How to solve outdoor blink 17 times & indoor not cold | Mitsubishi StarMex air conditioner
HTML-код
- Опубликовано: 15 сен 2024
- Brand : Mitsubishi Electric inverter R410A
Model : MXY-2G20VA
Symptoms : Indoor not cold & outdoor blinking 17 times.
Cause : Outdoor unit A LEV body jam.
Action : Using donut magnet to adjust open and close.
#bonmj #bonmj #mitsubishi
Make full video about donut magnet.....
Great Sir ❤
Thanks
Sir. This is temporary repair? The valve will jam again? Mitsubish electric system 2 quite a lot of this problem. Is control board problem sometimes? Also will no totally close the valve.
👍👍
感谢您的分享,让我有机会提升。
谢谢
Great video like always 👍
Thanks
good job thank for sharing
Thanks Sifu
Thanks bon !
You're welcome 😊
So hot today Mr bon 😂
Hi, Janshaw ya
Thanks sir
Welcome
Very good!!😎🇧🇷
Thanks
Hi Bon MJ, what is your company name & contact ? I am trying to look for your company for our aircon. Thanks !
MXY-4G33 outdoor blink 12times and indoor not cooling. what happen?
Hi, one of the split indoor unit automatically turn on when the outdoor unit is turn on. Does this mean the unit relay is spoilt? The indoor unit cannot be turn off using the manual on-off button or the remote controller. Mine is LG brand btw
May indoor Pcb faulty
👍👍👍 is it a common problem for Mitsubishi electric air con system?
Got few case
what is CUT IN mean/ LEV use for.
Normally we say cut in mean cu received signal from indoor and outdoor start running.
LEV is linear expansion valve,is open and close the valve
if LEV body can't close(totally open), cold when fcu off. donut magnet can adjust settle problem?
Force open and close should no problem, after adjust you need to monitor
Sg where can buy donut magnet?
May I knowdonut magnet hole size?
🎉🎉🎉🎉🎉🎉
Thanks
where to get that donut magnet???😆
Try online