Power Factor Correction Calculation in a Three Phase Circuit

Поделиться
HTML-код
  • Опубликовано: 6 окт 2024
  • This is a step-by-step solution to the question below:
    Two 3-phase motors are connected to a 208V 3-phase 60Hz source. Motor #1 has an FLA of 42A with a power factor of 0.82. Motor #2 has an output of 4kW with an 89% efficiency and a power factor of 0.79.
    What is the Line Current, and Apparent Power of the circuit?
    After correcting the circuit pf to 0.95, what is the Line Current, Apparent Power, and size of the required Delta connected capacitor bank?
    3-Phase Electrical Theory: • 3-Phase Electrical Theory
    #3Phase #PFC #Capacitor