What is Safety Relay PILZ ? Easy Explained | pnoz X2 X3 X4

Поделиться
HTML-код
  • Опубликовано: 21 июл 2024
  • #safetyrelay #relay #safety #PILZ #pnoz
    how to wire a safety relay
    pilz pnoz X2 X3 X4
    Siemens TIA PORTAL Tutorials for Beginners
    • Siemens TIA PORTAL Tut...
    Learn Electrical and Electronics
    • Learn Electrical and E...
    SIMATIC MANAGER TRAINING VIDEOS
    • SIMATIC MANAGER TRAINI...
    00:00 what is safety relay ?
    00:14 working of safety relay
    02:16 wiring of safety relay
    03:00 example demonstration of the safety relay
  • НаукаНаука

Комментарии • 78

  • @octymocty132
    @octymocty132 3 года назад +1

    thats made me look 100% right in an disgruntled converstaion over pilz
    verry clear and easy to under stand for the aprentice
    only thing i would say is use orange cable for controll identification as yellow is a no no
    thank you

  • @Jatin____Sharma
    @Jatin____Sharma 3 года назад +2

    Awesome, today I learn about a new device😍

  • @judeclark142
    @judeclark142 3 года назад +1

    thank you so much i finally understand safty relays

  • @baskarchandrakasan995
    @baskarchandrakasan995 3 года назад

    Excellent teaching sir.

  • @The11noodle
    @The11noodle 2 года назад

    Brilliantly explained

  • @user-ho2gj3rw8s
    @user-ho2gj3rw8s Год назад

    Thanks, now it's clear for me.

  • @irwinjimenez
    @irwinjimenez Год назад

    Great job. Very useful video. Thank you.

  • @Bigmallone
    @Bigmallone 3 года назад

    great work it was very useful for me

  • @afrid-li8ke
    @afrid-li8ke 2 года назад

    Great and well explained

  • @chappagiridhar5109
    @chappagiridhar5109 3 года назад

    Nice explanation sir👍👍👍

  • @user-saber-yasser.
    @user-saber-yasser. Год назад

    thank you very much 🌹good explanation

  • @monroestrike4378
    @monroestrike4378 3 года назад +4

    Perfect. Simple and well explained!

  • @manjunathamanju6204
    @manjunathamanju6204 3 года назад

    Good explanation thank you so much

  • @syedhassanali9330
    @syedhassanali9330 Год назад

    Thank you very much sir very informative video

  • @maintenancegc6568
    @maintenancegc6568 2 года назад

    Clear Explanation.

  • @glennrodrigues7111
    @glennrodrigues7111 3 года назад

    Thank you sir well explained

  • @xubairahmed951
    @xubairahmed951 2 года назад

    amazing work

  • @showshocka3k
    @showshocka3k 2 года назад +1

    Love it! Controls!!

  • @pnswg01
    @pnswg01 Год назад +3

    In the schematic section, the wires goes to the wrong pins but the audio is true. Possibly because the software wouldn't allow you to draw the lines to the correct pins. Good explanation anyway.

  • @vasanthakumar8167
    @vasanthakumar8167 3 года назад

    Good explanation

  • @ismatsumarjan290
    @ismatsumarjan290 Год назад

    Thanks for your information

  • @hatemzaatra5894
    @hatemzaatra5894 3 года назад

    Great video

  • @cathleyamaesantos4557
    @cathleyamaesantos4557 3 года назад

    Nice one

  • @aminizza1450
    @aminizza1450 2 года назад

    Thank's very usefull

  • @kevin00861
    @kevin00861 Год назад +1

    Thank you Sir for spreading your knowldge

  • @pogssss5058
    @pogssss5058 8 месяцев назад

    Thanks for this sir,

  • @alfredaxax
    @alfredaxax 4 месяца назад

    nice lecture

  • @antoniomondragongonzalez1692
    @antoniomondragongonzalez1692 2 месяца назад

    Excelente

  • @shahbazarain9488
    @shahbazarain9488 3 года назад +1

    Amazing

  • @phanduyautomation3737
    @phanduyautomation3737 2 года назад

    perfect. good

  • @TheThippu
    @TheThippu 3 года назад

    Excellent i have learned new thing today,
    Is it same as Siemens Sirius safety relay with more chancels

  • @Jarito1903
    @Jarito1903 3 года назад +2

    Great video, thanks. Keep on the hard work

  • @athilaldurry5880
    @athilaldurry5880 3 года назад

    Many thanks

  • @cascadeanalog320
    @cascadeanalog320 3 года назад

    Thank you Sir

  • @sebutir_embun6703
    @sebutir_embun6703 3 года назад

    thanks bro

  • @marijngade5403
    @marijngade5403 3 года назад +4

    Would this setup not require 2 master relays in series to consider it full safe? This way the relay could get stuck open and the intire safety part is useless.

  • @mantunaik9798
    @mantunaik9798 Месяц назад

    How to take feedback from this safety relay to plc for alarm generations

  • @RAMSINGH-0
    @RAMSINGH-0 22 дня назад

    Thankyou ❤

  • @ethan073
    @ethan073 2 года назад

    THANK YOU

  • @azharbarmare6847
    @azharbarmare6847 11 месяцев назад

    Sir I had a question in my case relay is starting but after some time but it is continuously asking to reset and sometime reset button also dnt work...

  • @mikeadler434
    @mikeadler434 Год назад

    👍👍

  • @devpatel361
    @devpatel361 3 месяца назад

    Do I compulsorily have to use a Contactor at the end? If not, do i attach 13-14. 23-24 directly to the actuator ? Why use contactor, if we are using relay for the saftey ? Thank you for the video ! :))

  • @shanefrank3281
    @shanefrank3281 Год назад +1

    Great video! I have been having trouble understanding safety relays from the data sheets and this helps. But I was wondering if you had only wired the contactor to only 13-14 (and not series 13-14 and 23-24) would only the red button connected to S11-S12 turn off the contactor? So S11-S12 safety input only controls 13-14 and S21-S22 only controls 23-24. Is that correct?

    • @GhostHostMemories
      @GhostHostMemories Год назад

      no. 13/14 and 23/24 are mechanically linked, and not tied to a specific input

  • @johnrece6622
    @johnrece6622 3 года назад

    So this relay doesn't have a reset option? So you will have to turn off channel 1 and 2 to restart it?

  • @showshocka3k
    @showshocka3k 2 года назад +1

    How could one even attempt to give this simple tutorial thumbs down?

  • @balachanderbalachander6959
    @balachanderbalachander6959 3 года назад

    nice sir. add other company relays also. sick, schmuller.

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад +1

      Almost similar .... but must go through wiring diagram

  • @danghoangvinh9512
    @danghoangvinh9512 3 года назад +1

    Perfect. but i have a question. Why do you have to wiring both 2 NO 13-14 and 23-24 to contactor instead of only 1 (13-14 or 23-24 to Contactor) .Thanks you about this video!

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад +2

      You can use single contact also , just as an example I looped both auxiliaries . These contacts are also used to give signals to other safety relays ... means if you have seen safety relays working in loops

    • @danghoangvinh9512
      @danghoangvinh9512 3 года назад

      @@EASYPLCTRAINING thanks you!!

  • @asifislam7376
    @asifislam7376 2 года назад

    Neutral A2..you draw black wire in s12..channel 1 s21,s22..but where u have drawn red push button? 14 and s11..how!! One red push button should be in ch1 (s22,s22) and another one in ch2 (s11,s12) Am k right? Pardon..

  • @kencooley5589
    @kencooley5589 3 года назад +3

    I have a question. If one of the channels are not closed when the on pulse to the start channel is made, do you have to turn off both channels to attempt to start it again?
    So if channel 1 is false and channel 2 is true. Start signal is received. Must channel 2 be made false before another start signal can be made true?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад +2

      Yes exactly we have to reset both channels ..... but in some relays we jut have to reset only one faulty channel .... I think It depends on the model of the Safety relay

  • @arunrajendran674
    @arunrajendran674 3 года назад +1

    Super explanation... Explain pilz X3 relay also?

  • @jwerry58
    @jwerry58 3 года назад

    Can you provide what type the 1 green button and 2 red buttons? Momentary or Latch? Red N.C.? Green N.O.?

    • @MenAreBrave07
      @MenAreBrave07 Год назад

      He said it need pulse signal which means momentary.

  • @ThePengue
    @ThePengue Год назад

    Why to reset the safety relay you have to push both red button?

  • @Love__yu
    @Love__yu 3 года назад +4

    The contactor is 24 v?, how can connect a 220v contactor

    • @MenAreBrave07
      @MenAreBrave07 Год назад

      Using relay.

    • @irwinjimenez
      @irwinjimenez Год назад

      220v can go to COM terminal, NO contact goes to the contactor coil. Safety relay energizes the 24vdc ice cube relay to turn on the 220v.

  • @ajayrawat9525
    @ajayrawat9525 Год назад

    sir PNOZ S3 have same function or different?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  Год назад

      Same function, but I thing It have 4 channels to monitor the safety loops

  • @Idrathernot.
    @Idrathernot. 3 года назад

    Very beginner here; what does K1 and K2 mean?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  3 года назад

      k1 and k2 are the internal relays of the safety device

  • @goriparthisrikanth646
    @goriparthisrikanth646 3 года назад +1

    Sir video prepared in three phase motor runs in single phase supply okk

  • @foxxmulder7524
    @foxxmulder7524 2 года назад

    This is incorrect:Channel 1 and channel 2 is not wired using single pole normally closed contacts. You must use double pole force guided contacts. going to both channels simultaneously.

  • @mosesmoyes3301
    @mosesmoyes3301 3 года назад

    Piloje

  • @AndrewBambiliano
    @AndrewBambiliano 6 месяцев назад

    Sorry but your bad wiring diagram made me so confused

  • @user-jc1lq6tb6r
    @user-jc1lq6tb6r 2 года назад

    Can you provide what type the 1 green button and 2 red buttons? Momentary or Latch? Red N.C.? Green N.O.?

    • @EASYPLCTRAINING
      @EASYPLCTRAINING  2 года назад

      All momentary button .... green NO .... and red NC push buttons

    • @user-jc1lq6tb6r
      @user-jc1lq6tb6r 2 года назад

      @@EASYPLCTRAINING Thank You ^^