Differential Protection of Power Transformer Webinar

Поделиться
HTML-код
  • Опубликовано: 7 июл 2021
  • НаукаНаука

Комментарии • 3

  • @ImranKhan-nu6xw
    @ImranKhan-nu6xw Год назад

    Thanks for sharing such a informative vedio

  • @rjshtk
    @rjshtk 8 месяцев назад

    At 30:20, are you sure that you need to have an interposing CT of YNd5??? I think it is wrong. If the Differential relay is inserted at the position shown as in the diagram, you need an ICT of YNd1 and not YNd5 to cancel out the phase shift of +30 degrees introduced on the secondary winding of the transformer.!! Correct me if I am wrong please!!

  • @3c_miftahulhakim40
    @3c_miftahulhakim40 10 месяцев назад

    excuse sir, can i get manual book from this presentation? thanks