Lennox package unit low on refrigerant

Поделиться
HTML-код
  • Опубликовано: 29 ноя 2019
  • This video was filmed during the summer, however I just got around to editing and uploading it.
    I return to a unit we had to service twice over the summer. We added refrigerant both times and attempted to find the leak. I am going to do a thorough leak check to try and find this mystery leak- where in the world could it be.
    Please consider subscribing to my channel and follow me below
    Social Media
    Facebook profile.php?...
    Instagram / curioushvacguy
    For any inquiries please contact me at
    curioushvacguy@gmail.com

Комментарии • 107

  • @pralaypatel7110
    @pralaypatel7110 4 года назад +13

    I had the same type of a leak through the low pressure control and it was venting from the wires into the wire nut. We changed it out and I still have it in my van as a Trophy! I'm a believer!

    • @sknight0391
      @sknight0391 4 года назад

      🏆🏆🏆 #thatscool

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад +1

      I would love to catch one of those leaks

    • @xavierleandro188
      @xavierleandro188 2 года назад

      I dont mean to be so off topic but does anyone know of a tool to get back into an Instagram account..?
      I stupidly lost my account password. I would appreciate any help you can offer me.

    • @josephwalker484
      @josephwalker484 2 года назад

      @Xavier Leandro Instablaster :)

    • @xavierleandro188
      @xavierleandro188 2 года назад

      @Joseph Walker thanks so much for your reply. I found the site thru google and I'm in the hacking process atm.
      Seems to take a while so I will reply here later with my results.

  • @rookierefrigeration4357
    @rookierefrigeration4357 4 года назад +4

    Mystery leaks are the best. Lol. Good video

  • @TheLenaweeTrekker
    @TheLenaweeTrekker 3 года назад +1

    You mentioned an internally leaking pressure control, leaking from the wires. I have seen that. It really blew my mind. In fact my boss missed it when he was in "I'll show you" mode. Neither one of us would have believed it if we didn't see for our selves. That particular job confounded all of us.

  • @sknight0391
    @sknight0391 4 года назад +8

    If it leaks again, lift up the cond. fan motor & shine a really bright flashlight on that microchannel on the inside & look for faint oil stain spots. That crap will drive you crazy with super micro leaks. But the oil stains are the dead giveaway that the leaks do exist 👍

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад +2

      Good tip Shannon, its been awhile since I had a good super micro leak

  • @bryantylerservices
    @bryantylerservices 4 года назад +4

    The dreaded Lennox mystery....
    Defitinely a good video!
    I have had a few that i went ahead and replaced the Schrader valve stems and low pressure switch,being that i did get hit and miss,well that being said,on one particular one i did both high and low pressure switches and stems..being low cost items, and have yet to go back to recharge...but my gut lennox evap.coil ...?? ( hairline crack at header(s), as you mentioned , more than likely.
    Keep us posted..very interesting!
    There is only so much we can do as contractors/ technicians.,especially when its a small leak..Defitinely a leak somewhere..
    Appreciate your time and effort.as always! ( great tips and clip)
    These type can rack your brain though!!
    Bryan Tyler Refrigeration.

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад +2

      Thanks Joseph- it left me scratching my head since I was able to pull such nice tight vacuum as well- Just going to have to see what happens this coming summer

  • @JuanTodoli
    @JuanTodoli 4 года назад +2

    Two things.
    Nº1: I know your hate it, I hate it and sure the most of the techs in this room hate it but: Some shoot o dye? as a last resort.
    Nº2: I remember some of the high-techs here in his youtube channel filmed a couple of wires of a presure switch leaking... not sure if was Ulises Palacios, Eric Mele, Alex... didn't remember... but had a beautiful pair of wires leaking soooo good.
    Cheers from Europe Bill. Love your channel.

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад +1

      Thanks Juan- If I remeber correctly I did check the wires and switches and didnt get a hit but I would love to find a leaking pressure switch one day, just because there so rare. Im going to see if they call us back out this summer, if so I may need to add dye-- if so I will film a follow up

  • @josephmettes9147
    @josephmettes9147 4 года назад +1

    Was already hitting the like button as you were asking for it in the video 😂 Thanks for the video man, definitely some great tips in there!

  • @donnierobertson3088
    @donnierobertson3088 4 года назад

    Great job again like always

  • @goldhammer561
    @goldhammer561 4 года назад +1

    I agree on trying higher pressure, I had a York package unit with a micro channel coil .I did a leak check with nitrogen and 410a mixture at least 325 on pressure to find the leak on the bottom corner of condenser coil. Great video thanks for sharing.

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад

      Thanks for sharing Eric- I may have to do that, well see how it plays out this coming summer

  • @lewiemcneely9143
    @lewiemcneely9143 4 года назад +1

    You gave it your best shot. Sooner or later it'll really show up and you can nail it! A-PLUS!

  • @jackbrennan754
    @jackbrennan754 3 года назад +1

    Lots of good information like the videos

  • @Tc-gt5vm
    @Tc-gt5vm 4 года назад +3

    Ac service tech had a good tip on checking for leaks at schrader cores. He drilled a hole in a plastic valve cap and put bubbles on the valve cap. I have been using that tip since I watched his video. Thought to pass it forward.
    Peace

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад

      Ac service tech that is a great tip, Im going to use that myself- Thanks

  • @jimmysegovia2688
    @jimmysegovia2688 4 года назад +1

    Excellent! Love all your video's!.

  • @HVACRNorth
    @HVACRNorth 4 года назад +4

    Good video bud, i think you did all the right steps. If i was in this situation the following year that pressures were low, I would defiantly inject some dye. Sometimes with formicary corrosion it can really be hard to pinpoint on commercial units. p.s. thanks;)

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад

      Thanks for the feedback Joe- as a last resort I might have to add dye someday but Ill wait to see how this next summer goes

  • @chrisscerbo5731
    @chrisscerbo5731 4 года назад +1

    one of our priorities from the manufacturer a magic airhandler the capillary tubes are usually right against the blower motor housing and over time it made kinchs or small holes in the tubes. good for me able to find the leak right away but sucks for the resident tho. I hate these kinda leaks that are impossible to find. nice work

  • @analogmoz
    @analogmoz 4 года назад +3

    Someone is climbing up there and huffing the good stuff.

  • @LeoS41280
    @LeoS41280 4 года назад

    Instead of using bubbles on the ports use a drop of nylog. So if you need to put your gauges back on you won't chance getting moisture in the system.
    I'm really enjoying your videos.

  • @douchecanoe8811
    @douchecanoe8811 4 года назад +1

    Great vid with your procedures

  • @kangaroogod
    @kangaroogod 4 года назад +5

    Nothing more frustrating than having all of your tools there and doing the full evac and charging without being able to locate a leak

  • @JCM2LA
    @JCM2LA 4 года назад +1

    Eres el mejor!!! Gracias!!

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад

      Gracias Juan Y Gracias para ver mis videos y su comentario

  • @koastelkenn
    @koastelkenn 4 года назад +1

    awesome vid

  • @coolbreeze1774
    @coolbreeze1774 3 года назад

    Dont forget to pop the cover and check the compressor terminals bakelite for leaks. Some leaks will only show up with thermal expansion - UV dye additives sometimes help with finding that type, just be sure it is compatible with that type of oil in system.

  • @aliabrahimi3711
    @aliabrahimi3711 Месяц назад +1

    Probably another company stealing refrigerant from that unit

  • @jacobscyphers3630
    @jacobscyphers3630 4 года назад +2

    Here come the "why aren't you using a bluvac micron gauge" and "you can't pull a proper vacuum without 18" diameter hoses" guys. I hate these type of leaks. I've been known to jack the pressure up into the 400-500 psi range. If it blows.....it blows.

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад

      Hey Jacob- if I get another call this summer about that unit I may have to do something crazy like that, lol thanks for watching

  • @jonathanraul4086
    @jonathanraul4086 4 года назад +1

    Ty nice video

  • @scottmattson4765
    @scottmattson4765 3 года назад +1

    Did you change the filter Driers?

  • @engeclimarefrigeracao3644
    @engeclimarefrigeracao3644 4 года назад +1

    good video.Congratulations .'.

  • @MacStrong55
    @MacStrong55 4 года назад +1

    Nothing more frustrating than an inconclusive leak check in my books..

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад

      I still think about this one, I wonder if ill be called out again over the summer and find it low again-- hope not-- thanks for watching

  • @emmanuel.alcantara
    @emmanuel.alcantara 11 месяцев назад

    Did it leak again?

  • @chrisgormley5751
    @chrisgormley5751 4 года назад +2

    I hate those mystery leaks. Came across a few of them.

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад +1

      There almost as hard to solve as intermittent issues

    • @chrisgormley5751
      @chrisgormley5751 4 года назад +1

      @@curioushvacguy6876 those situations are the most frustrating ones.

  • @jeffgrant6914
    @jeffgrant6914 4 года назад +1

    Nor cal Dave is an awesome technical 😁

  • @Jamesoh777
    @Jamesoh777 11 месяцев назад

    The nitrogen is added on top of the freon. I' wondering how the nitrogen and the feron can be separated.

  • @cepedajavier4275
    @cepedajavier4275 4 года назад +1

    Try to spray soapy water over the microchanel coils and maybe you can see the leak 👍

  • @patrociolacic6088
    @patrociolacic6088 12 дней назад

    Ninety percent of the time the leak leaves an oil mark... the problem is that annoying 10% in which it will leave an oil stain after years of refilling and the machine makes us look useless and some once I thought I heard her laughing at me

  • @HVACRSurvival
    @HVACRSurvival 4 года назад +2

    How low were the system each time?

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад +2

      Hey Rick- If I remeber correctly, which I sometimes I dont, I think they where a pound ish low on the previous techs visits-- its in my notes attached to that customers account and since it was a few months ago that bit of info escapes me. I wonder if maybe my leak detector is or was having issues

  • @douro20
    @douro20 4 года назад +1

    My old GE H-10 will detect the tiny amount of gas which seeps out the valve of a halon fire extinguisher.

  • @atouchofa.d.d.5852
    @atouchofa.d.d.5852 4 года назад +1

    Maybe the core was leaking under pressure, but under vacuum it wasn't? Just that little bit of movement?

  • @joea2274
    @joea2274 4 года назад +2

    Leave your gage on over night and check it in the morning

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад +1

      Good tip Joe- Ill have to try that if they call us back in the summer

  • @jimbola77
    @jimbola77 4 года назад +1

    thank's partner for sharing! how do you like that sniffer?.

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад +1

      Hey Jimbola- Im satisfied with it so far, there have been two or three other occasions where I suspected a leak but it never went off-- which could be because there isnt really a leak, I know some customers who have preventative maintenance done and want there refrigerant levels checked everytime

  • @megacisco69
    @megacisco69 2 года назад +1

    Those are rookie words. ‘’ leaking cores’’

  • @jonnymac31
    @jonnymac31 4 года назад +1

    I got instant gratification.

  • @hvacslayer2929
    @hvacslayer2929 4 года назад +1

    300 microns and no decay psh . If there is a leak you’re micron gauge isn’t calibrated no way you would achieve that on a leak. Idk how touchy that cps is but I always have the microns creep a little then settle on the bluvac gauges yours was just instant 0 rise.

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад

      I agree- maybe theres a refrigerant huffer in the area or they have a maintenance guy who likes attaching gauges everytime he visits

  • @Sctronic209
    @Sctronic209 4 года назад +1

    You may want to try ultrasonic leak detection.

  • @douro20
    @douro20 4 года назад +1

    Is that an FTIR leak detector?
    Didn't know Sensata made pressure switches.

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад

      I believe it is- whats your go to leak detector? Ive been looking to upgrade

    • @douro20
      @douro20 4 года назад

      @@curioushvacguy6876 I'm no tech personally, just interested in the technology.

    • @sprockkets
      @sprockkets 4 года назад

      ​@@curioushvacguy6876 This person likes ultrasonic.No effect with wind. Also would work if you need to detect something like CO2. ruclips.net/video/3qgyqejXZIk/видео.html Using a smaller SRL8 or the Testo 316-3 works, and if they fail, the old and true H10, or the H10PM battery model.

  • @steveblake8766
    @steveblake8766 4 года назад +1

    #42 thumbs up

  • @actechformallyyomama746
    @actechformallyyomama746 4 года назад

    So I had a York package unit. One circuit flat the other low on charge. Using an ultrasonic leak detector I found both leaks in less than 5 minutes. We had a safety meeting yesterday. One tech was having problems with pneumatic tubes leaking. Rats had eaten the tubes. I told him to use the ultrasonic. Everyone gave me sht about having one and some had never heard of it. Well this morning a tech was on a 260 ton chiller. He could not find the leak. He called me and asked me about my ultrasonic. I told him he could borrow it. We met at lunch and he got it. He just called me and said he had found a leak within 5 minutes and was searching for more. He’s going to order one today. The chiller is 134A my unit was 22. The ultrasonic leak detector does not care what refrigerant you are working on. If their is a leak it will find it. I have sniffers but I couldn’t tell you when they last had batteries in them. Best $500 dollars I ever spent.

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад

      Hey ACTech- what brand of ultrasonic do you have?

    • @actechformallyyomama746
      @actechformallyyomama746 4 года назад +1

      Amprobe.

    • @actechformallyyomama746
      @actechformallyyomama746 4 года назад

      Hey curious something I forgot to mention. On tube and fin coils the manufactures are rifling the tubes. They remove material for this process. It used to be if you had a leak it would be at the welded U bends. Now the potential is everywhere. I’ve found leaks other techs couldn’t find with sniffers. They were in the middle of the coil. You should try an ultrasonic. Anyway stay safe.

  • @IRONDICKMECHANICALHVACdavis
    @IRONDICKMECHANICALHVACdavis 3 года назад

    Wrong place to install micron gauge. Install on the system.

  • @gene-khvacr
    @gene-khvacr 4 года назад +1

    Why not dye n bye that way if its does leak again that'll be Easier to pinpoint thoughts!

    • @actechformallyyomama746
      @actechformallyyomama746 4 года назад +1

      GeneK Hvacr die is a contaminant. Oil and refrigerant are the only things that should go into a circuit.

    • @curioushvacguy6876
      @curioushvacguy6876  4 года назад

      I would consider it as a last resort but before that I would repeat everything I did there, maybe up the pressures a bit and isolate each component of the system

  • @IRONDICKMECHANICALHVACdavis
    @IRONDICKMECHANICALHVACdavis 3 года назад

    Remove the top off the unit.

  • @rigakit
    @rigakit 4 года назад +1

    Sucks nothing significant,

  • @xavierramirezz2231
    @xavierramirezz2231 4 года назад +1

    Hi

  • @knockitofff
    @knockitofff 3 года назад

    you never said which circuit the leak was in and it looks like you're treating it all as 1 circuit, what gives?