How to by-pass Standard 1 compressor | Daikin VRV3 | ermergency setting.

Поделиться
HTML-код
  • Опубликовано: 26 авг 2024
  • Brand : Daikin VRV 3
    model : RXQ14PAY13
    Error : E6
    Cause : Standard 1 compressor jammed
    Action : By-pass standard 1 compressor for temporary use. (Ermergency setting)
    Ermergency setting for standard 1 compressor,
    1)press mode button more than 5 seconds (until H1P light up)
    2)press set button 19 times.
    3)press return button once.
    4)press set button once.
    5)press return button once.
    6)press mode button to exit.
    #bonmj #daikin #vrv

Комментарии • 59

  • @BonMj
    @BonMj  2 года назад +2

    Please like and share + Subscribe.
    Please leave your comments.
    Thanks🙏🙏

  • @amirhvaccenter5967
    @amirhvaccenter5967 Год назад +2

    Bon mj u didn’t tell about bypass standard compressor 2 and inverter compressor for single outdoor in this video.
    Please explain

  • @anilpradhan2263
    @anilpradhan2263 2 года назад +2

    Good Bon sir well-done

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @tabresztabu562
    @tabresztabu562 2 года назад +2

    Tq அண்ணா ✌️

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @phoekwar233
    @phoekwar233 3 месяца назад +1

    Thank you so much Sir

    • @BonMj
      @BonMj  3 месяца назад

      Most welcome

  • @aureliancioroiu8178
    @aureliancioroiu8178 Год назад +2

    Mr Bon.Thank you for all your guide.You are the best instructor.
    Would you help me please.I have the VRV Classic Inverter and in my case I have that issue: the H2P and H8P is blinking and H5P is ON.The compressor and fan does not working.
    Thermostat display indoor units shows Error button Menu of three of them and for other 2 units: Clean filter.
    Can I make the same steps as you showed in this video to bypass the Standard Compressor 1 or is different in my case?
    Is there a problem or mean some error?I thing the compressor does not have refrigerant,can also run the compressor and fan for this VRV Classic without refrigerant?.In the compressor 2 does exist refrigerant?Thank you!

    • @BonMj
      @BonMj  Год назад

      Hi.thanks watching my video.
      1)What is the outdoor unit model
      2)what is the error

    • @aureliancioroiu8178
      @aureliancioroiu8178 Год назад +1

      ​​@@BonMj Hi Mr Bon,the model for this VRV is: RXYCQ12A7Y1B DAIKIN EUROPE N.V.
      MFG DATE 2014.01
      DAIKIN VRV CLASSIC INVERTER.
      1) External single DAIKIN unit. When I start the VRV the master PCB model SEB11050(D) has: H2P and H8P blinking
      The H5P is ON.The other lights is off.The PCB does not have display.The PCB it looks like a VRV III.
      It is single external unit.Also the fan and compressor not working(is there a problem as long the gas is insufficient or not at all?the compressor and fan can work only if the PCB detect pressure and/or refrigerant?)
      2) Internal units
      On the Thermostat(remote controllers display i mean) from indoor units shows:
      ERROR BUTTON MENU
      I didn't press the Menu button because I didn't know.Now I know what I have to do to show the error in this display.
      Maybe the next 2 weeks can I tell you what error show in display from indoor units.Thank you!

  • @serviceacbekasi4733
    @serviceacbekasi4733 2 года назад +1

    God job ,ijin Belajar 😊

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @manjuviratuperavai3610
    @manjuviratuperavai3610 2 года назад +2

    Tq sir🙏

    • @BonMj
      @BonMj  2 года назад

      Thanks

  • @amirhvaccenter5967
    @amirhvaccenter5967 Год назад +2

    Please tell me vrv3 u4 alarm
    All whole building all units same

  • @karaors8970
    @karaors8970 2 года назад +1

    Good video bon 🧿🛠️🤳🇹🇷👍

    • @BonMj
      @BonMj  2 года назад

      Thanks bro

  • @dominicaliviado2
    @dominicaliviado2 Год назад +1

    How to by pass standard 2 compressor at set button press same 19 times or 20 times because I look for your video for standard 2 compressor by pass but none, Sir Bon Mj

  • @VinodKumar-ix7rt
    @VinodKumar-ix7rt Год назад +1

    Nice👍👍👍

  • @govindarasugovindarasu7440
    @govindarasugovindarasu7440 2 года назад +1

    Hi sir Daikin KRP928BBS Adaptor card how to install the change over panel please thanks

  • @shivaHVAC
    @shivaHVAC Год назад +1

    Sir how we know if the std 1 or 2 compressor is already bypassed?

    • @BonMj
      @BonMj  Год назад

      Check emergency settings

  • @brandonle4930
    @brandonle4930 2 года назад +1

    Good video Bon! If I have VRV4 master and slave 1, can I bypass CU slave 1 and have master CU run? Thanks

    • @BonMj
      @BonMj  2 года назад +1

      Can

    • @brandonle4930
      @brandonle4930 2 года назад +1

      @@BonMj thank you sir.

    • @BonMj
      @BonMj  2 года назад

      @@brandonle4930 welcome

  • @hidayaturrokhman3538
    @hidayaturrokhman3538 2 года назад +1

    Hy mr. Bon, I want to ask, how about multi outdoor emergency settings for the compressor?

    • @BonMj
      @BonMj  2 года назад

      Multi outdoor unit only can by pass the cu for vrv3(main,or slave 1 or 2)

    • @hidayaturrokhman3538
      @hidayaturrokhman3538 2 года назад +3

      @@BonMj that's right.. then if there is a problem with CU Slave 1, it means that vrv 3 multi outdoor unit can only by pass. which can be turned on CU main and slave 2. for CU slave 1 off (by pass) like that kah?

    • @BonMj
      @BonMj  2 года назад

      @@hidayaturrokhman3538 yes

    • @hidayaturrokhman3538
      @hidayaturrokhman3538 2 года назад +1

      @@BonMj thank you ..

    • @BonMj
      @BonMj  2 года назад

      @@hidayaturrokhman3538 welcome

  • @desmondteo6223
    @desmondteo6223 2 года назад +1

    Hi mr don ,how to contact u?

  • @kashibaba521
    @kashibaba521 Год назад +2

    Bon Sir If the standard Compressor 1 is Defective we press the Set button 19 times for the by-pass setting But sir if the standard Compressor 2 is Defective then how many times press the set button??

    • @kashibaba521
      @kashibaba521 Год назад +1

      In an other case if the Inverter compressor is Defective then What should we do?

    • @BonMj
      @BonMj  Год назад +1

      If both compressor down,mean the system cant work .

    • @BonMj
      @BonMj  Год назад +1

      This is single module?

    • @BonMj
      @BonMj  Год назад +1

      Later i check.
      Standard compressor 2 a bit different

    • @kashibaba521
      @kashibaba521 Год назад +1

      @@BonMj yes its Single module system

  • @wenjietea6212
    @wenjietea6212 2 года назад +1

    Hi bon
    After change new standard Compressor still high amp 9++
    What is the reason??

    • @BonMj
      @BonMj  2 года назад

      Check cu EEV

    • @wenjietea6212
      @wenjietea6212 2 года назад

      @@BonMj 👍

    • @amirhvaccenter5967
      @amirhvaccenter5967 Год назад +1

      Please tell me u4 alarm for vrv3
      All building all units

    • @BonMj
      @BonMj  Год назад

      @@amirhvaccenter5967 check communication wire, CU main pcb or indoor pcb

  • @mohammedrezaulkarim1702
    @mohammedrezaulkarim1702 17 дней назад +1

    Sir i need inverter comp
    Model JT1GCVDKYR@B
    once nos. In Bangladesh
    Chittagong
    Please...

    • @BonMj
      @BonMj  16 дней назад

      Sorry dun have

    • @mohammedrezaulkarim1702
      @mohammedrezaulkarim1702 9 дней назад

      @@BonMj
      Sir,Thank you
      For your suggestions.
      I change Compressor and fill gas with vacuum. Now VRV run smoothly. So many thanks again

  • @mohdmaqsoodshaikh5234
    @mohdmaqsoodshaikh5234 Год назад +1

    Sir Multy unit Daikin vrv3 18hp inverter compressor bay paas codes pls help

    • @BonMj
      @BonMj  Год назад

      Multo outdoor unit cant by pass compressor.
      Only can by pass the cu

  • @rahulramesh9735
    @rahulramesh9735 2 года назад +1

    Hi, master
    Daikin vrv 3 error L5
    what was the problem, boss

    • @BonMj
      @BonMj  2 года назад

      Check inverter pcb and inverter compressor

    • @BonMj
      @BonMj  2 года назад

      @@rahulramesh9735 you replace inverter pcb?
      Do you check compressor terminal?

  • @bvrajuchinni6340
    @bvrajuchinni6340 Год назад +1

    CU meaning

    • @BonMj
      @BonMj  Год назад

      Condensing unit