PS98 Sequence Networks of Earthing transformer

Поделиться
HTML-код
  • Опубликовано: 15 дек 2024

Комментарии • 18

  • @avradeepdas1606
    @avradeepdas1606 4 года назад

    Beautifully described. Very nice.

  • @kmnkr24
    @kmnkr24 4 года назад

    Hi,
    Thank you for your nice lectures ...
    To enhance this lecture technically more correct, we can go by taking industrial powersystem as an example (where it ll be YNd1/11 - step down trafo ... and Delta side will be grounded via grounding trafo... )
    and to add one more point, Generating stations usually have YNd1/11 (step up trafos)
    :)

  • @sunjang1905
    @sunjang1905 2 года назад

    Thank you for providing comprehensive lecture

  • @surendrakverma555
    @surendrakverma555 2 года назад

    Very good lecture Sir. Thanks 🙏🙏🙏🙏🙏🙏🙏

  • @paulthompson5856
    @paulthompson5856 2 года назад

    Good video. We have an 11kV earthing transformer with an earthed star connected primary winding and a secondary winding with a broken delta connection with a resistor that limits the primary winding current to 60A. How do you determine/model the zero sequence impedance of a broken delta connected transformer. thanks

  • @MANOJKUMAR-mb2uw
    @MANOJKUMAR-mb2uw 3 года назад

    Sir what happens if there is no path for circulating currents.

  • @cricketinformationcapsule
    @cricketinformationcapsule 4 года назад

    Superb sir

  • @gonencakcam4335
    @gonencakcam4335 4 года назад

    Hi, thanks for these kind of videos.
    1- How can we calculate zero sequence impedance of zig-zag transformer ? As you mentioned, during phase to ground fault, only impedance that effect to our ground fault short circuit current is zero sequence of zig-zag transformer. Also other component will be effect on the path of that faulty line.
    System Voltage (L-L)=10,5Kv
    Irated/phase=100A
    Short Circuit current in neutral=1000A, 10sec
    Ohm/per phase = 18,2 ohm/phase
    2- On ETAP program, below informations are needed. But I could not understand these value is ohm or pu values of zero sequence. Even I am not sure these values zero or not ? If I put ohm/per phase values, ground fault is going to limit from 15kA to 2kA. I do not know how it calculate ? Do you have any advice ?
    Impedance;
    Ohm= ..... --> Etap Help page said that ''Enter grounding resistor or reactor in ohms''
    X/R= ...... --> Etap Help page said that ''Enter the grounding transformer X/R ratio''

    • @gonencakcam4335
      @gonencakcam4335 4 года назад

      Lectures in Electrical Engineering
      Let me ask different way. How can we calculate zero sequence impedance of zigzag grounding transformer ?

  • @mallikarjunayh6345
    @mallikarjunayh6345 2 года назад

    Hi Sir, its a very informative lecture. I have a question, can we convert IT Earthing network to TN using Zigzag transformer at LV side (415V), but we cant use Earthing resistor in neutral of Zigzag transformer. Is it possible?

  • @sanjibkumardas6521
    @sanjibkumardas6521 4 года назад

    Thanks a lot sir for the sequence diagram for earthing transformer..these kind of informative videos helps a lot in our work field....sir i have 1 more request..can u provide sequence diagram of autostransformer having delta as tertiary stabilising winding(YNyn0d11 as well as Yy0d11)?

  • @biswaljayanti665
    @biswaljayanti665 4 года назад

    Sir can u provide a sequence network of 3 phase transformer consists of HV star,intermediate volatage star and lv voltage delta for example 220/132/33 KV transformer

  • @sanket.shelkar
    @sanket.shelkar 4 года назад

    sir please add subtitles

    • @sanket.shelkar
      @sanket.shelkar 4 года назад

      @@lecturesinelectricaleng ruclips.net/video/qfJthDvcZ08/видео.html