can you guide me how to where to connect the vista to the network like where should I connect the phone line and the ethernet cable ( I have the same one vista 32fb)
Hi again sorry if I ask so much questions, in the vista 20p how can I wire it so the strobes don’t flash in code 3? Is that in programming? Also what resistors should I use in the NAC and zones? Thanks
I'm not sure if you can set the nac to continuous in fire mode. Resistors are 2.1-2.2k, you don't need a resistor for the nac unless the jumper for Bell supervision has been cut
No, it has to be programmed and be connected to some sort of communications line. Even then, you'll still need to program it. The vista by itself can't call the police anyway, it has to be programmed to dial into a central station and from there the central station will dispatch fire, police, medical etc
On the vista 20p what terminals do you wire the horn strobe? Where do you wire the pull station? Can anyone give me some info on how to wire this ( I know it’s not code complaint)
awesome video! i have a vista 32FB
can you guide me how to where to connect the vista to the network like where should I connect the phone line and the ethernet cable ( I have the same one vista 32fb)
Hi fire tech! Is there a way for me to wire a 24/7 audible into my panel without it saying fault 02? It’s driving me crazy thanks
Awesome video!! Looks really nice 👍. Do you have any videos on how to power cycle a fire alarm panel? If not, could you do a video on it?
Power cycling is when you disconnect all the power sources, wait like a minute, and then power it back up again
@@FireTech7 Thank you.
Nice
On the vista 20p I accidentally put the power 1 and 2 on 3 by accident. Will my panel break?
Test it with 1 and 2
@@FireTech7 ok thanks
Awesome
Hi again sorry if I ask so much questions, in the vista 20p how can I wire it so the strobes don’t flash in code 3? Is that in programming? Also what resistors should I use in the NAC and zones? Thanks
I'm not sure if you can set the nac to continuous in fire mode. Resistors are 2.1-2.2k, you don't need a resistor for the nac unless the jumper for Bell supervision has been cut
@@FireTech7 okay tysm!
@@jzzhang726 you need to buy a relay module and wire your strobes to it then program it to be a continuous output on 24 hr fire zones
@@alexandersalarms5380 alright thanks !
Is it possible to have the keypad siren or piezo (built in) to turn off, i have a 6160 keypad
You can disconnect it if that's what you're asking
@@FireTech7 how?
The speaker plugs into the board and can be disconnected
@@FireTech7 so you don’t have to permanently cut anything?
@@a6cct no sir
will my vista 20p call the police if I don’t have monitoring or a phone line? thanks
No, it has to be programmed and be connected to some sort of communications line. Even then, you'll still need to program it. The vista by itself can't call the police anyway, it has to be programmed to dial into a central station and from there the central station will dispatch fire, police, medical etc
@@FireTech7 okay thanks so I can press the panic button all I want?
Yes, as long as it's not connected to any sort of monitoring
@@FireTech7 okay tysm happy new year
On the vista 20p what terminals do you wire the horn strobe? Where do you wire the pull station? Can anyone give me some info on how to wire this ( I know it’s not code complaint)
Terminals 3 and 4 is the nac. 3 is positive and 4 is negative. A pull station would go on zone 1 and needs to be configured for fire
@@FireTech7 TYSM!