How to Manually Operates Sparlon EEV
HTML-код
- Опубликовано: 27 авг 2024
- MCS-EXV-DRIVER
Operation Manual
Control of Bipolar Expansion Valves
FEATURES
• Modes of operation: Auto/Manual
• Closing of the valve on loss of power.
• Universal main supply operation (accepts 110 to 240 VAC ±10% (50/60 Hz); 44 VA or 24 VAC ±
10% (50/60 hZ)
• Supports a variety of expansion valves (SEE CHART ON FOLLOWING PAGES)
• POWER OK indicator LED
• FUSE BLOWN indicator LED
• If a power failure occurs it activates the MCS-EXV-DRIVER into power down mode AND CLOSES THE VALVE
Assalamu alaikum thx
Valekumassalam welcome
Sir isko direct kese open ya close kare agar humare pass ye controller nhi hai to...... mujhe microsmart zamil chiller mai open krke check krna h
Individual aap ko step-down transfermer laga ke check Krna padega
For auto command , what input is required for UED. Rather than 24vdc.
Both Control & EXV 24v command
Isko kase cheak karte h expation valve ko ki sahi h ya khrab
Isme 4wire rehte hi 2 wire ek winding baki 2doosre each winding ka resistance 75ohms ana chahiye tabi sahi hai ya phir kharab
+/- 5%no issue usse km ohms Aya to kharab mana jata hi
Or Kitana om ata 4 core m
2wire me 75 ohms
+/-5%