  • @smokeGR20
    @smokeGR20 5 лет назад +18

    When you do the churn test and you start the pump by dropping pressure through the sensing line, that is automatic start if the pump is on a 10 min. Timmer it will automatically shut off..so you should always time it..if no automatic shut off then you have to manually press the stop button. And it should be noted on the controller or pump inspection tag as to whether it has a 10 minute run timer...remember if you manually start pump via the start switch you have to manually stop..the auto stop usually only works when you automatically start. Also while the pump is running you should check the packing and bearing to ensure they are not getting hot..Ethier by touch or use a infrared heat gun

    • @ikennaogwogwo
      @ikennaogwogwo 4 года назад

      Very nice. Can you share you email to me, I'd like to ask you some questions.
      Here is mine : ogwogwoikenna@gmail.com
      Thank you.

    • @jonijimene
      @jonijimene 4 года назад +2

      In NYC, fire pumps can ONLY be stopped by manually

  • @ronfranz7578
    @ronfranz7578 7 месяцев назад +1

    When doing a churn test it is advisable that there are certified oil filled gauges on the sensing lines for both the jockey and fire pumps. These are a better read when dropping pressure than the reading in the controller. Depending also by the AHJ or insurance company some locations what you to close the valve on the discharge side when doing the test because catastrophic failure can happen. The jockey pump on the wall should not be part of a bid anymore because its the cheapest thing that you can install. It was hard to tell inn the video but I never saw a casing relief valve as you showed an air relief. Lastly some pump runs are just a supervisory/trouble. It is always been recommended to tie it in as an alarm. As an example the security guard silenced the trouble on the panel from a smoke detector being out. The pump started inn the pump house on a Friday night and there was smoke coming out of the pump house on a Monday morning. This is why an alarm is suggested.

  • @willlock3644
    @willlock3644 Год назад

    6:30
    No. You cannot do drain tests or whatever during the churn test.
    It’s in the name. Churn test.
    That pump needs to churn for 10 minutes. Again…churn.
    The casing relief valve is being exercised during the churn as well.

  • @jeffhail5778
    @jeffhail5778 5 лет назад +2

    Good training. Thanks.

  • @gilsgarageofficial
    @gilsgarageofficial 2 месяца назад

    In this video, which valve would you close to prevent catastrophic failure during a churn test? I know NFPA 25 requires it but company policy is to close it before conducting test for liability reasons.

  • @angelvaltierra6356
    @angelvaltierra6356 13 дней назад

    If hooked up to fdc. How do I know if fire pump stopped working.

  • @ryanyetman1335
    @ryanyetman1335 Год назад

    Can I shut the os&y to the header or shut the systems off on the butterfly to not pump the systems up ,

  • @joseaguilar584
    @joseaguilar584 5 лет назад +2

    Question: What about the pressure on the field? After the test should we open a drain valve to reduce pressure? Thank you!

    • @luizbueno4293
      @luizbueno4293 5 лет назад +2

      By the NFPA 20, the system pressure needs to be maintained close to the main fire pump churn discharge pressure to minimize pressure surges in the pipeline. So, you should not reduce the system pressure after the test. I hope it helps you!

  • @ikennaogwogwo
    @ikennaogwogwo 4 года назад +2

    Is it normal for water to leak through the suction side of the pump(This is close to the impeller).

    • @fidelbautista1561
      @fidelbautista1561 3 года назад +3

      if that is on the packing gland, yes its normal

  • @jj13jh
    @jj13jh Год назад

    Doing a pump run do i shut any valves off will pressure the whole system?

    • @stevengreen7484
      @stevengreen7484 Год назад +1

      Shut off the main discharge valve so as not to pressurize the whole fire system while performing your test

  • @willlock3644
    @willlock3644 Год назад

    I was really hoping that you would explain what the air release valve is four… Downstream of the pump. 🤦🏼‍♂️

  • @fredbarnich8145
    @fredbarnich8145 4 года назад

    Look like the casing relief valve you are showing look like more like a Air vent? I can be wrong, never mind the main relief valve is under the Air vent

  • @LiamKianAdventures
    @LiamKianAdventures 5 лет назад

    how do you replace the back up battery?

  • @ann0ynim0us
    @ann0ynim0us 4 года назад

    hi there, judging from the video, it looks like there's only a single pumpset for this fire protection service? do you guys practice the 1 duty 1 standby pumpset philosophy or is that not a requirement in NFPA?

    • @daninraleigh
      @daninraleigh 2 года назад +1

      You must be in a rich country to ask a question like that

    • @ann0ynim0us
      @ann0ynim0us 2 года назад

      @@daninraleigh naw, I'm in a country with different rules.

    • @mikefuentes2657
      @mikefuentes2657 2 года назад

      If it was the French alps and the systems were turned off yes

    • @ironmatic1
      @ironmatic1 Год назад

      @@ann0ynim0us Where??? There's a very small jockey pump but that's just to maintain normal pressure.

  • @rittachannelinturkiye_9328
    @rittachannelinturkiye_9328 2 года назад

    good luk my frind

  • @mustangfox302ho
    @mustangfox302ho 3 года назад

    Joslyn Clark controller, wonder if it's been replaced by now.

  • @willlock3644
    @willlock3644 Год назад

    Also…you cannot leave while the pump is running.

  • @sircampbell1249
    @sircampbell1249 2 года назад +1

    Hard to hear what your saying with pump on ...