Transformer IR Value Test || Hindi

Поделиться
HTML-код
  • Опубликовано: 4 дек 2024

Комментарии • 38

  • @justwelltariang2456
    @justwelltariang2456 Год назад +1

    Your explanation is simple and precise and very articulately defined. Keep it up. And thank you so much .

  • @zahidyahya7793
    @zahidyahya7793 2 месяца назад

    Too Good Explanation Sir

  • @shahbazrehman7211
    @shahbazrehman7211 Год назад

    Excellent explain❤

  • @gulabsinghgulabsingh8709
    @gulabsinghgulabsingh8709 8 месяцев назад

    Very nice video concept clear

  • @shahrukhkhan4190
    @shahrukhkhan4190 Год назад

    please continue & complete the all series
    And please make video in future design related videos

  • @azimkure9323
    @azimkure9323 Год назад

    SUPER SIR JI

  • @ashokmosun4204
    @ashokmosun4204 Год назад

    Good information 👍

  • @nandyroy1856
    @nandyroy1856 Год назад

    Sir... HV me teno phase ko short krna hai ya nahi? IR testing me.

  • @jayaramuduarekallu7864
    @jayaramuduarekallu7864 Год назад

    Very useful video

  • @surendrakverma555
    @surendrakverma555 Год назад

    Thanks Sir 👍

  • @HVELECTRICAL
    @HVELECTRICAL Год назад

    Please make a video on short circuit calculation and relay protection and time gradation.

  • @rkhanda
    @rkhanda Год назад

    Sir in Star star winding TF connections are any bush to earth or star point to earth

  • @dipeshlimbabhai6503
    @dipeshlimbabhai6503 Год назад

    Ten delta ct and transformer and pt ka vedio plese banao

  • @ShairAliDar
    @ShairAliDar 26 дней назад

    Sir, when you connect red lead to Hv side, so we have to connect just one phase only or do we short all three hv phases and then connect red lead?

    • @Insighttecs
      @Insighttecs  25 дней назад +1

      actully all three phase are connected each other internally, and we are applying DC voltage through insulation tester hense, not required to short. if you short all three phase than no problem..

  • @manojSwami-wi1wg
    @manojSwami-wi1wg 5 месяцев назад

    HV to E k liye , HV k RYB ph Bushing short karna hai kya

    • @Insighttecs
      @Insighttecs  5 месяцев назад +1

      technically it is not required, but for accurate result it is to be done.

  • @Aman-pg4ky
    @Aman-pg4ky Год назад

    Sir please explain What should be the minimum IR value for power transformers, motors, generators, breakers, CT

  • @ShairAliDar
    @ShairAliDar 26 дней назад

    Sir how do you decide at voltage transformer hv is to be tested. For example i have to test 1250kva, 11kv/433v transformer, how much testing voltage should i apply on LV side and hv side. My equipment can max generate 5kv testing voltage.

    • @Insighttecs
      @Insighttecs  25 дней назад +1

      for 433v, the insulation is design at 1100v, so it can be mesure at 1kv i.e 1000v,
      for HV side- at 11kv you can mesure at 5KV

  • @dasrajak9340
    @dasrajak9340 5 месяцев назад

    IR value minimum kitna hona chahiye for 11 kv transformer

  • @abengalitravellertm2034
    @abengalitravellertm2034 Год назад

    Sir Star point is grounded and I don't understand why star winding terminal and ground shown gohm of resistance?

  • @prashantverma45
    @prashantverma45 7 месяцев назад

    How did u calculate PI value ? Pls tell !

    • @ShairAliDar
      @ShairAliDar 26 дней назад

      IR value at 10 minute divided by IR value at 1 minute

  • @prabhatsingh5377
    @prabhatsingh5377 Год назад

    PI VALUE SHOULD BE HOW MUCH FOR VERY GOOD INSULATION ?

  • @dodiyasanjay7777
    @dodiyasanjay7777 Год назад

    Ten delta test transformer video

  • @rkhanda
    @rkhanda Год назад

    Sir in Delta star TF LV to earth connection star point to earth
    Or any LV bush to Earth
    Pl explain

  • @md.farhadhossain2378
    @md.farhadhossain2378 Год назад

    Please upload video with english subtitle

  • @pemasquare8845
    @pemasquare8845 Год назад

    Why are u testing with 5kv?what is the concept behind choosing 5kv for this?

  • @ArvindKumar-yn7hb
    @ArvindKumar-yn7hb Год назад

    Ir value kitna hona chahiye

  • @FredjAJ
    @FredjAJ 5 месяцев назад

    5kv for LV !!!

  • @HVELECTRICAL
    @HVELECTRICAL Год назад

    First veiwer

  • @safvan1996
    @safvan1996 4 месяца назад

    Sorry Sir... But u r wrong... When Star (LV) Side IR Value test time Nuetral Link open karna rahega to hi IR Value Test kar sakte hai otherwise Value 0 aayega....

    • @Insighttecs
      @Insighttecs  4 месяца назад

      of corce... you are right...
      in star windig you need to open the nuetral from earth...

  • @toseefmalek5541
    @toseefmalek5541 Год назад

    What is satisfaction value . To ensure equipment healthy .