Restricted Earth Fault Protection | Restricted Earth Fault Relay | Hindi

Поделиться
HTML-код
  • Опубликовано: 1 янв 2025

Комментарии • 333

  • @electricalwithabhishekjoshi
    @electricalwithabhishekjoshi  3 года назад +16

    Video Dikhne mein agar problem ho rai ho to comment karke bataye.. Kya Video wapas banana chahiye??

    • @hirennavadiya147
      @hirennavadiya147 3 года назад +2

      No problem.. Ok hey.

    • @sudhirskamble
      @sudhirskamble 3 года назад +1

      please make on insta. overcurrent, tcs, lbb and autoreclouser

    • @helpelectricals9410
      @helpelectricals9410 3 года назад +2

      Sir jee Industries me cable Selection ke bare ma dijhaye..with current Dansity and sqmm and Amp. Or Cable try type and Selection

    • @rahulyadav-du9po
      @rahulyadav-du9po 3 года назад

      Sir no problem in video. I want to know smthg more.....
      How is the connection of relay when we use REF for a line? and
      What is REF non directional stage 1 start or stage 2 start and stage 3 start

    • @kaifsaif184
      @kaifsaif184 3 года назад +1

      No sir. Great.
      Your explanation is awesome

  • @QammarabbasKhan-fe3kz
    @QammarabbasKhan-fe3kz Год назад +1

    Your are great sir i am from Pakistan .Even difficult things become easy with your way explaining.

  • @debdutmajumder9939
    @debdutmajumder9939 2 года назад

    Today I read this scheme from the book of JB Gupta, I hardly understood the working principle, but after watching this video, it's crystal clear. Thank you

  • @niteshchourasia500
    @niteshchourasia500 3 года назад +1

    It's is very good Subject sir that you clearlified in very easy way.It support us for in troubleshooting in problem

  • @badgujarminesh6776
    @badgujarminesh6776 2 года назад

    Ye video dekhkar aaj muze lag raha hai interview me agar muze pucha jaye aur me definitely iska ans kar pauga and mera impression bhi positive rahega..

  • @sayonarasheikh6974
    @sayonarasheikh6974 2 года назад

    Sir apane bahot achha bataya hai.....I m also electrical engineer....but college me jitana nahi samjha usase kahi jyada ap ne achha smjhaya hai....thank you very much sir🙏🙏🙏 for your efforts....

  • @muhammadkashif2356
    @muhammadkashif2356 Год назад +1

    bohat he Alaaa! Allah pak apko mazeed kameabi dy ameen

  • @NarayanVyasElectrical
    @NarayanVyasElectrical 2 года назад +2

    Very well explained. Clearly understood function of stabilising resistance. Thanks!

  • @सिर्फसत्य
    @सिर्फसत्य Год назад

    Bahut badhiya bhaai..mai b bahut pareshan tha..Books me thoda sa topic de rakha tha but ye to bahut bada aur important topic ha...

  • @karanshah471
    @karanshah471 2 года назад +4

    Very important for field engineers! Very well explained. One more point can be added like why in CT secondary current flows opposite concept of P1-P2 ~ S1-S2..so that if it gets reversed in wiring that fault can also be found.

    • @sitarampanda5040
      @sitarampanda5040 2 года назад +1

      reverse the polarity then will be a fault creat automatically

  • @harpreetsinghgrewal643
    @harpreetsinghgrewal643 3 года назад +8

    Great upload. You explained really well. Next topic: How to choose the CT ratio and C value (C100, C200 etc) so the CT doesn’t saturate during a fault?

  • @MuhammadIsmail-t7q
    @MuhammadIsmail-t7q Год назад

    Good Explanation and I understand it very well. Good way of teaching. Love from Pakistan.

  • @karansbhagat
    @karansbhagat 7 месяцев назад

    You are amazing tutor such a nicely explained. Thank you so much.

  • @Adarshvrm23
    @Adarshvrm23 3 года назад +1

    in such busy schedule sir you have attented my doubt after cmnt love u sirrrrrrr

  • @deepakghorpade8896
    @deepakghorpade8896 3 года назад

    Perfectly getting clear concept sir.....

  • @jotyrmoychakraborty2284
    @jotyrmoychakraborty2284 2 года назад +1

    Thank you so much. Your explanation is so much great.

  • @RohitKumar-kr3du
    @RohitKumar-kr3du Год назад +1

    Without any fault occurence, what is the direction of secondary current in the line CT

  • @ajitchauhan5753
    @ajitchauhan5753 3 года назад

    One of the best vedio Abhishek Ji.

  • @abhishekroy1846
    @abhishekroy1846 3 года назад +5

    1)Why nct is not getting saturated but phase CTs are getting saturated due to high fault current?
    2) What is the zone of protection of lvref and hvref in a 33/11kv substation?

  • @SatishYadav-pk5eh
    @SatishYadav-pk5eh 11 месяцев назад

    Dear sir , I'm a big fan of your teaching style ....

  • @theworldbysinu
    @theworldbysinu 3 года назад

    Full package for electrical.,. excellent sir

  • @avantikav13
    @avantikav13 2 года назад +1

    Very clera and sound as well as informative, Thanks . Please make a detailed video on transform oil testing and action incase of oil contain danger gas, furan test analysis and action.

  • @khankakar0121
    @khankakar0121 Год назад +2

    Thankx buht kuch sekha ap say sir

  • @souvikduttaroy2241
    @souvikduttaroy2241 3 месяца назад

    Best explanation ever ❤🎉

  • @MuhammedIrfanMuhammedRamzan
    @MuhammedIrfanMuhammedRamzan 2 месяца назад

    Well done, bro.
    I like your presentation very much.

  • @gaurav_14329
    @gaurav_14329 2 года назад

    kya gazab explain kiya hai🙌🙌🙌

  • @muhammadalimughal3488
    @muhammadalimughal3488 4 месяца назад

    Bilkul samajh agayi bohat shukria .

  • @aydanahir9360
    @aydanahir9360 Год назад

    Thank you Sir I understand all your explanation. Very nice video Sir

  • @NandlalSingh-l4z
    @NandlalSingh-l4z Год назад

    Sir aapki samjhane ka yahi tarika chahta tha ❤🙏

  • @ANILKUMAR-gu4yc
    @ANILKUMAR-gu4yc Год назад

    Gr8 sir 👍👍🙏, aaj clear ho gaya REF, differential protection ka bi video bunaya

  • @banajkumarsahu6676
    @banajkumarsahu6676 4 месяца назад

    Sir,You are explained very well

  • @sivatejakulukuri9612
    @sivatejakulukuri9612 Год назад

    Super sir excellent concept given very understandable thanks for making this video sir🙏

  • @Music_talents
    @Music_talents 2 года назад

    Awasome brother I learnt clearly from this video video is very helpfull thanks for your video

  • @viewjankari
    @viewjankari 3 года назад +2

    Jab resistriced zone ke andar fault hota hai, tab bhi current I2 lowest resistance path kyun nahi karta? Kya tab stabilizing resistance series mein nahi hota hai?

    • @rahamgul1702
      @rahamgul1702 3 года назад

      yes same question arised in my mind

  • @prasun_mandal97
    @prasun_mandal97 7 месяцев назад

    Explained very well sir. 😊

  • @maheshchinvagol7299
    @maheshchinvagol7299 Год назад

    Sir. I would like to know the ceiling fan rotates in anticlock wise direction. And blades are skewed in such a way that air comes downward. If it make direction clockwise blade will be made skewed opposite of anticlockwise . Is it work. Why you make direction only in anticlock why not clockwise. But tables fans were in clock wise. Please explain sir. I am awaiting

  • @wajahatsohail2435
    @wajahatsohail2435 Год назад

    Thanks for such an amazing explanation Sir

  • @सिर्फसत्य
    @सिर्फसत्य Год назад

    Mera ek question hai ki
    Books me likha ki differential relay ko jab transformer (delta star) k protection me lagate h to CT delta side star me aur star side delta me connect hota h..but actually Maine power transformer (delta star) me dekha h ki star side CT ko bhi star connected kar rakha h...aisa kyun karte h? Aur kon sahi h books ya practically.

  • @bhuwneshwarsahu2390
    @bhuwneshwarsahu2390 3 года назад

    Bahut achhe se samajh me aaya sir 🙏🙏

  • @Sailor1864
    @Sailor1864 Год назад

    Very Nice Explain And More Knowledgebal vedio Sir 👍👍

  • @sanandachhatria6465
    @sanandachhatria6465 2 года назад

    so simple teaching sir I could easily understand

  • @snnmurtay7925
    @snnmurtay7925 10 месяцев назад

    In normal working condition what is the current flow direction in current transformer

  • @AlishaKhan-ld2qt
    @AlishaKhan-ld2qt 2 года назад

    Bahut ache se samjhaya sir

  • @mohdmustafa82
    @mohdmustafa82 3 года назад

    Sir..
    Kya Restricted earth fault relay ko transformer ke delta connection ke liye use nhi kar sakte...

  • @pankajsinghbora880
    @pankajsinghbora880 3 года назад +1

    Sirji.....Earthing and neutral ka RYB k sath sequence kya hota h.... Transmission nd distribution line m

  • @prakhar5star
    @prakhar5star 6 месяцев назад

    Great explanation sir...thank you so much

  • @naushadmohammad2784
    @naushadmohammad2784 Год назад

    Iske jagah pe efr use kr sakte hain kya with 4 ct

  • @tradersadda3345
    @tradersadda3345 11 месяцев назад

    Sir ,in normal condition 3 phase ct seconary current also flow which can flow through the earth fault meater and trip the circuit

  • @ajaysharma-jv6ml
    @ajaysharma-jv6ml 3 года назад +1

    Sir need help sir ..
    My 14pin relay many time fault then I change but some time use but after some time then also fault

  • @sayantanpaul4766
    @sayantanpaul4766 2 года назад

    Precisely explained 👌👌

  • @TheMasterShow-TMS
    @TheMasterShow-TMS 8 месяцев назад

    Amazing Explanation 🎉

  • @electricaljagat7159
    @electricaljagat7159 3 года назад

    Mere solar plant me 5mva TRAFO ka REF tripping relay operate hota hai jab outside area (substation) me earth fault hota hai.. restricted area k bahar k faul pe operate nahi hona chahiye na... Stabilizing resister work nahi kar raha kya?
    Please suggest more....

  • @ElectricalEngineer106
    @ElectricalEngineer106 2 года назад

    Amazing video, your videos are very helpful in my internship ❤️❤️❤️

  • @shailshanshah
    @shailshanshah 3 года назад +1

    Sir you have explained beautifully. Thanks for sparing time & making such informative video . I have few queries, request to address them .
    1. Why this REF protection only use in transformer having capacity equivalent or more than 2.5 MVA?
    2. REF protection Relay will be installed in primary side of transformer or secondary side ?
    Once again thank you very much for this video . 🙏🙏

    • @sitarampanda5040
      @sitarampanda5040 2 года назад

      Ref is primary side also primery and secondary side

  • @deependrarolania5491
    @deependrarolania5491 11 дней назад

    Fpro 116 and solkar relays k liye kuch information btaye plz

  • @viveksingh3989
    @viveksingh3989 3 года назад +2

    Sir ji
    In case of high currents of external faults, only phase CT is getting saturated, not Neutral CT. Why so?
    And in case of internal earth faults, why neutral ct is not getting saturated, tgough the cirrent intensity lies similar to case of external faults...
    Please help sir ji

  • @abinashsahu2192
    @abinashsahu2192 3 месяца назад

    Very important information sir Thank you

  • @Abhishekpanwar001
    @Abhishekpanwar001 Год назад +1

    Sir please explain MC61A earth fault relay?

  • @anshraj7862
    @anshraj7862 2 года назад

    AMAZING....
    PLEASE MAKE VIDEO ON CT SATURATION........

  • @ashishahlawat6355
    @ashishahlawat6355 3 года назад +1

    Sir nhi aayi ,iska real lyf ka picture dikha dijiye or video bnao

  • @munafabdul3879
    @munafabdul3879 3 года назад +1

    Sir please explain the difference between motor protection and transformer protection

  • @pankajvaja1299
    @pankajvaja1299 2 года назад

    Very helpful for understanding sir

  • @rajeshjadhav00
    @rajeshjadhav00 3 года назад

    Very informative video ... 👌🙏

  • @praveenulloju9662
    @praveenulloju9662 2 года назад

    Really Explained very well
    Thankyou

  • @roopeshyadavendra9993
    @roopeshyadavendra9993 2 года назад

    Sir synchronising pe bi video dalo with drawing ki kaise konsi pt use hoti hai or kaise bus ka selection hotha hai

  • @Sneha_Status_4k
    @Sneha_Status_4k 3 года назад +1

    नमस्कार सर् आप बहुत अच्छा से समझाते हैं और समझ में भी आता है
    सर् एक request थी आप से ड्राइंग कैसे read किया जाता है ओ भी एक part by part सर् समझाए आप की बहुत कृपा होगी हम सब पर

  • @ZDGamer53
    @ZDGamer53 Год назад +1

    sir 51N or 50N pr video bna do please

  • @MrRaj-un3zy
    @MrRaj-un3zy 3 года назад

    Sir TB ke bareme kuchh bataye aur, iske jyese aur device kebareme bhi bataye...

  • @kedarpatwardhan6064
    @kedarpatwardhan6064 Месяц назад

    Restricted Earth Fault Protection scheme explained very well and in a very easy to understand manner , sir .. One request sir .. can you please make video on topics , [1] 400 KV Busbar differential Protection scheme and [2] 400 KV Line Distance protection relay scheme ? please do the needful sir .. Thanks & Regards ..

  • @parveenpatel2653
    @parveenpatel2653 11 месяцев назад

    Sir Metrosil ka kya use h

  • @kunaldeysarkar1362
    @kunaldeysarkar1362 2 года назад

    well explained sir 👍👍👍👍👍

  • @yog6801
    @yog6801 2 года назад +1

    Hi Abhishek Ji
    Plz make a video on Back Up Impedance protection of Alternator

    • @electricalwithabhishekjoshi
      @electricalwithabhishekjoshi  2 года назад +1

      Okay Yogendra..

    • @yog6801
      @yog6801 2 года назад

      @@electricalwithabhishekjoshi Thanks for your quick response Sir
      Your explanation is very impressive
      Please make a video on Alternator testing like
      PD Test
      Elcid test
      Tan delta test
      And on
      Complete protection of Alternator...

  • @jagdeepsingh-kf5qp
    @jagdeepsingh-kf5qp 8 месяцев назад

    Sir please yeh baat clear krna k CT k secondary me current direction opposite kyo hota hai kis law k according. Aur ye sarbhi secondary core me hota hai??

  • @faridkhan-mf5xg
    @faridkhan-mf5xg 3 года назад

    minimum kitna load ho phr hamy cT lagani hoge.kia hm single phase meter per CT laga sakty hai?sir plz guide kare

  • @amoljadhav8757
    @amoljadhav8757 4 месяца назад

    What is neutral CT ratio and phase CT ratio. Could you explain with actual fault current values, thanks

  • @gohiljaydev3131
    @gohiljaydev3131 Месяц назад

    Sir ye metrosil kya hota hai?? Kyu use hota hai

  • @nabanitakundu8506
    @nabanitakundu8506 3 года назад +1

    Sir beautifully explained. Could u pls tell us about high impedance and low impedance REF

  • @soccerinveins7259
    @soccerinveins7259 День назад

    Sir
    Ref setting in relay = 0.3 I/Ino what does this means?

  • @subhadipmandal53
    @subhadipmandal53 Год назад

    Such a good explanation ❤

  • @kanojiyagyan8798
    @kanojiyagyan8798 3 года назад

    What will be time delay to operate ref protection

  • @sureshkarunakaran8500
    @sureshkarunakaran8500 Год назад

    Excellent explanation sir.thank you

  • @GopalSarkar-di3ce
    @GopalSarkar-di3ce 3 года назад

    how calculate stabilizing resistance vallue?
    plz make a vedio about this matter.

  • @GhulamMurtaza-xg5hc
    @GhulamMurtaza-xg5hc 2 года назад +1

    Thanks sir from Pakistan

  • @anandbhoj4714
    @anandbhoj4714 Год назад

    Ye current ki direction CT ki secondary me opposite ku hoti hai.. primary ke direction ke comparison me

  • @vivekchoudhary5148
    @vivekchoudhary5148 2 года назад

    Winding agar delta me hui to?

  • @mkmkm4408
    @mkmkm4408 3 года назад

    Abhishekji, beautifully explained. Can you just add, what will be the scenario if the transformer winding is delta connected?How the CTs will be connected?

  • @ermohdrizwan423
    @ermohdrizwan423 Год назад

    Sir what is droop ct in ht alternator

  • @subhashelect
    @subhashelect 2 года назад

    Very Good Explain..very nicely ..I have one queation Line CT and Neutral CT SHOULD BE ONE POINT EARTH OR SEPERATE EARTH..

  • @sivakrishna-rq8rq
    @sivakrishna-rq8rq 3 года назад

    Good explanation, great bro

  • @lucarioind2203
    @lucarioind2203 2 года назад

    you earned a subscriber sir

  • @pratishpatil1218
    @pratishpatil1218 3 года назад

    Great knowledge sir really apriciate

  • @manubtek
    @manubtek 6 месяцев назад

    Well explained. Thank you

  • @simplifyLife604
    @simplifyLife604 10 месяцев назад

    Sir nice explanation. Dear sir i think stabilizing resistance will be in opposite side of the relay.

  • @abdulroufashraf4065
    @abdulroufashraf4065 2 года назад

    thanks dear , you have explained well

  • @madhuvanprajapati1722
    @madhuvanprajapati1722 2 года назад

    bias differential protection also give earth fault protection then why we need restricted earth fault protection ?

  • @RajeshRaj-rp5ht
    @RajeshRaj-rp5ht 2 года назад

    Wonderful explanation good knowledge

  • @vikrambhuva2526
    @vikrambhuva2526 Год назад

    Sir jub line ct saturate ho jata he tab current ct se hote huye resistance ke through relay me kyo nahi jata jab ki pehle case me neglect hote samay to vaha se flow ho rha tha ?

  • @abhinandanthute2362
    @abhinandanthute2362 3 года назад

    Thank you sir 😊 for answer my comment question thank you very much 👍🏿🙏

  • @subhashelect
    @subhashelect 2 года назад

    Very Good Explanation ..pls let us know the CT Sceondary Grounding will se sepearately line ct secondary and neutral CTSeconday seperate Grounding..

  • @afrozalam6390
    @afrozalam6390 3 года назад

    Sir tell about 67 relay in switchgear. When it is parallel condition.