  • @matthiasgoetz458
    @matthiasgoetz458 7 месяцев назад

    Hi thanks a lot for this video, was struggeling today a lot to get it running similar like you have, what doesn´t work on my side is the Life List for the DP sensors, only for the PN devices. Do you have experience how to get the Life List for DP working or do you have an idea where to step on?

    • @IOTConnectivity
      @IOTConnectivity  7 месяцев назад

      Check your PGPC interface settings are set correctly and you can see the slaves from here. Are you connected directly to DP network?

    • @matthiasgoetz458
      @matthiasgoetz458 7 месяцев назад

      @@IOTConnectivity no i am connected to a PLC 1500 via ethernet and using this PLC as datasetgateway, reading and writing sensors is working but the DP address changing doesn´t work via PDM. Actually we changed the DP addresses via a Field PG with DP CP using Simatic Manager but we would like to know how to get the Life List and DP Change via PDM running.

  • @geraldpavoz771
    @geraldpavoz771 3 года назад

    I cannot establish routing communication with PDM: A PC is connected to the PN - X2 network of the CPU 1516 and an ET200SP with HART module is connected to the PN - X1 network. I declared the routing in PDM with S7 DSGW (PLC Simatic) but it does not work from PROFINET-X2 to PROFINET-X1. However, from PROFINET-X1 to PROFIBUS DP-X3 it works. It's possible ?

    • @IOTConnectivity
      @IOTConnectivity  3 года назад

      The routing for PDM will not work accross X1 & X2. I has to have all the IO and the PDM connnection on the X2 Profinet Port.