Liebert MC condenser board reading in BAR?
After you replaced a motor you unit now reads in bar not psig. How to fix this.
Просмотров: 20

Видео

Liebert DS evacuation mode
Просмотров 1314 часов назад
How to use the unit to keep solenoid or eev open in order to pull a vacuum
Liebert unit name
Просмотров 5414 часов назад
How to change your unit name as it appears in the display
Liebert GCB ambient temp diff
Просмотров 2319 часов назад
The reasons why your getting gcb ambiant temp diff. When you have dual condensers if the ambient sensor is reading more the 10 degrees difference between the other unit you get this alarm and most likely you have a bad sensor in one of the units or a bad mc condenser fan board. Buy both sensors and a board save yourself a trip.
Econo pump enabled?
Просмотров 323 месяца назад
How to see if your Econo pump is enabled through the icom controller
Belt wear
Просмотров 1937 месяцев назад
Liebert challenger excessive belt wear correction.
Evacuate mode
Просмотров 122Год назад
How to engage solenoid or EEV through your display to pull a vacuum or recovery
Liebert EEV battery alarm
Просмотров 330Год назад
Liebert EEV battery alarm
Why is my unit in bar!? How to get to psi…..
Просмотров 46Год назад
Why is my unit in bar!? How to get to psi…..
Liebert challenger 3000 low pressure
Просмотров 614Год назад
Pressures looked good when gauges connected. However kept throwing low pressure alarm and locking compressor out. Hot gas solenoid partially stuck open making suction pressure appear good. Pulled dryer and was plugged 85%. Customer said tech was telling them they had a bad board.
VS/DS high pressure switch tip
Просмотров 67Год назад
VS/DS high pressure switch tip
What’s my software revision?
Просмотров 61Год назад
What’s my software revision?
Cleaning Liebert MC condenser
Просмотров 9332 года назад
Cleaning Liebert MC condenser
Liebert MC fan reverse clean
Просмотров 1952 года назад
Liebert MC fan reverse clean
Wellness Bar?
Просмотров 1282 года назад
Wellness Bar?
Is unity card for Liebert data mate
Просмотров 1613 года назад
Is unity card for Liebert data mate
Liebert Mini Mate 2 condensate pump wiring
Просмотров 5763 года назад
Liebert Mini Mate 2 condensate pump wiring
Liebert DSE EEV board issue
Просмотров 1,7 тыс.3 года назад
Liebert DSE EEV board issue
Mini mate 2 wiring (unit board)
Просмотров 2713 года назад
Mini mate 2 wiring (unit board)
2 condenser to 1 indoor set up
Просмотров 3993 года назад
2 condenser to 1 indoor set up
Mini mate 2 wiring (self contained)
Просмотров 7563 года назад
Mini mate 2 wiring (self contained)
Liebert MC Condenser Fan motor
Просмотров 1,9 тыс.4 года назад
Liebert MC Condenser Fan motor
Adding a float switch to your Liebert Mini Mate
Просмотров 4824 года назад
Adding a float switch to your Liebert Mini Mate
Liebert iCom 2 bms part 3
Просмотров 2594 года назад
Liebert iCom 2 bms part 3
Liebert iCom 2 bms part 2
Просмотров 3924 года назад
Liebert iCom 2 bms part 2
Wellness bar
Просмотров 134 года назад
Wellness bar
York Drive parameters
Просмотров 114 года назад
York Drive parameters
Mini mate 3 low voltage wiring
Просмотров 1154 года назад
Mini mate 3 low voltage wiring
Liebert power meters
Просмотров 844 года назад
Liebert power meters

Комментарии

  • @blu-birb
    @blu-birb 3 дня назад

    Boy, i tell you. Being a mechanic in this age is both a blessing and a curse. Id imagine it would only take another 15 years before any "quality" mechanic also holds a degree in software language.

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 3 дня назад

      @@blu-birb it’s become more electronics then anything I’m a refrigeration mechanic who was hired for y2k project and been with Liebert ever since

  • @pipedown7969
    @pipedown7969 7 дней назад

    Having this problem currently on one of my units. Just changed the super cap board but still have the battery bad error. Is there any setting I need to reset after replacing it?

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 6 дней назад

      @@pipedown7969 you need to let it charge then reset the counter

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 6 дней назад

      @@pipedown7969 I’ll try and make some more videos on this next week

    • @pipedown7969
      @pipedown7969 6 дней назад

      @@hvac-runauthorized7326 cool thanks for responding man I will give this a shot. I’m trying to get my company to send me to the Vertiv training in Ohio because these things are so intricate. Even with an HVAC background they have so many settings it can get hard to troubleshoot some stuff.

  • @pipedown7969
    @pipedown7969 7 дней назад

    Thanks for the content on these things, it’s pretty difficult to find any troubleshooting help on them. Was wondering if you ever experienced a “bad battery” error with the EEV board? I have one currently where the suction line thermistor is showing around 8degrees when i measure it’s actually 47 and the circuit won’t calculate any superheat. I replaced the thermistor which didn’t solve the issue, then the EEV board and the super cap board. Turned the unit on and still have the issue with the thermistor showing 8degrees and the EEV page is showing ”battery bad”. Do you know if there is some sort of setting I need to reset to clear this after replacing the boards?

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 6 дней назад

      @@pipedown7969 set the eev to manual at 38% and see what the pressure looks like

    • @pipedown7969
      @pipedown7969 6 дней назад

      @ I’ve got a tandem compressor circuit, should I just run it with one on and see what I get? It’s just weird that it’s showing a reading of 8degrees but when I take a measurement directly at the thermistor with a thermometer it’s showing 47

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 6 дней назад

      @ run both

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 6 дней назад

      If you run at that eev position you will see the real pressure. A lot of times the unit is undercharged or the gas is contaminated

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 6 дней назад

      If you have core dryers check your td

  • @JoshuaBurdette-b5n
    @JoshuaBurdette-b5n 24 дня назад

    One of our sales men just sold a contract to a data center in SC so we’re about to pick up a ton of Liebert units. He sent me the equipment list and there’s some Trane, Carrier, and Rheem but the vast majority are Liebert. Lots of DS, DCD, DCS, VS, and a couple MCL. Just trying to see what he’s getting us into…

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 7 дней назад

      @@JoshuaBurdette-b5n I have been working on these systems for over 30 yrs. Need any help let me know. I work for the reps office

  • @hakimeusma9119
    @hakimeusma9119 2 месяца назад

    How to deactivate humidefecateur

  • @peerod673
    @peerod673 3 месяца назад

    These are great videos

  • @azzeddineghazyl4306
    @azzeddineghazyl4306 9 месяцев назад

    Compresseur de protection thermique surcuit 1compresseur 1

  • @ZRock7771
    @ZRock7771 Год назад

    Nice! I had a leak on pressure switch cap tub last week. Lost about 40lbs of r22🙁

    • @treasuredtimescruising8265
      @treasuredtimescruising8265 Год назад

      This trick is only good on the ds/vs

    • @treasuredtimescruising8265
      @treasuredtimescruising8265 Год назад

      I’ve had a few of those leak and the tubes crack off

    • @ZRock7771
      @ZRock7771 Год назад

      ​@treasuredtimescruising8265 Right, the one I was working on was an older VH model. Unfortunately, I had to replace it with another manual reset high pressure switch that had a cap tube.

  • @oscarsosa6984
    @oscarsosa6984 Год назад

    👍👍

  • @MovingHeatLata666
    @MovingHeatLata666 Год назад

    Stand off ( board supports ). Pimp shit. Thanks.

  • @champa1169
    @champa1169 2 года назад

    What about the control box for Ethernet?

  • @thetman2301
    @thetman2301 2 года назад

    No offense but that manual was the worst one i ever read. They are so vague about everything. None of the wires are labeled or have numbers so on the vertiv split they for instance have two brown wires and you have to pick the right one. took forever to figure that out before it dawned on me. nice units bit they need to make things just a bit more installer and service friendly. Even just a simple label on the service panel would have been nice.

    • @treasuredtimescruising8265
      @treasuredtimescruising8265 2 года назад

      At the condenser yes I know if you look close there are numbers by the end for 1 and 4. The blue and white are not numbered either you have to look at the condenser wiring schematic to figure what number they are

  • @mherzcode4393
    @mherzcode4393 3 года назад

    Hi Sir, I have a question about MC board after the installing of the board if we need to configure the board

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 3 года назад

      If you are just replacing the board you will need to make sure it is set up properly for your system. Psi or bar Freon type etc plus it’s a good idea to run it through the motor set up process

  • @martyechols5780
    @martyechols5780 3 года назад

    I am doing 2 condensors connected a econophase and a crac unit.do you have any videos of wiring,charging and piping on those?

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 3 года назад

      Not at the moment. But be careful with the piping if it’s not correct they start up guy will make you change it. The next one I come too I’ll make a quick video

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 3 года назад

      Also keep in mind this is an anauthozed Chanel I do this to help people that may question some of this stuff. I work on these systems everyday.

    • @martyechols5780
      @martyechols5780 3 года назад

      Thank you.i followed the piping by the book.ive done a couple of 5 ton leiberts but this is the biggest one I've done.

    • @hvac-runauthorized7326
      @hvac-runauthorized7326 3 года назад

      They get very big. Use nitro when brazing and pull a deep vacc 250 micron or better and it will run forever