Looking at Profibus connectors and correct cable preparation.

Поделиться
HTML-код
  • Опубликовано: 27 окт 2024

Комментарии • 8

  • @yasserali7355
    @yasserali7355 4 года назад

    thanks sir ,
    we appreciate your efforts

  • @Luzt.
    @Luzt. 6 лет назад +1

    Excellent learning help. Thank you.

  • @hugonogueira8705
    @hugonogueira8705 2 года назад

    What about not to connect the Shield on one side, i.e. the (last) slave side?
    If we connect both shields on both sides, the electromagnetic field will interfer. Doesn't it need to be connected to only one side for the shield to be efective?
    Great video!

    • @andymorse3963
      @andymorse3963 Год назад

      Actually no, sorry didn't get a notification of your comment, it's important in profibus networks to be continuous throughout the network all screens to be connected. Drop me your email and I'll send you some information

    • @commenter5469
      @commenter5469 Год назад

      Shielding continuous all throughout, and terminators switched on at the ends ( off in the middle).

  • @commenter5469
    @commenter5469 Год назад

    Recently had a machine with alarm acknowledgment delaying about 30-40 seconds. Couldn’t find anything, the profibus terminations looked good. But I decided to cut it back and re connect anyway - it’s been two weeks since then, customer says it’s back to normal.