Aap ek banaye jisme pure plant ka information ho jaise kitne tr ka water chillar hai cooling tower kis capacity ka hai kitne hp ki motor Lage hai kittne pump hai matlab ek plant room ka full informatic video banaye. Sukriya....
dost hamne aor bhi vidio upload kiya hua hai jisme plant details hai .. description me link hai aap dekh sakte hai...baaki kuch doubt ho to aap pooch sakte hai Sukriya 👍
Ji agar apke cooling towers ka COC 3.5 to 5 ke beech me hai to apko 200 ml ya 300 ml tak chemical add karna rahta hai .. around 40000 liter se 80000 liter water me .... Aor agar apke cooling tower ka COC 5 se ooper ja raha hai to apko chemcal ki capecity badhani hogi ... Aor uske sath sath apko 👉cooling tower ka water bhi kuch drain karna padega ....
Ji agar apke cooling tower ka COC level 5 ke andur hai... to apko chcemical 200 ml add hoga ... Aor agar 5 ke ooper coc hai to chcemical ki dosing jyada hogi
Agar apka tds ppm aor ph level under coc rahega yani ki sab kuch theek rahega to weekly ya phir har teesre din ..aor agar tds,ppm,ph jyada rahega to daily padega ...sukriya ji apka 💐
Depend on water parameters..if parameters high mean PH and hardness and TDS so chemical amount will be increase and if parameters in average so .. 200 ML chemical dosing in cooling towers
Only drain water .. Tds agar badh raha hai to apko 👉condenser line se water drain karna padega ... Uske liye koi chemical nahi hai ... .👉. COC ke hisab se apko water parameters maintain karke rakhna padta hai ।।। COC Ki vidio main upload ki hui hai aap link pe dekh sakte hai apko aor achee se samjh aa jayega ...👍 Sukriya
Ji hamne already ph,ppm,tds,tools par vidio upload kiya hua hai ..aap channel pe jaake dekh sakte hai .. aor bhi agar kisi cheej ki jaankri chahiye to ham jarur apke liye vidio upload kar denge ...💐💐🙏🙏
dost ...ye condenser ki capecity pe depend karta hai ....uske GPM ko nikalalne ke baad ....aor phir hight pipe length.....👉 aor agar only apko .. cooling tower ke tank ka water capecity nikalna hai ..to pahle us cooling tower ke tank ki depth and width nikalo phir aap direct liter nikal sakte hai aap .......👍
Sir, let's say l have checked ph, ppm and tds, found these are not as per standard requirements. Please make a video on dosage calculation with examples for a better understanding.
Ji iska bhi ...PH TDS PPM ( haardness) hota hai ..but ye parameter hamesha under maintain rahta hai qki ye chilled line ka watar poori tarh se pack rahta hai ...kahi se bhi dhool mitti jaane ka chance nahi rahta hai.......isme bus 2 cheej badhti hai wo bhi 1 ya 2 saal me ..chloride and nitryt ..ye parameter valve ke jung ke lagne ki vajah se badhte hai ..jo jung lagta hai wo paani me mil jaata hai ...iske liye ham 1 saal me 25 ltr corrosion inhibitor chemical daal dete hai chilled line me ....sukriya
केमिकल कितनी कितनी मात्रा में डालना है कूलिंग टावर में वह अपने बताया नहीं वह आप बताओगे तो काम थोड़ा आसान हो जाएगा इस पर आपने वीडियो डाली है नहीं डाली है तो डाल दो तो बड़ी मेहरबानी हागी सर
depend on your coc level ...mean agar apke cooling tower ka parameter yaani ph .tds .and hardness sahi level pe hai to 300 ml 300 ml add hota hai .aor agar water parameter high ja raha hai to quantity badha di jaati hai .. chemical name👉 ..anti scaler , corrosion inhibitor,and alkaline reducer
aor kahi kahi par dosing pump lage hote hai wo auto pe work karte hai ..jitne chemical ki required hoti pump usi ke according dosing karta rahta hai ..
sr bahot acha guide keya ap ne....excellent
Ji sukriya apka 👍
RUclips pr Aapke ke jeysa Samjhane wala koi nahi hai
Thank you sir for your information 🙏
Very nice
Aap ek banaye jisme pure plant ka information ho jaise kitne tr ka water chillar hai cooling tower kis capacity ka hai kitne hp ki motor Lage hai kittne pump hai matlab ek plant room ka full informatic video banaye.
Sukriya....
Thankx for giving information 👍
thank you 🤗
Really u r a great experience holder for HVAC sector
bahoot sukriya ...lekin aap bhi kisi se kam nahi hai..🙏👌
بہت شکریہ
Video me ghus gaya tha Achhha laga sir thanks
Knowledge ke liye kahi bhi ghus jao yaar 🤗👍
👍👍👍 very good
Thank you for information
💐💐 sukriya ji
Really mast video 👍👍
بہت ہیلپ فل رہی ویڈیو
شکریہ جی آپکو
You are best sir 💯💯🇵🇰🇵🇰🇵🇰
thank you 👍
Good instarecation
👍😊
Kisi or ka video 100 bar dekhne se behtar hai apka video 1 bar dekh le, thanks sir
thanks for supporting and loving ✊💐
Nice bro 👌
thank you dost 👍
Good 👍
Great
Superb sir
Thank you ji 💐
Sir 😊
Tell some of chemicals which use to clean/service condenser or evaporator.
(AHU/FCU)
Sir condenser pump k Sath 1 bara tank laga hota Hai wo q hota Hai please answer sir
Sir Maine chemical iti ki hai (acop) ki video banana sir please please sir please sir
How we take water sample and feed chemical in cooling tower ? Please ak video banaye
ok ji will make early your vidio .. thanks for response 🙏
Tino chamical kitna dalna chahiye
Sir 30 tr water chillar k barre me video bnaiye compressor and condensor k bare me btaiye utility system operate krta hu sir
Very good ... But apko kya janna hai apne chiller me aap बताएंगे कोई topic
Sir, tell us a little more about the chemical of the cooling tower.
daily usage chemical
1.👉 anti scaler
2.👉 corrosion inhibitor
3.👉 alkaline reducer
Phosphoric acid anti scaler
Cold storege cpcity ke anusar kitne tone ka compressor use Kiya jata batao
Kaha use karna hai apko ... Ye batay aap ??
kya cond.me ..bacteria marane wala chemiacal use karate hai agar karate hai to konsa
Condenser me 3 chemical use hote hai water ko soft karne ke liye
1. Alkaline reducer
2. Anti scaler
3. Corrosion inhibitor
Sir Aap Please Plant me jo jo use hua h Os ka name ka video bnao na
dost hamne aor bhi vidio upload kiya hua hai jisme plant details hai .. description me link hai aap dekh sakte hai...baaki kuch doubt ho to aap pooch sakte hai Sukriya 👍
Sir hmko chiller plant ki control aur power wairing ki video bataeeye kaise kaise eska canection hoga plz sir batao
Chiller ka connection ka vidio banaya hai hamne...aap channel pe vidio dekh lijiye
automatic tube cleaning system please explained sir (my name chandan)🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏
Three chemical aap n bataya inki kitni quantity kitine me Milana hai jo sahi ho water quantity and chemical quantity
Ji agar apke cooling towers ka COC 3.5 to 5 ke beech me hai to apko 200 ml ya 300 ml tak chemical add karna rahta hai .. around 40000 liter se 80000 liter water me ....
Aor agar apke cooling tower ka COC 5 se ooper ja raha hai to apko chemcal ki capecity badhani hogi ... Aor uske sath sath apko 👉cooling tower ka water bhi kuch drain karna padega ....
Ye mera instagram id hai agar apko koi questions karna hai to aap yaha kar sakte hai .... Id 👉kgufran195
automatic tube cleaning system please explained sir please
Water parameters kitna hoga to kitna chemical dosing karne padega uska ek list dijie pls... 😢
Apke system pe COC setup Kitna rakha gaya hai ?
4 hai
Corrosition inhibitor chiller line me kaise aur kaha se dalte hai
Sabse top floor ke ahu ke pass ek line di jaati hai ..jaha se ham fill karte hai
Daily konsa pramitor chak karnaka kitna hona chahehe
3 water parameters daily 👇
1. TDS (conductivity)
2. PPM (hardness)
3. pH value
Sir can u explain how much quantity of Chemical add in cooling or daily ya weekly
Ji agar apke cooling tower ka COC level 5 ke andur hai... to apko chcemical 200 ml add hoga ... Aor agar 5 ke ooper coc hai to chcemical ki dosing jyada hogi
Kon si site hai
🙏🙏🙏🙏
Sir ji head pressure kya hota
Gas ke discharge pressure ko head pressure bolte hai
Cooling tower ke andar dalte hai chemical daily dalte hai ya weekly bateyege
Agar apka tds ppm aor ph level under coc rahega yani ki sab kuch theek rahega to weekly ya phir har teesre din ..aor agar tds,ppm,ph jyada rahega to daily padega ...sukriya ji apka 💐
What is the amount of chemical do we have to add?
Depend on water parameters..if parameters high mean PH and hardness and TDS so chemical amount will be increase and if parameters in average so ..
200 ML chemical dosing in cooling towers
TDS level ko kaise menten rakhege??
Only drain water ..
Tds agar badh raha hai to apko 👉condenser line se water drain karna padega ... Uske liye koi chemical nahi hai ... .👉. COC ke hisab se apko water parameters maintain karke rakhna padta hai ।।।
COC Ki vidio main upload ki hui hai aap link pe dekh sakte hai apko aor achee se samjh aa jayega ...👍 Sukriya
Sir, could you please explain how to check ph, ppm and tds ..??
Which tools we use to check these..??
Ji hamne already ph,ppm,tds,tools par vidio upload kiya hua hai ..aap channel pe jaake dekh sakte hai .. aor bhi agar kisi cheej ki jaankri chahiye to ham jarur apke liye vidio upload kar denge ...💐💐🙏🙏
Ji hamne link add kar diya hai aap dekh sakte hai ...sukriya apka💐💐
@@c4chiller9984 thank you sir, informative video 💯
Sir par day kitna liter chemical dalna hai cooling tower me
wo depend karta hai ki apke cooling tower water ka parameters kya chal raha hai .. but ye daalte hai ham
. 200ml per cooling tower
Great explain
sukriya jiii
Cooling tower me water ki capacity kitna hota hai Sir
dost ...ye condenser ki capecity pe depend karta hai ....uske GPM ko nikalalne ke baad ....aor phir hight pipe length.....👉 aor agar only apko .. cooling tower ke tank ka water capecity nikalna hai ..to pahle us cooling tower ke tank ki depth and width nikalo phir aap direct liter nikal sakte hai aap .......👍
Sir yeh chemical liquid mei hota hai ya powder mei
ji liquid me
Sir,how much chemical quantity using in daily for dosing??
Depend on cooling tower water parameters..
But standard quantity is . 200 ml per cooling tower
@@c4chiller9984 tnx sir, I have above 7 years experience in hvac and mep filled if you have any opening plz let me know
Ji jarur
Sir, let's say l have checked ph, ppm and tds, found these are not as per standard requirements. Please make a video on dosage calculation with examples for a better understanding.
What pamameter your shoft water ???
@@c4chiller9984 water ki hardness 80ppm hay aur tds 1800 hay.
80 ppm aor tds 1800
Ye apke shoft water ka parameter hai ???
chillar water line Kitna kamical ade karnaka
only use 👉corrosion inhibitor chemical for chilled line
Sir 404 or 129 camical kary
sir chilled water ke kya std parameter hote hai?
Std mean ???
@@c4chiller9984 i mean standard Parameter of Chiller Water line water.
Ji iska bhi ...PH TDS PPM ( haardness) hota hai ..but ye parameter hamesha under maintain rahta hai qki ye chilled line ka watar poori tarh se pack rahta hai ...kahi se bhi dhool mitti jaane ka chance nahi rahta hai.......isme bus 2 cheej badhti hai wo bhi 1 ya 2 saal me ..chloride and nitryt ..ye parameter valve ke jung ke lagne ki vajah se badhte hai ..jo jung lagta hai wo paani me mil jaata hai ...iske liye ham 1 saal me 25 ltr corrosion inhibitor chemical daal dete hai chilled line me ....sukriya
केमिकल कितनी कितनी मात्रा में डालना है कूलिंग टावर में वह अपने बताया नहीं वह आप बताओगे तो काम थोड़ा आसान हो जाएगा इस पर आपने वीडियो डाली है नहीं डाली है तो डाल दो तो बड़ी मेहरबानी हागी सर
ok ji jaise hi time milta hai mai practical me ye vidio upload kar doonga . thank you 👍
Please
Pani ka kitna TDS hona chahie 😉
1200 to 1500 tds
but depend karta hai ki aapke shoftwater ka TDS kitna hai ...jis water se aap cooling tower tank full karte ho
Hi
Sir how much chemical add in water
depend on your coc level ...mean agar apke cooling tower ka parameter yaani ph .tds .and hardness sahi level pe hai to 300 ml 300 ml add hota hai .aor agar water parameter high ja raha hai to quantity badha di jaati hai .. chemical name👉 ..anti scaler , corrosion inhibitor,and alkaline reducer
aor kahi kahi par dosing pump lage hote hai wo auto pe work karte hai ..jitne chemical ki required hoti pump usi ke according dosing karta rahta hai ..
Chemical daily nhi pdta hai
Dost as a required daily bhi padta hai ,👍
How can calculate
depend on your COC level to cooling tower
how to calculate coc in cooling tower ۔۔۔aaj hi hamne ispe vidio apload ki hai ۔۔۔aap dekh sakte hai ۔۔۔۔sukriya apka 🙏💐
Sir india me HVAC assistant job me help chahiye
Location
@@Cartu786 any location chalega
It's urgent
Ji bataiye aap
Kya questions hai apka
Want a job in outside India in HVAC 3 years of experience..plz suggest
Ye mera instagram id hai aap yaha pe aaiye 👉 kgufran195
Contact krna bhai
Sir ap apana mob. No. Bataye
Ji ye instagram id hai apko koi bhi questions ho aap pooch sakte hai..👉 kgufran195