with each other basically having 2 paths from neutral/ground bar to subpanel ground.

  • @garydudgeon
    @garydudgeon Год назад +2

    Great explanation again Sparky.

  • @AO2007US
    @AO2007US Год назад

    Could the wires from the ATS come to the panel in the middle through the same bottom conduit if it was large enough?
    Also, not directly related to this video but does the code require a disconnect between the ATS and Generator.Thanks!

  • @undaya
    @undaya 7 месяцев назад

    No, just go out meter at bottom and in bottom change over switch. Much more neat.

    • @timgerk3262
      @timgerk3262 7 месяцев назад

      The generator switch added as a retrofit is going to be oddly placed like this most of the time, I reckon.

  • @patrickkelley3408
    @patrickkelley3408 Год назад

    Very helpful,thanks.

  •  Год назад

    que bueno tus videos, saludos

  • @undaya
    @undaya 7 месяцев назад

    Why all the green wires going every which away?

  • @sherpadelgatos
    @sherpadelgatos Год назад

    thank u! very helpful

  • @nathanlindley5354
    @nathanlindley5354 9 месяцев назад

    You do need Myers hubs on the higher nipple as they are above the bottom of the bus bars

  • @damienbender213
    @damienbender213 Год назад

    Thanks sparky 👍⚡⚡⚡

  • @undaya
    @undaya 7 месяцев назад

    This is why you need to stop and go to desk ( may be truck ) and figure what plan is. Boss and or customer may wonder why sitting in truck. This is my office.

  • @vdinhq
    @vdinhq Год назад

    Thanks. Your video addresses my situation directly. I want to install a sub panel next to a main panel on an exterior wall, and the wires for the sub circuits will be spliced in the main enclosure and feed-through a foot of conduit into the sub. However, can the source of power for my sub panel come from another meter of a different address? That is, two houses with different address meters next to each other on the same lot, and the power for the sub panel installed on house A comes from house B. (Solar is installed on B but underutilized.)

    • @SparkyChannel
      @SparkyChannel  Год назад +1

      Wow, but that is illegal without house B's permission.

    • @vdinhq
      @vdinhq Год назад +1

      @@SparkyChannel House B is our ADU. In California, all new units must have solar.

    • @GeorgeVCohea-dw7ou
      @GeorgeVCohea-dw7ou Год назад

      This is almost certainly something to involve an attorney and an electrician on to get everything down on paper and filed as necessary. The next owners will want to be aware of this, even and especially if you intend to be there long haul.

    • @idhatemet00
      @idhatemet00 Год назад +1

      Ask your inspector or call the presiding utility company before you do anything.

  • @normferguson2769
    @normferguson2769 Год назад

    I would have dropped the pass-through cables in lower conduit to bypass the second box just to keep it easy for future electricians.

  • @mnolan5095
    @mnolan5095 Год назад

    It's going to get quite busy in the main panel once you start putting circuits in...

  • @AngelFuller-j1x
    @AngelFuller-j1x Год назад

    I’m not sure if you saw my other comment . But is there anyway I can get intouch with you directly?

  • @stevenpersinger6577
    @stevenpersinger6577 5 месяцев назад +1

    Why in the world would you even install that way. That makes no sense

  • @kenbrown2808
    @kenbrown2808 Год назад +3

    perfectly legal. but it sure makes the transfer switch look like an afterthought.

    • @SparkyChannel
      @SparkyChannel  Год назад +1

      So true. Thanks Ken!

    • @shogunsmoke491
      @shogunsmoke491 Год назад +1

      In my experience, they typically are. 😂

    • @kenbrown2808
      @kenbrown2808 Год назад +1

      @@shogunsmoke491 that doesn't mean it has to LOOK like it.