HVAC 3-Phase Motors / 9 and 12 Lead Motors

Поделиться
HTML-код

Комментарии • 19

  • @sd5722
    @sd5722 3 года назад +1

    Nice work.
    Keep it up👍

  • @wojtekkucharski1270
    @wojtekkucharski1270 2 года назад

    Great video. Answered my question with 12 lead wire whether to use Y or D

  • @user-dj6wo1jo6r
    @user-dj6wo1jo6r Год назад

    Great video. Am interested in the wye delta motor wiring and trouble shooting

  • @chriscrawley1014
    @chriscrawley1014 2 года назад +1

    This is awesome! Would you be able to email me the PowerPoint? Great video

  • @JamesJoseph-te3jm
    @JamesJoseph-te3jm 4 месяца назад

    i have a 12 wire toshiba 7.5 hp 3 phase, how do i test the windings for continuity?

  • @whirlwind8825
    @whirlwind8825 11 месяцев назад

    I have a 480 volt motor I pulled from a old machine . The motor has the 9 wire high voltage configuration ... there was also a #10 and #11 wire but no #12 wire ... The #10 and #11 were just capped off with a wire nut .. I was curious as to why I have only 11 wires... or if they are not #10 and #11 but maybe a thermal that is bypassed ?

  • @mackeverhart1041
    @mackeverhart1041 2 года назад

    I have a GE sever duty motor 12 wire. I have it wired 9-5-11-L3 4-8-10-L2 6-7-12-L1 runs at 900 rpm on vfd (3510 rpm on plate ) I know the vfd is set up right. Why will it not run 3510 like it says?

    • @music6101
      @music6101  2 года назад

      Mack,
      On the VFD it my be set for a 8-pole motor which is 900 RPM at 60Hz, a 3600 RPM motor is a 2-pole motor
      RPM = (120 x Hz) / # of Motor Poles

  • @sd5722
    @sd5722 3 года назад +1

    One question
    Why we need 12 or 9 lead motor instead of 6 lead motor.
    Where these motors used

  • @oscarmendez1372
    @oscarmendez1372 2 года назад

    Question: I'm going to install a used system 27 Hp bitzer compresor, for ultra freezing, this system was assembly in china, installed originally in Seattle Washington, and I'm goin to install here en Baja Sur Mexico. The evaporator has 4 Chinese motors 3/4 hp 220/ 380 V, and each motor has 8 leads, 6 black lead numbered from 1 to 6 and 2 more Yellow leads. I notes that it were connected to 220 volt 3 face, L1 to leads 1,5 L2 to leads 2,6 and L3 to leads 3,4 The other two yellow lead i don't know exactly where were connected, I'm assuming something for controls. Did you saw this kind of connections before? do you have any idea what the yellow leads are for? there is not information at all in this motor and system, no serial numbers no model numbers only the compresor who was made in Germany. The evap motors only has the voltage, Hp and amperes that's it.
    Thank you in advance.
    I'm apologize, my English is not the best.

    • @rsburke71
      @rsburke71 Год назад

      Yellow leads are for thermal overload

  • @vicentecarrasco3653
    @vicentecarrasco3653 3 года назад

    hi,what happen if the 12leads motor run in 3 coils?the speed will be slow?

    • @megaturon1212
      @megaturon1212 3 года назад +1

      It can run with the same speed but the torque will be reduced, assuming you applied the rated voltage per coil.

    • @vicentecarrasco3653
      @vicentecarrasco3653 3 года назад

      @@megaturon1212 when the torque will be slow the motor will damage?

    • @megaturon1212
      @megaturon1212 3 года назад +1

      @@vicentecarrasco3653 It depends on the load, you need to check the motor current.
      If the measured motor current exceeds the rated current on the nameplate, the motor will burn.

  • @axelateon1384
    @axelateon1384 Год назад

    why never when a compressor is in a vacuum???????

    • @rsburke71
      @rsburke71 Год назад

      Cannot not arc to other leads or to ground if there is no atmosphere to carry the charge