in my case, the replacement of four 35V 220uF capacitors helped, previously I checked the voltage on the DC BUS and it was ok also the voltage of 24V DC between terminals 12 and 20 was fine
For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
I have an old vlt 2800 which the display will come on after a long time when energized but today the display stayed out, what I did: put the power out and took the wire out on connector 18 and 20 and then I put the power on. Direct the display started up 🤗 Lucky me.
For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
It's definitely significant for us, thank to so many
You're welcome, we are happy the video helped.
in my case, the replacement of four 35V 220uF capacitors helped, previously I checked the voltage on the DC BUS and it was ok also the voltage of 24V DC between terminals 12 and 20 was fine
For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
I have an old vlt 2800 which the display will come on after a long time when energized but today the display stayed out, what I did: put the power out and took the wire out on connector 18 and 20 and then I put the power on. Direct the display started up 🤗
Lucky me.
For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
Blank display, I think that problem is in firmware of LCP or interrupt data stream.
For installation, start-up, programming and troubleshooting assistance please email: Drives.TS.NA@Danfoss.com
or if you need immediate assistance contact Danfoss Drives 24/7 tech support at: +1 888 DANFOSS (326-3677)
DC bus overvoltage