How to connect to a relay to use PCM600 and find its information?

Поделиться
HTML-код
  • Опубликовано: 8 сен 2024
  • This instructional video will guide you through establishing a connection between protection relay and engineering tool PCM600, and finding out critical data. Check the content below for direct access.
    Content:
    0:07 Fundamental Relion® family protection relay engineering concepts
    0:26 Establish the physical connection
    0:47 Enable communications between the relay and the laptop
    1:25 Manually change the laptop's IP address to one that is on the same sub-network as the relay's IP address if you are using the rear port
    2:08 Set the technical key
    3:03 Find the relay's serial number
    4:28 Find the relay's information with the web HMI

Комментарии • 49

  • @ngophuchau5679
    @ngophuchau5679 29 дней назад

    Thank you so much!!!

  • @MichaelEdgarEscalante
    @MichaelEdgarEscalante 9 дней назад

    I am unable to access the WHMI even though it is already ON/activated and have correct IP address. Do you have detailed video tutorial for this?

  • @raeesnawaz5831
    @raeesnawaz5831 3 года назад +1

    nice information.thanks bro

  • @shijogeorge7915
    @shijogeorge7915 3 месяца назад

    REF 615 Communication is established but when I tried to read from the relay, it started reading but suddenly stopped and showed a cancelled message.
    NB:
    I'm accessing the relay using PCM 600 2.11

  • @ZirveAzeri
    @ZirveAzeri 6 месяцев назад

    Hi, can we connect to front port from remote network ? (not same subnet)

  • @suriyamoorthi4275
    @suriyamoorthi4275 3 года назад +1

    Good

  • @bharatlalmali8695
    @bharatlalmali8695 Год назад +1

    Hello sir, i am not able to use "work online" mode in PCM600. The "work online" tab is showing deactivate, please guide

    • @ABBlearning
      @ABBlearning  5 месяцев назад

      Hello @bharatlalmali8695. To online monitor the application configuration, the complete IED configuration must first be written to the IED.
      - Only when the application configuration in the IED and
      PCM600 are the same, the online monitoring starts.
      - When the IED does not support online monitoring, the button is disabled.
      - The Work online function is not supported if the split window is
      enabled.

  • @sandeskunwar6581
    @sandeskunwar6581 2 года назад

    I had connection with new ABB Relay RET670, there is green signal as shown(no any red cross), this means there is sound connection. But when I tried to read for the internal configuration of relay setting in order to check and modify as per our requirments, while using read option or write option, it cant read issuing . It issued
    :Configure IED first. with remarks Cancelled>
    is there any configuration still do be done, what exact configuration is it looking for.
    At some point it "common read/ write menu", it comment section while writing it issued error at application configuration point and then signal matrix error(just flash for very short time which i got by using camera video mode to get what exaclty happened.
    But I coudnt configure the source of exact problem.

    • @ABBlearning
      @ABBlearning  2 года назад

      Hi Sandes, thank you for your question. Please contact Hitachi ABB Power Grids' Customer Connect Center for support with RET670 IED.

  • @ILAYARAJAraja
    @ILAYARAJAraja 3 года назад

    Hi, In REF615 relay trigger continuously breaker on and breaker service signal in the disturbance record how can we stop continuously triggering, I need one trigger only at the time, kindly give the information,thanks..

    • @ABBlearning
      @ABBlearning  3 года назад

      ​ @Ilaya Raja it is difficult to answer without seeing the configuration. Please contact your local ABB channel, so they will contact factory customer help for support.

  • @paulinadukabain9701
    @paulinadukabain9701 3 года назад

    Hay ABB
    I have a problem with relay ABB RET 650..
    I used PCM 2.10 600 to connect with relay but the path is not of a legal form..
    I need problem solving from you.
    Thank you

    • @ABBlearning
      @ABBlearning  3 года назад

      Hi Paulina, thank you for your question. Please contact Hitachi ABB Power Grids’ Customer Connect Center for support with RET650 relay.

  • @christopherserojano3953
    @christopherserojano3953 3 года назад

    Hi ABB, can you please make a video on how to set the reclosing function (DARREC) of RER615. Also, in the phase and ground directional settings, is changing the curve types requires the change in the parameters (A, B & P)? For Schneider and SEL relays, the curve type does not require the change in parameters except for customized curves. We've done a SCIT, but the actual trip time does not match with the computed. Also, the reclosing function isn't working. Whom can we contact for our technical inquiries? Thank you.
    Christopher - Philippines

    • @ABBlearning
      @ABBlearning  3 года назад +1

      Hi Christopher,
      Thank you for your suggestion.
      Please check DARREC Technical notes available on the link abbtm.fi.abb.com/fi//attachments/TechnicalNotes/tech_DARREC_756960_ENc.pdf. If you need support, please, contact ABB Philippines Electrification unit (ph.electrification@abb.com) and they will address your request to the correct person.

    • @christopherserojano3953
      @christopherserojano3953 3 года назад

      @@ABBlearning Thank you for your reply, really appreciate it. Will communicate with ABB Philippines as we implement the technical guidance you gave. Thanks a lot.

  • @ILAYARAJAraja
    @ILAYARAJAraja 2 года назад

    Menu-control-CBXCBR, this section not getting access to close BREAKER, I need access to close from this section, what I want to do to,

    • @ABBlearning
      @ABBlearning  2 года назад

      Dear Ilaya,
      The primary equipment can be controlled via the LHMI with the Open and Close buttons when the protection relay is set to the local-control mode and accessing the
      control operations is authorized. In 615 series Operation Manual, there is more details about the operating procedures.
      Regards,
      ABB Learning

  • @mothanhattran2032
    @mothanhattran2032 4 года назад

    Hi guy, Could you tell me How did you do to setup PCM600? I don't find PCM600 driver. Thank you!

    • @tapanikoski6603
      @tapanikoski6603 3 года назад

      PCM600 is available from ABB Library. Create login prior to accessing. www143.abb.com/SoftwareLibrary/Library

    • @ABBlearning
      @ABBlearning  5 месяцев назад

      Hello @mothanhattran2032. PCM600 can be freely downloaded from here: new.abb.com/medium-voltage/digital-substations/software-products/protection-and-control-ied-manager-pcm600/pcm600-downloads

  • @ILAYARAJAraja
    @ILAYARAJAraja 3 года назад

    How to do manual syn enable in REF 615 relay

    • @ABBlearning
      @ABBlearning  3 года назад

      Hi Ilaya,
      Could you please clarify what kind of “syn” you are referring to, so then we can assist you better?

    • @ILAYARAJAraja
      @ILAYARAJAraja 3 года назад

      @@ABBlearning manually enable synchronize from the relay itself

    • @ABBlearning
      @ABBlearning  2 года назад +1

      @@ILAYARAJAraja,
      The synchronism and energizing check function SECRSYN checks the condition across the circuit breaker from separate power system parts and gives the permission to close the circuit breaker. SECRSYN includes the functionality of Synchro check and energizing check.
      In the command mode operation, an external command signal CL_COMMAND, besides the normal closing conditions, is needed for delivering the closing signal. In the command control mode operation, the Synchro check function itself closes the breaker via the SYNC_OK output when the conditions are fulfilled. In this case, the control function block delivers the command signal to close the Synchro check function for the releasing of a closing-signal pulse to the circuit breaker.
      In 615 series Technical Manual you can find detailed information about the SECRSYN function.
      Regards,
      ABB Learning

  • @rohitrhtx9
    @rohitrhtx9 3 года назад

    Where can i find REB670 technical key?

    • @ABBlearning
      @ABBlearning  3 года назад

      Hi Rohit, thank you for your question. Please contact Hitachi ABB Power Grids' Customer Connect Center for support with REB670 IED.

  • @mahdeyousif5399
    @mahdeyousif5399 3 года назад

    Hello dear
    Can help me about point list ref 615 modbus register address mapping.

    • @ABBlearning
      @ABBlearning  3 года назад

      Hi Sajad,
      Please check Relion 615 series Modbus Communication Protocol Manual, search.abb.com/library/Download.aspx?DocumentID=1MRS756468&LanguageCode=en&DocumentPartId=&Action=Launch.

  • @ranjithkumar-yn2um
    @ranjithkumar-yn2um Год назад +1

    wrongly said DHPC service instead of DHCP Dynamic Host Configuration Protocol

    • @ABBlearning
      @ABBlearning  5 месяцев назад

      Hello @ranjithkumar-yn2um. Noted.

  • @hassanpropro7262
    @hassanpropro7262 2 года назад

    Hi Abb Can I get Arabic subtitles for the video

  • @lebonsbons
    @lebonsbons 3 года назад +1

    Hi..How can I access the application configuration/signal configuration in REU611 through PCM600? I was made to understand that the signal configuration can be accessed in both web HMI and PCM600 as per video in link below:-
    ruclips.net/video/T1dxW8AS4Yg/видео.html
    However I couldn't find the options to get to the application configuration in the PCM600 for 611 IED series. Please help!

    • @ABBlearning
      @ABBlearning  2 года назад

      Hi Akay,
      Thanks for your question.
      Application Configuration tool in PCM600 is not available for 611 series relays. You can use Parameter Setting Tool (Generic logic settings) in PCM600 for signal configuration of 611 series. Like shown in the video, in web HMI there is an easy way for signal configuration in 611 series as well.
      Regards,
      ABB Learning

  • @H.M.D_support_ABB
    @H.M.D_support_ABB 2 года назад

    hii ABB ,
    I need help,Username and password Administrator WHMI REF611 ABB. Factory default password or shall we set it.
    Hominhduc- Vietnam's
    Thanks.

    • @ABBlearning
      @ABBlearning  5 месяцев назад

      Hello @H.M.D_support_ABB. WHMI Admin Password: remote0004

  • @hiloufalakhdar1065
    @hiloufalakhdar1065 3 года назад

    hi,REF542plus please

    • @M.Elvis_Jacinto
      @M.Elvis_Jacinto 3 года назад

      Hello, what do you need?

    • @simonesenomi
      @simonesenomi Год назад

      @@M.Elvis_Jacinto hi i need to estract fault record from an ABB REF543 via PCM600

    • @ABBlearning
      @ABBlearning  5 месяцев назад

      Hello @hiloufalakhdar1065. Plesae contact your local ABB service representative.

  • @nguyenvantung1987
    @nguyenvantung1987 3 года назад

    what is the password for web ADMINTRATOR in the browser ?

    • @M.Elvis_Jacinto
      @M.Elvis_Jacinto 3 года назад +1

      The user and password is: SuperUser

    • @nguyenvantung1987
      @nguyenvantung1987 3 года назад

      So in case the computer reports the wrong code order and cannot find it, why? Detail to view the below hyperlink , pls

    • @nguyenvantung1987
      @nguyenvantung1987 3 года назад

      ruclips.net/video/bLww_xg0xM0/видео.html

    • @M.Elvis_Jacinto
      @M.Elvis_Jacinto 3 года назад

      @@nguyenvantung1987 Your correct model is REF615C and not REF615, you need download and install the connectivity package REF615C.
      Look at drive.google.com/drive/folders/1QhfTuG1FYWrb0OLDNT0SctNMPk1sDnAi?usp=sharing

  • @hassanpropro7262
    @hassanpropro7262 2 года назад

    Hi abb Can I get Arabic subtitles for the video