Single Stack Sanitary Plumbing System (3-17b) (a) The single stack system may be used for buildings up to six storeys high where there are single appliances connected to a discharge stack or where the sanitary appliances/ fittings are closely grouped round a discharge stack which is large enough to limit pressure fluctuations without the need for a ventilating stack. (b) The main discharge stack shall have a uniform diameter of not less than 150mm without offset throughout its entire length. However, for conventional housing, a main discharge stack of 100mm diameter may be provided. (c) The length of the discharge pipe connecting to the discharge stack shall not be more than 2.5m and there shall be not more than two connections made to the discharge pipe.
যদি আর ১টা ভিডিওতে দেখাতেন যে আপনারা কিভাবে ঐ ৬" পাইপের টির মুখ থেকে কিভাবে প্রত্যেকটা ফ্লোরের টয়লেট- গুসলখানায় ৪" বা ৫" বা ৬" পাইপ কিভাবে মিলান তবে আমি অনেক উপকৃত হবো। আর আল্লাহ-তাআলার কাছে আপনার জন্য দোয়া করি আল্লাহ যেন আপনার মনের নেক বাসনা পোরন করেন। আমিন
Ventilated Stack Sanitary Plumbing System (a) The ventilated stack system may be adopted in situations where there are close groupings of sanitary appliances around the discharge stack in buildings up to thirty storeys high. (b) The main discharge stack shall have a uniform diameter of not less than 150mm throughout its entire length. (c) Separates discharge stack (secondary discharge stack) of diameter not less than 100mm shall be provided to serve the second and third storeys. This secondary discharge stack shall be extended to serve as ventilating stack. (d) Cross venting between the ventilating stack and the discharge stack shall be provided at third, sixth, ninth, twelfth, fifteenth, eighteenth, twenty-first, twenty- fourth and twenty-seventh storeys. (e) The length of a discharge pipe connecting to the discharge stack shall not be more than 2.5m and there shall be not more than two connections made to the discharge pipe.
sanitary Systeams design 3 types 1) less then -6 sty of building single ventilated systems 2) higher than 6sty lower them 20 sty ventilated stack systems 3) more then 30 sty fully ventilated systems.
আমার ৫ তলা বিল্ডিং এ প্রতি তালায় ৪ টি করে বাথরুম। এখন প্রতি বাথরুম থেকে মিস্ত্রি ৪ ইঞ্চি পাইপ দিয়ে ময়লা আর পানির লাইন একসাথে নামিয়েছে। ভাই এখন অনেকেই বলতেছে ভবিষ্যতে সমস্যা হবে। আপনার নাম্বার পেলে একটু পরামর্শ করতাম। এখনো টাইলস করাইনি এখন আমার করনীয় কি ভাই একটু বলেনতো। খুব চিন্তায় আছি
ফলছাদের ভিতরে কিভাবে লংট্রাপ লাগাতে হয়?? কমেট থেকে লংট্রাপ কতটুক নিচে দিতে হয়এবং কোন কোন ফলছাদে বিম থাকে আবার বিম থাকেনা ঐ কাজটা কিভাবে করতে হয়??বললে উপুকার হত
চাচা আমি একটা ৪" পাইপের উপর দিয়ে ৩" পাইপ নিয়ে যাবো কিভাবে? এটা কিন্তুু অলের গাদিয়ে যাবে? কিন্তুু আমি ওটা বুঝতে পারলাম না? আমি ওটা কিভাবে দেবো একটা ভিডিও দেন??? অপেক্ষা আছি চাচা ধন্যবাদ???
চাচা আমি আপনাকে যে কথাটা বলছি সেটা হচ্ছে? আমার বাথরুমে গেসপাইপ ওটানো আছে? আমি এখন আমার বাসার সাদের পানি ৩" পাইপ দিয়ে নিয়ে যাবো কিন্তুু এটা আমি দেয়াল দিয়ে নিয়ে যাবো কিন্তু আমার বাথরুমে ৪" গেস পাইপ আছে? তাহলে আমি এখন ওটার উপর দিয়ে কিভাবে নিয়ে যাবো সেটা একটু বুজার জন্য একটা ভিডিও দেন?? আরো একটা কথা আপনি ১" বা ৩/৪ পাইপের পেচ কাটান কি ডায় দিয়ে??অটো নাকি মেনুয়োল একটু দেখাতে বলছি? কারণ আমি একটা অটো ডায় কিনতে চাই? সেটা ভালো হবে কিনা 'জানতে চাই?? এবং একটা ভিডিও দেখতে চাই??? ধন্যবাদ অপেক্ষায় আছি চাচা????
@@SanitaryWorkEducationCenter আর ৭ তলা বিল্ডং থেকে ৭ টা টয়লেট ও ৭ টা কিচেন এর জন্য ৪"পাইপ দিয়ে নামালে কোন সমস্যা হবে কিনা।।।।।।।নাকি ৬" দিয়েই নামাতে হবে ।।।।।।
@@SanitaryWorkEducationCenter ভারতে একটি কোম্পানী জার নাম হল৷jaquar.....এই কোম্পানীর নাম লেখে সাচ কোরলে দেখা যায়।।।ডাইভেটার। যাকিনা একটি কল।।।।জাদিয়ে ঠান্ডা/গরম । পানি বার হয়
খুব সুন্দর কাজ
Dhonnobad
আমিও একজন প্লাম্বার... আপনাদের কাজ গুলো দেখে অনেক ভালো লাগলো
ধন্যবাদ, আপনার মূল্যবান মতামতের জন্য।
মাশা আল্লাহ
জাজাকাল্লাহু খায়রান।
Good work sir❤️❤️❤️❤️❤️
Thanks for your Comment 🥰
অনেক সুন্দর
জাযাকাল্লাহ
আপনার কাজ গুলো অনেক সুন্দর
خزاك الله
মাশাল্লাহ
জাযাকাল্লাহ।
Assalamo alaikom
চাচা ১০ তলার উপরে সুইংমিন পুল এর লাইন কিভবে করা যায় এ নিয়ে একটা ভিডিও দেন
অপেক্ষা করুন,চেষ্টা করবো ইনশাআল্লাহ।
Single Stack Sanitary Plumbing System (3-17b)
(a) The single stack system may be used for buildings up to six storeys high where there are single appliances connected to a discharge stack or where the sanitary appliances/ fittings are closely grouped round a discharge stack which is large enough to limit pressure fluctuations without the need for a ventilating stack.
(b) The main discharge stack shall have a uniform diameter of not less than 150mm without offset throughout its entire length. However, for conventional housing, a main discharge stack of 100mm diameter may be provided.
(c) The length of the discharge pipe connecting to the discharge stack shall not be more than 2.5m and there shall be not more than two connections made to the discharge pipe.
যদি আর ১টা ভিডিওতে দেখাতেন যে আপনারা কিভাবে ঐ ৬" পাইপের টির মুখ থেকে কিভাবে প্রত্যেকটা ফ্লোরের টয়লেট- গুসলখানায় ৪" বা ৫" বা ৬" পাইপ কিভাবে মিলান তবে আমি অনেক উপকৃত হবো। আর আল্লাহ-তাআলার কাছে আপনার জন্য দোয়া করি আল্লাহ যেন আপনার মনের নেক বাসনা পোরন করেন। আমিন
ইনশাআল্লাহ,অপেক্ষা করুন।
ধন্যবাদ
৬" ডোর টি দেওযা লাগত বাহিরে
Ventilated Stack Sanitary Plumbing System
(a) The ventilated stack system may be adopted in situations where there are close groupings of sanitary appliances around the discharge stack in buildings up to thirty storeys high.
(b) The main discharge stack shall have a uniform diameter of not less than 150mm throughout its entire length.
(c) Separates discharge stack (secondary discharge stack) of diameter not less than 100mm shall be provided to serve the second and third storeys. This secondary discharge stack shall be extended to serve as ventilating stack.
(d) Cross venting between the ventilating stack and the discharge stack shall be provided at third, sixth, ninth, twelfth, fifteenth, eighteenth, twenty-first, twenty- fourth and twenty-seventh storeys.
(e) The length of a discharge pipe connecting to the discharge stack shall not be more than 2.5m and there shall be not more than two connections made to the discharge pipe.
sanitary Systeams design 3 types
1) less then -6 sty of building single ventilated systems
2) higher than 6sty lower them 20 sty ventilated stack systems
3) more then 30 sty fully ventilated systems.
গ্যাস পাইপ এর রেট কেমন নেন
আপনাদের সাতে কাজ করা জাবে......
Vai basa kotai
অনেক জরুরী ভাই ।।।।।।।।৭ তলা ভবনে একপাশে প্রতি তলায় ১ টি করে ৭ টা টয়লেট আছে ।।।এখন আমি কি ৪" পাইপ দিয়ে লাইন টানতে পারব?????অনেক জরুরী ভাই
।।।
হ্যাঁ,পারবেন।
তবে পানির এবং ময়লার লাইন আলাদা হবে, এবং উভয় লাইন ৪ ইঞ্চি পাইপ দিয়ে করবেন।
@@SanitaryWorkEducationCenter অনেক ধন্যবাদ ।।।আমার ৬০% কাজের সমস্যার সমাধান আপনার কাছ থেকে পাই ।।।আল্লাহ আপনার হেফাজত করুক ।।।
আমীন, ইয়া রাববাল আ'লামীন।
আমার ৫ তলা বিল্ডিং এ প্রতি তালায় ৪ টি করে বাথরুম। এখন প্রতি বাথরুম থেকে মিস্ত্রি ৪ ইঞ্চি পাইপ দিয়ে ময়লা আর পানির লাইন একসাথে নামিয়েছে। ভাই এখন অনেকেই বলতেছে ভবিষ্যতে সমস্যা হবে। আপনার নাম্বার পেলে একটু পরামর্শ করতাম। এখনো টাইলস করাইনি এখন আমার করনীয় কি ভাই একটু বলেনতো। খুব চিন্তায় আছি
চাচা ফ্লোর টাফের কাজের কোন ভিডিও থাকলে দিলে উপকার হতো।
অপেক্ষা করুন।
চাচা টি ছাদ থেকে কতফিট নিচে রাখতে হবে
জুলুন্ত ভীম হলে ভীমের নিচ দিয়ে টি ফিটিং করতে হবে,আর যদি কনসাল ভীম হয়,তাহলে ছাদের নিচে ক্লিয়ার রাখতে হবে,আশাকরি বুঝতে পেরেছেন,ধন্যবাদ।
অফ সাইড কয়তলায় দিয়েছেন
আমীও প্লাবার কাজ করী আপনার সাথে কী কাজ করা যাবে একটু যানান
cpvc pipe primiar diey clin koren na kenw
পাইপ দেয়ার জন্য যে ডাগ ঐ খান দিয়ে দিলেন্না কেন ভাই।
Your design standard under code of practice ?
???
Brother, I did not understand you correctly, please elaborate, thank you.
অফ সাইড কয়তলা দিয়েছেন এবং কেন?
গ্যাস পাব কি খুব জরুরী. এটা না দিলে কি কোন সমস্যা হবে
হ্যা,জরুরী।
Dada electronic kaj ki apne koren
জ্বীনা।
ফলছাদের ভিতরে কিভাবে লংট্রাপ লাগাতে হয়?? কমেট থেকে লংট্রাপ কতটুক নিচে দিতে হয়এবং কোন কোন ফলছাদে বিম থাকে আবার বিম থাকেনা ঐ কাজটা কিভাবে করতে হয়??বললে উপুকার হত
এই কাজটা কোন থানায়
Kapasia, gazipur
৯ তলার আউট সাইডের জন্য ৪" পাইপের পুরুত্ব কত দিতে হবে?
VAI AR KE NEW VIDEO PAVO NA
সোয়া ইঞ্চি মানে কত mm?
চাচা আমি একটা ৪" পাইপের উপর দিয়ে ৩" পাইপ নিয়ে যাবো কিভাবে? এটা কিন্তুু অলের গাদিয়ে যাবে? কিন্তুু আমি ওটা বুঝতে পারলাম না? আমি ওটা কিভাবে দেবো একটা ভিডিও দেন??? অপেক্ষা আছি চাচা ধন্যবাদ???
আপনার প্রশ্নটি ক্লিয়ার বুঝা যাচ্ছে না।
আপনি কোনটা বুঝতে পারেননি?
চাচা আমি আপনাকে যে কথাটা বলছি সেটা হচ্ছে? আমার বাথরুমে গেসপাইপ ওটানো আছে? আমি এখন আমার বাসার সাদের পানি ৩" পাইপ দিয়ে নিয়ে যাবো কিন্তুু এটা আমি দেয়াল দিয়ে নিয়ে যাবো কিন্তু আমার বাথরুমে ৪" গেস পাইপ আছে? তাহলে আমি এখন ওটার উপর দিয়ে কিভাবে নিয়ে যাবো সেটা একটু বুজার জন্য একটা ভিডিও দেন?? আরো একটা কথা আপনি ১" বা ৩/৪ পাইপের পেচ কাটান কি ডায় দিয়ে??অটো নাকি মেনুয়োল একটু দেখাতে বলছি? কারণ আমি একটা অটো ডায় কিনতে চাই? সেটা ভালো হবে কিনা 'জানতে চাই?? এবং একটা ভিডিও দেখতে চাই??? ধন্যবাদ অপেক্ষায় আছি চাচা????
অপেক্ষা করুন,ইনশাআল্লাহ ভিডিও আসবে।
@@SanitaryWorkEducationCenter ধন্যবাদ
গ্যাস পাইব কোথা থেকে সনজুগ করা হয়েছে?
প্রতিটি তলায় ফল ছাদের ভিতর থেকে সংযোগ দেয়া হয়েছে,সামনে এ লাইনের ভিডিও আসবে,তখন দেখে নিবেন,ধন্যবাদ।
হাতের মৌওজা গুলো কত করে নিছে
ভাই ৭ তলা বিল্ডং এর এক পাশে ১ থেকে ৭ তলায় মোট ৭ টা টয়লেট ও ৭ টা কিচেন"""" শুয়া ইঞ্চি """" পাইপ দিয়ে লাইন নামাইতে পারবো??????????
কমপক্ষে দেড় ইঞ্চি পাইপ দিতে হবে।
@@SanitaryWorkEducationCenter আর ৭ তলা বিল্ডং থেকে ৭ টা টয়লেট ও ৭ টা কিচেন এর জন্য ৪"পাইপ দিয়ে নামালে কোন সমস্যা হবে কিনা।।।।।।।নাকি ৬" দিয়েই নামাতে হবে ।।।।।।
বাংলা দেশে কি হাই ফোল ডাইভেটার পাওয়া যায়
'ডাইবভেডার' বলতে কী বুঝিয়েছেন?
@@SanitaryWorkEducationCenter ভারতে একটি কোম্পানী জার নাম হল৷jaquar.....এই কোম্পানীর নাম লেখে সাচ কোরলে দেখা যায়।।।ডাইভেটার।
যাকিনা একটি কল।।।।জাদিয়ে ঠান্ডা/গরম । পানি বার হয়
ওযাল হ্যাঙ্গ কোমটের দাম কেমন আমাদের দেশে৷
জি ভাইজান,পাওয়া যায়।
RAK কোম্পানির পি ট্র্যাপ কমোড ৮৫০০ টাকা।
বাজনা ওয়ালা ভিডিও সবাই দেখে না। আপনার মনে রাখা উচিত ছিল।আল্লহ কে ভয় করি।
ভাইজান,এটি বাজনা ওয়ালা ভিডিও না। এটি অনলি ভোকাল ইসলামিক গান, এতে কোনো প্রকার মিউজিক ব্যাবহার করা হয়নি।
আশাকরি বুঝতে পেরেছেন, জাযাকাল্লাহু খায়রান।
চাচা আপনার ইমু নাম্বারটা দেন পিজ
আমাদের নাম্বার শেয়ার করা হয় না,আপনার ফোন নাম্বারটি দিন,আমরা আপনার সাথে যোগাযোগ করবো ইনশাআল্লাহ।
@@SanitaryWorkEducationCenter 01727473510