Hello. Kya iss model mein temperature ka upper limit and lower limit set kdr sakte hai? For example, below 40°c heater should turn on and above 70°c heater should turn off
Dear, 1. If input supply AC 1-Phase,then, a. Connect Line(L) to terminal no. 1 b. Connect Neutral(N) to terminal no. 2 2. Relay Terminals use as per circuit requirements. 3. Input Sensor: A. If input sensor is Thermocouple(TC), then a. TC + connect to terminal no. 8 b. TC - connect to terminal no.9 B. If input sensor is RTD a. RTD White wire + connect to terminal no. 8 b. 2 Red wires are common to be connect at terminal no. 9 & 10. IN CASE OF RTD: The resistance between terminal no. 8 & 9 and also between 8 & 10 should be 110 to 116 ohm at room temperature. The resistance between terminal no. 9 & 10 should be 0 Mega ohm.
Sir ji kya aap temperature controller oil extraction machine jo ghar pe use karte hai usme kaise fit karte hai uska blog banayege please
Good job 🎉❤
Thanks
Hello. Kya iss model mein temperature ka upper limit and lower limit set kdr sakte hai?
For example, below 40°c heater should turn on and above 70°c heater should turn off
please set in
Level-1
SPLL
SPHL
ACt1
CntL
FOR ANY OTHER PLEASE CALL.
Sir powder coating oven me konsa rtd sensor used kare
Oven ka temperature kita
Sir 200 se 300
Bhai mera wala Scrubber machine me lagaya hai plz Thoda bata do na kesa were lagaye
Plzz bhaiya
Ke type kaise set Karen
Bhai please ik bar sara process bta doo konsi wire kaha lage giii
Dear,
1. If input supply AC 1-Phase,then,
a. Connect Line(L) to terminal no. 1
b. Connect Neutral(N) to terminal no. 2
2. Relay Terminals use as per circuit requirements.
3. Input Sensor:
A. If input sensor is Thermocouple(TC), then
a. TC + connect to terminal no. 8
b. TC - connect to terminal no.9
B. If input sensor is RTD
a. RTD White wire + connect to terminal no. 8
b. 2 Red wires are common to be connect at terminal no. 9 & 10.
IN CASE OF RTD: The resistance between terminal no. 8 & 9 and also between 8 & 10 should be 110 to 116 ohm at room temperature. The resistance between terminal no. 9 & 10 should be 0 Mega ohm.