Load shedding solution in Grid tied solar system using Automatic transfer switch | PV switching
HTML-код
- Опубликовано: 13 янв 2024
- Load shedding solution in Grid tied solar system using Automatic transfer switch | PV switching
Load shedding in Pakistan is a big problem specially in summer season due to electricity short fall. So in this video I present a cheap solution for this particular problem having in any on grid solar system because system is shut down during load shedding hours solar panels gone useless.
I used TOMZN Three Phase 4 pole Din Rail ATS 220V Dual Power Automatic Transfer Electrical selector Switch for change over the PV power between two strings of solar panels and between a on grid solar inverter and off grid solar inverter.
On grid and hybrid solar systems are connected to the electrical grid and can provide a potential solution to mitigate the impact of load shedding. Load shedding typically occurs when there is a shortage of electricity supply, and the demand exceeds the available capacity. Here are some another ways in which on grid solar systems can help address the issue of load shedding:
Grid-Tied Solar Systems with Net Metering:
Install a grid tied solar power system with net metering capabilities. Net metering allows excess energy generated by the solar panels to be fed back into the grid, and the consumer receives credits for this surplus electricity.
During times when the grid is experiencing load shedding, the solar system can't generate electricity and can not provide power to critical loads in the premises. therefore another solution is Hybrid solar systems.
Backup Power Systems:
Integrate an energy storage system (such as batteries) with the on-grid solar system to store excess energy generated during periods of high solar production.
In the event of a power outage or load shedding, the stored energy can be used to power essential appliances and maintain critical operations.
Hybrid Systems:
Consider installing a hybrid solar system that combines solar panels, energy storage, and a backup generator. This system can provide continuous power during grid outages or load shedding.
The solar panels contribute to power generation during normal conditions, and excess energy is stored in batteries for later use.
*Contact us For Booking/Event Invitations/Sponsors your Products/Business Inquiries**
WhatsApp Only : +92 311 674 5016
email : ajelectric.wah@gmail.com
My other useful videos links :
Switching solution of load shedding in grid tied solar system | PV Switching Mechanism
• Switching solution of ...
10 KW Grid tied solar system best quality installation | Net metering | Bahria Town
• 10 KW Grid tied solar ...
5KW Solar system complete installation guide with Longi solar panels and Solarmax inverter
• 5KW Solar system compl...
3.2 KW Solar system complete installation guide | Aerox 3.2 KW inverter | system cost • 3.2 KW Solar system co...
Solar system frauds and scams in Pakistan | 5KW solar system improvement | Axpert 5.2KW
• Solar system frauds an...
5 KW Solar system complete information in Urdu/Hindi | Tesla solar inverter • 5 KW Solar system comp...
3.2 KW solar system complete calculations ¦ Solar panels ¦ Solar inverter ¦batteries requirement • 3.2 KW solar system co...
Best solar panels brands in Pakistan | Canadian solar panels review | how to buy solar panels https:/ • Best solar panels bran...
300 Watts Solar system complete installation guide | Solar system cost | Battery | Inverter • 300 Watts Solar system...
How to install Solar Panels on fitting stand | Complete installation guide • How to install Solar P...
Inverex 180 Watts Mono PERC Solar Panel review | Best Solar Panel 2020 in Pakistan • Inverex 180 Watts Mono...
For more Interesting Technical Videos Please Subscribe This Channel :)
Subscription Link: ruclips.net/channel/UC6C2...
Also here you will find a variety of videos about Engineering and Technology Including Tech reviews, unboxing, specially electric and electronic circuit’s tutorials in Urdu / Hindi.
My motive behind to create this channel to spread the knowledge about advance and easy technologies around the world.
And I want each and every individual whoever is interested in technology to be able to understand it in the easiest possible way. It’s all here on AJ Electric. #ajelectric
Make sure to subscribe my channel and press that bell icon for latest notifications so never miss any video.
Thanks for your Support and Visiting :)
Facebook : / aj-electric-1083315874...
WhatsApp : 923116745016 Наука
بہت مہربانی اللہ پاک اپ کو ہمیشہ خوش رکھے اپ کی وجہ سے ہمیں بہت کچھ سیکھنے کو ملتا ہے
ماشاءاللہ کوئی بھی چیز دوسروں کو بانٹنے سے الللہ تعالیٰ اس میں برکت عطا فرماتا ہے چاہے عزت دولت یا علم ہو الللہ تعالیٰ آپ کے صدقہ جاریہ کو قبول فرمائے آمین آپ کو ہمیشہ خوش اور تندرست صحت مند زندگی عطا فرمائے آمین
Ap ka explain krnay ka tareeqa boht behtreen aur kamal ka. Boht shukria
Sir ap ke solar systems ke bare me informative videos share krne se buhut kuch sekne ko Mila thanks sir g
Exactly 💯 main bhe Kuch dino say yahe soch rha tha k esa koi too option ho ga aor main yahe question Amir Bhai say krny wala tha k on grid agr load shading ho jati h koi too solution ho ga he ya koi solution bna k updated krein so ye soch chal he rhe thii too solution samney aa geia that's why I love this channel and Amir Bhai you are very professional.
ماشاءاللہ بھائی جان اللہ آپ کو صحت والی لمبی عمر عطا فرمائے اور آپ کے رزق میں برکت عطا فرمائے آمین جزاک اللہ خیر
❤
ماشاءاللہ بہت خوب جناب عمدہ ۔۔
جزاک اللّٰہ خیر کثیر
اسلام وعلیکم ۔ عامر بھائی بہت انفورمیٹیو ویڈیو ہے۔ اللّٰہ جزائے خیر عطا فرمائے آمین ثمہ آمین ۔
Sir I was literally searching for a solution and your video just came what a brilliant solution
Bhai Ji Salam hai aap ko zabatdast hal nikala hai aap ne Ma sha Allah
This is the reason you have got 1 million subs. Great content.
Pagal bna rha logo ko AC ats DC mein use krke it’s very risky and dangerous
Aoa dear. I have never seen a person like you who share his knowledge without any pride and money. Inshallah Allah ap ko iska bahut bara ajar dega jonap ki soch se b bahar hoga. Allah ap ko dunya o akhirat ki kamyabyan atta karey.
Shuja Ur Rehman
Mech Engr from PIEAS.
بہت خوب معلومات ہیں۔ الحمدللہ ہم نے ایسا سرکٹ پہلی بار 2018 میں انسٹال کیا تھا۔
Is it safe to supply full fledge DC voltage to Inverter suddenly?
MashAllah amir bhai bohat khoob mene to aap apna Ustad mana Hua ha Allah aap ko sehat aor ajar aata farmaen
Very useful information about solar system. You have explained each and everything very clearly. Thanks for sharing your knowledge....
Very professional and talented guy...
Great idia sir very thankfull to Allah for such true heart people around amongs them❤❤❤❤
Very informative, I really appreciate your efforts, Dr Sadruddin Baloch
My favorite aj electric RUclips channel.
Bhai zabardast zabardast bht hi achi information di bhai yeh Main tamam logon ko kahun gaa yeh lazmi video daikhain solar lagwana sa phla ta kh ap ko sahi guidness milaa
ماشاء اللہ جی بہت خوب زبردست
سر آپ کو ایک ملین سبسکرائبر کے پڑوس میں پہنچنے پر دل سے ایڈوانس میں مبارکباد 🎉🎉🎉🎉🎉
Much informatic video with excellent presentations to understand. Your video solved the upcoming question. Stay blessed 🌹
بہت ہی عمدہ معلومات
بہت زبردست سر اپ بہت معلوماتی ویڈیو بناتے ہو اللہ تعالیٰ اپ کے رزق میں برکت عطا فرمائے سر اپ علم کے سمندر ہو اور ہم علم کے پیاسے ع سر اسانیاں بانٹ رہے ہو اللہ تعالیٰ اپ زندگی میں آسانیاں پیدا فرمائے
Zabardast....Allah paak aap ko rehmatain or barkatain atta fermaei Ameen
Excellent, well explained video. it solves the issue of many consumer's concerned. Thanks
Kya bat hy yrrrr, boht zabrdast video hy, boht information btai apne.
Thanks❤
Excellent video. You have great presentation skills.
Well done 👍✅
Good work.
Always first in providing best solutions in pakistan
Very nice great training video
ماشاءاللہ ڈیر خہ زبردست
اسلام علیکم جناب بہت اچھا کام کر رہے ہیں
Ma Sha Allah, highly professional presention , you deffinately deserve appreciation.
Stay Blessed 😊🌴
اللہ تعالی اپ کو بہت کامیابی عطا فرمائے
Very nice presentation and explanation Sir G
Aamir bahi is the most talented technation of pakistan
Assalam o Alaikum, Tomzn TOQ5-125/4 ATS and their variant models for both 2 pole and 4 pole are designed to work for AC current only. They are not designed for the DC. So you should not provide the DC current output from PV panels as an input to ATS terminals. Your design configuration may work for some time, but I think it will likely result in causing damage to the equipment at some later stage. The product details available online also depict that this product and its variants should NOT be used with PV panels and inverters. It is to be only used for AC input/output equipment/setup. Stay safe!
But it’s magnetic coil on both sources is getting a 220V AC current only it’s contacts are getting directly PV input which is DC. Is it still not safe?
@@AB-rz2kuATS is designed for Alternating current (AC) that is why the manufacturers have instructed to use it with AC power sources only in case of interruption of primary supply. Product data sheet also provide complete details of its usage. Do little research, things will be more clear to you as it is difficult to explain the working mechanism in a post. So, it should Never be used like this gentleman is using it. Stay safe!
@@ThePiPerspective-mg8bbI was wondering about the same thing and that's why exploring the comments section and came across your comment. What other options do we have for automatic switching of DC?
Awaiting for DC alternative sir
Bahat khoob, Zarardast ideas 👍
Amir bhai zindabaad. Always helpful 👍
Mashallah ye ats to bohat Kamal ka hai sir
Excellent presentation.
Very clear explanation. nice and informative.
bohat bohat thanks Bhai g ....useful video
Aamir bai you provide best information 😊😊😊😊😊
MashAllah sir very informative video sari bat clear ho gai 2 kw off grid key sath kam say ka betry kitny chay not for back up only to on the solar thanks
Very clear communication 😊
Nice and very informative video,
Very informative video thank you Sir.
You have explained it really well sir
Well done keep it up
Amir bhai very nice work,👌👌⚡⚡
ماشااللہ، اللہ پاک آپ جیسے لوگوں کو بہت کامیابی دے آپ ہمارے قوم کے ہیرو ہیں۔ جو کسی ہچکچاہٹ کے بغیر اور کسی لالچ کے بغیر لوگوں کو عمدہ انداز میں سمجھاتے ہیں۔
یو ٹیوب سے ڈالرز تو ملتے ہیں!
Very nice dear brother ❤️
ammir bhai Great ماشاءاللہ
very informative 👍
MashaAllah good work ❤
Bohttt zbrdst treen Sir...
God bless you and your family
best teacher sar ji thnk
Very informative video thank you sir
Mashallah sir ap bht genius hein mashallah
Very very useful informative vedio....
Excellent work
🎉🎉🎉🎉👋👋👋👋👋Thanks bhae aaj m aise he video dakh raha tha
Jazak Allah khair bhai jan......
Explain in good way
Bht achi information share Jo ka her solar walay share nhi karty hain...
Excellent explanation
True informative vedio keep it up
MShallah jnb zabrdast
Very informative
Great information❤❤
ماشاءاللہ، بہت اعلٰی،
Very good information video
Nice content 👍
JazakAllah Khair brother
Excellent Dear
Very informative, keep it up
Kamal ki vidio hai❤
Amir bhai this is an AC ATS, for low DC voltages it works, but in High DC voltages switching it possibly causing problems. Please use DC ATS.
ongrid inverter grid jaany pe foran operation band kr dta hy us doran jo switching hogi terminals pe us wqt koe current flow ni ho rhi hogi .. i think
Very valid point @AJElectric ... Hm ye b try kr skte ke hmari max voltage 250v DC se zyada na jaen.. Mtlb max 6 panels use kren..
Some delay is required between switching and solar solar current flow in to off grid inverter otherwise it is likely to produce high spark thus damaging ATS terminals, I suppose. Practical checking or experiment is necessary. Please give feedback if any one does it. Regards.
@@zaheerbabar5510any update Amir bhai
1.2kw 12v ka system hota hy uspe 48v waly panel lag sakty hn???
Thanks 👍😊 Salamat raheen
So informative vedio....
Nice work sir g ❤
MashahAllah zabardast
Very good information
Aslam o alikum Sar mein aap ka new fan hun
السلام و علیکم کیا حال ہے آپ کا سر میں کراچی سے ہوں آپ کی ہر ویڈیو دیکھتا ہوں بہترین طریقے سے آپ لوگوں کو سمجھاتے ہو اللّٰہ آپ کو آ پنے حفظ وامان میں رکھے میں گھر میں 8kw کا hibrid solar system lagwana cahta hn nitrox inverter k sat aur j n ntype panal ho mujhe is me kitana harcha aye ga aur ap krachi me system lagwate ho?
solar panel ab kafi sastay hogaye hain. abhi say panel khareedo. FBR nay dobara mehngay krnay ka bola hai.
You sure Abt inverex?Naam KY paisy service lazy btw 8kw inverex 450k 6kw 350k ip65,crown dekh lu sasta acha,n type 56/watt ,himo 6 better yr choice ,bus fronus nhi 2 clients ki iss week hi warranty claim 😢
@@rohaitastanoli3414PTA Ka solar panel k sath kya lena dena hy 😀
@@rednetworksolutions FBR likhna tha PTA likh dia
F
So nice vedio.......
JazakAllah, I was looking for this solution for a while, thank you for such detailed information.
Could you please share price of this ATS device, I have a question, if I opt for your solution will batteries be needed for off grid to work?
Great info. ❤👍👍
Amir Bhai mere pas 3.2 Veyron invirex Laga huwa Hai pehle Maine AAP se single to dual device Bhi le kar lagai Hai wo Masha Allah boht hi acha Kam kar rahi Hai lekin masla sirf ye Hai K( XP 230 Phoenix) battery lagi hui Hai lekin wo backup Nahin de rahi sirf 4 se 5 light lagi hui Hai lekin 1ghante me battery khatm ho jati Hai
Amir bhai is real human
Very well Explained
good vedio...
Thank you very much......
As per manufacturer, Only for city power and Generator, not for a PV system and inverter.
Exactly
Salam .good work
زبردست شاندار
❤❤❤ good information