IMPROVE "F3" ERROR AC SPLIT DAIKIN INVERTER 1 PK
HTML-код
- Опубликовано: 12 дек 2024
- "F3" error on split ac with an inverter due to the error of the exhaust pipe temperature in the outdoor. (outdoor thermistor sensor) there are 3 types of discharge pipe sensor, reverse pipe sensor, outdoor temperature sensor, of the three types of sensors that read the outdoor working temperature and provide a signal to the inverter module.
"F3" error can be caused by lack of freon, outdoor thermistor sensor is damaged / misread temperature, electronic expansion valve is broken, body valve expansion is broken, pcb inverter module is error / damaged.
Here I use a capillary pipe to replace the damaged valve expansion. Sy, don't recommend friends to replace it with capillary pipes, but so far there are no problems for its use, the AC still wants to cool at low, med, high comp speed.
Hopefully this will be useful for all my friends and if there are feedback or comments please write below the comments column.
Don't forget to like and subscribe, friends - thanks.
Ilmu yg bermanfaat..semoga tmbh mju dah berkembang
Wah ini mah teknisi ac yg udah pro..ngerti cara kerja komponen ac..
Trimakasih mas bagi bagi ilmu TUHAN BERKATI AMIN
Trimakasih mas bagi bagi ilmu saya trimasih banyak
Bli sy subcribe.., semoga sewaktu2 bisa share ilmu utk problem yg belum pernah sy atasi. Thxs
Bli., boleh minta kontak WA untuk tanya2 soal AC. Terima kasih
Mantab kang,salam dingin dari indarung padang,terimakasih
Okee mass terimasih atass videonya,, saya bertahun2 benam AC daikin inverter..
Kedip2 jg luar dlm,, saya bongkar2 vcb nya..
Gak jg
Coba mas kabel2 kontrolnya mungkin ada yg gak kenceng, sy jg ngalamin pusing n ribet.
Trimakasih mas nambah sy ilmu sekali lagi trimakasih
mantab nas,nambah wawasan
Terimakasi mas sugeng
Made arsa..mau tanya, itu tadi motorized coil nya tidak dipasang ? Ndak pengaruh pada pcb outdoor..terimakasih
Salam dari bali...ikut belajar bli
Mantab made .......
Thnkyu sob... itu Ac brp PK ya, dan brp panjang kapiler nya..? 🙏👍
Trimakasih 👍👍
Kalw katup exspansi d ganti dengan pipa kapiler, sensor.y delepas aja apa di pasang gan.
Di lepas saja
sekedar masukan bli... gak baik bagi kompresor ac inverter klo ekspansinya diganti dengan kapiler. karena desain ac inverter harus menggunakan katup ekspansi dimana fungsi ekspansi adalah selain pengganti kapiler pada sirkulasi freon tetapi juga menjaga tekanan pada pipa tekan dan pipa hisap agar berada pada tekanan yang seharusnya. karena ac inverter kompresornya bekerja secara variabel. maksudnya ketika kompresor berjalan pada medium speed maka ekspansi akan menyempit dan apa bila kompresor berjalan pada high speed maka ekspansi akan melebar agar perbandingan tekanan tetap pada takaran yang semestinya. jika diganti dengan kapiler maka penyempitan pada sirkulasi freon akan terjadi secara flat (tetap). alhasil kompresor pada kecepatan rendah sirkulasi freon akan mendekati loss di kapilernya yang mengakibatkan tidak terjadinya pengabutan freon dikapilernya dan tidak mengahasilkan dingin dan jika diukur tekanan pada pipa tekan pada kompresor akan turun dan tekanan pada pipa hisap akan naik dari yang semestinya. sementara jika kompresor berjalan pada high speed atau kecepatan tinggi maka tekanan pada pipa tekan kompresor akan naik tinggi sedangkan pada pipa hisap akan rendah dari yang semestinya, walau pada kecepatan high speed ac akan menghasilkan dingin tetapi akan mengakibatkan kompresor dipaksa bekerja diatas batas kemampuan semestinya untuk memompa dikarnakan debit aliran freon yang diterima kapiler sudah di atas yang semestinya. ini akan membuat kompresor tidak akan bertahan lama.... saran untuk ac inverter jika ekspansinya rusak, alangkah baiknya diganti dengan ekspansi yang baru ketimbang diganti dengan kapiler... karena ac inverter tidak sama dengan ac non inverter.. atau jika suku cadang tidak ada di daerah sekitar tempat tinggal atau terlalu mahal maka opsi kedua lebih baik ac nya dijadikan non iverter dulu baru di ganti dengan kapiler...
Mantapss mAs sarannya masuk akan dan Kerennn
Kalau inverter daikin eror L5 solusinya apa bos ku?
ciri" katup exspansi rusak gimna ya bang ?
punya saya di ganti kapiler sudah 3 tahun ke skrg ga masalah ampere normal,mau ganti katup ekspansi waktu itu harganya selangit.
Ter merubah kompresor inverter 3phase menjadi manual, apa kah cukup coneksi S,C,R L,N, dan kapasitor?
Ok. Baik
Bos Sayaa Mau Tanya daikin split duct 2.5 Pk..Fan outdooor nyala tapi compresskr Ga manggil..walaau indoor nyalaah.di cek remot kode error ga terdetek
Bli... mau tanya donk..sy lg service ac.. Metk LG, inverter 1 PK.. problennya, saat dinyalakan pertama, putaran compressor low ( 2,4 amper..sesudah 2 menit hidup, puteran compressor naik dan ampelr menjadi 3.4 amper..sesudah 2 menit kwmudian, puteran naik lagi jadi 5-6 amper..hampir 3x yg teryera di nameplate (name plate 3.3 amp).. apa penyebabnya bli..trimkasih.salam dingin dari tangerang
Ok makasih
Kalah profesor jepang sm oi😄
Hahaha, maaf sy juga baru belajar, memang bisa di gunakan ganti dengan kapiler bisa normal kembali, munkin pd setingan low watt agak kurang dingin sedikit tp tidak terlalu signifikan, dr pengalaman sy pribadi.
Metaken pak de..kenapa tdk d vacum ya? R32 kan wajib vcum..apalagi itu invrter. Kmudian apa pipa kapiler bisa mengatur volume gas spt elektronik expnsi valp? Apa masih bisa hemat listrik klo sudah di modif spt nike?ampure masih belajar pak made.. 🙏
Divacum lebih baiknya...! Daya listrik masih hemat seperti biasa hanya saja jika seting low watt di remote dingin nya agak kurang sedikit seperti biasanya.
Utk area jakarta ada? Saya kena f3 juga
Saya lokasi di bali mas
After your modification sir.. In several week or months no have problem afyer you change expansion valve to capillary? Tnx for your response..
Sahabat thenik info .
AC emperter Daikin 1 pk
Tdk eror ..
Permasalahannya
Compresor .hidup dlm watu pling lama 5 menit ..setelah dlm 5 MIT mati lgi tu compresor .nunggu smpi 20 mnt .baru bisa hidup .treus mati lgi ....aph tu kerusakannxa
Blum bisa di simpulkan apa kerusakannya, karena kurang detail pengecekan posisi outdoor ac hidup ampere berapa? Tekanan freon berapa? Sudah dpt cleaning ac indoor dan outdoor?
Ada indikasi kode errornya apa? Trims
@@madearsa93 lo ac 1 1/5 ukran kapiler brp kh
Udah subcribe mas
Tquuuuu.. Brother !
Maaf bos, kl koder error' H6 ac Daikin inverter 1pk, kira2 ada kerusakan di komponen bagian mana bos..?🙏
Bisa modul pcb outdoor, dan bisa juga kompresor.
Error f3 .ekpansi valvenya di ganti kapilr. Untuk 2pk panjang berapa diameter berapa. Lalu selenoid nya dicabut atao di biarkan saja. Terimakasih.
2pk ukuran kapiler 80mm panjang 60cm , motorize expansi di cabut.
Thank you sir
You are welcome
Om mau nanya nih AC Daikin 1pk invater saat di nyalahin di lampu indor nya kedap kedip lalu berapa menit AC nya mati lalu dinyalahin lagi tetap gak lm mati lg tp pake kode pan ttp menyalah pas kita kasih kode cool AC nya mati lg dan kira² apaan nya yg jd travel om.?🙏 Mksh sblm nya om.🙏
cek kode error di remote
Kode error' nya U4 om itu kira² apanya ya om.? Trabel nya komponen indor apa Autdor nya om.??
bang kalo sudah ganti ke kapiler apakah future Low watt nya masih bisa berfungsi atau gk?
Gan..klau utk 1/2 pk menggunakan pipa kapiler ukuran brapa?
Cara kerja anda sudah saya kerjakan ac suda ok tapi aneh nya setelah 3 hari ac daikin inverter 1pk kumat lagi yaitu out door mati lagi freon r.410a nya kondisi ok ga bocor.
Error f3 adalah kesalahan kontrol suhu deteksi pd thermistor pipa discharge.
Bnyk faktor yg menyebabkan error f3 , bisa karena 3 sensor thermistor pd outdoor yg rusak, kebocoran freon, bisa juga pcb outdoor itu yg rusak. Perlu menganalisa kerusakan pd error f3 tidak semua kerusakan pd body expansi dan eletronic expansinya yg sudah di rubah dgn pipa kapiler.
Perhatikan panas suhu pd pipa discharge kompresor.
Perhatikan tekanan freon dan ampere pd saat start kompresor hingga running kompressor di posisi ngegas putaran tinggi, apakah ampere mengikuti kerja kompresor pada putaran bawah dan putaran atas tidak melebihi ampere yg di tentukan di putaran tinggi sampai 4,5 A, dan tekanan freon perhatikan pada jarum manifol dari putaran bawah kompresor stabil turun jarum manifol di 170-180psi hingga putaran tinggi di tekanan 140-150psi. Untuk ac freon r32 atau r410a
Mau tanya bli... Klo Daikin multi split bisa kah diganti kapiler jg? Soalnya ada 2 katup ekspansi/selenoid Valve.
Tidak bisa
Mslah AC sya sama persis dgn di video.
Mau tanya bang itu ampere nya idealnya 3,4-3,8 ya bang. Klo ampere nya dibawah nilai standard knpa ya bang?
Bli, tanya AC DAIKIN 1/2 PK SMILE INVERTER saya ketika di hidupkan 2mnt outdoor mati dan indoor tetap running setelahny LED power berkedip indikasi error' L5? Mohon bimbingannya?
Jika diganti pipa kapirel gitu kira"berbahaya ga,dan brpa lama bisa tahan
@@suyonouton9169 kalo masih 3 tahun mending manggil service resmi. Masih free
Klo untuk ac ukuran 1,5pk brapa ukuran pipa kapiler dan panjangnya bli? 🙏
Ampura kari pemula.
Biasanya di gunakan ukuran 0,70mm panjang 60cm
@@madearsa93 oke, suksma bli 🙏
Pak eror u4 inverter daikin yg kerusakannya bagian apa ya.trim ksh.
Udah nyoba ini kelemahannya ko multi split, ga bisa 1 indoor aja yg menyala, harus 2 2 nya menyala karena freon mengalir ke indoor yg lainya jg.
Setelah di ganti kapilernya.ekspansi elektronik nya di ke mana kan yah mas?
Saya lepas, kalo dia protek di pasang aja pinggirin taruhnya
Made Arsa...
Di lepas tanpa di jemper..? Atau di jemper..?
Maksudnya socket nya dilepas dari pcb ya bli, atau socket tetap terpasang di pcb
dingin sih mungkin bisa maksimal,tapi pemakain itu kuat berapa jam???
karena dikasus yg hampir sama seperti ac ini pemakain yg saya uju ini hanya bertahan kurang lebih 5-6 jam setelah itu ac kembali ngetri lagi.
mohon bimbingannya....
Cek termistor nya bisa jadi rusak.
Bli Made ada wa???
AC saya rusak Daikin inverter r32, outdornya nyala sebentar, belum dingin sudah mati.
081999021433 🙏
Pas AC Daikin Inverter 1PK saya krna F3. Terima service AC bli? Ada kontak yang bisa di hubungi?
Ada ..alamat nya di mana biar kita datangi .. khusus Medan ya .. 🙏
081 999 021 433 daerah denpasar - bali
Untuk info harganya bang . . .share dong harganya . . Dapet kasus sama untuk daikin inverter 1 pk model lama
Bang mau tanya nih..ac sya daikin inverter 1/2 pk..habis ganti pipa elbow indoor gara2 bocor..usia ac baru 1 stngah thun..setelah seleasai servis..dah berjalan hampir sebulan lebih..dingin mash kurang nyess..tekanan freon normal di cek kode eror remote ga gak ada yg eror..dinginyya kurang nyess..aer pembuangan embun ac normal bgt klo di suhu 25..tpi klo di turun ke 24 atau 23 sma aja gak ada perubahan dinginya..malah aer pembuangan embun mlah jadi agak lambat..padahal sebelumny di suhu 25 aja dah dingin banget sebelum penggantian pipa elbowny...kira2 apa ya solusiny..
Mhon penjelasany..
Bisa jadi pada saat perbaikan kebocoran, sirkulasi pipa ac kurang dibersihkan dan tidak di vacuum, kurangnya tekanan freon, sirkulasi pipa pendinginan terhambat sedikit buntu jadi pendingin tidak normal kurang dingin.
Secara prosdur di vacum..tpi yah gtu saya suruh cek kembali tekanan freon sma besar ampereny smpe skrg teknisiny blm dtng2 jg krmh..
Colek.. suhu made Dulu...
Bagaimana bisa tentu kan mana satu yg rosak..? Sensor? Eev atau pcb
apakah untuk ac samsung ,bisa juga di kasi seperti daikin
Kalo untuk ac 1.stngah pk pake pipa kapiler ukuran berapa
AC inverter lebih ribet perbaikinya.
Kalau bisa di ganti aja mas jangan di rubah rubah gitu GK baik.🙏😁
Kalo punya uang banyak gpp bang main ganti" aja tapi kalo masih bisa diakalin dengan nominal yg kecil kn gak salah juga
Untuk AC 1/5 PK pipa kalilernya ukuran berapa yah?
Bagaimana kita tau kalau expansi valevnya rusak. Dilihat dari fisik atau ada bunyi2 atau bagaimana pak.
Di cek lewat manifold tekanan freon dan ampere nya. Kompresor hidup seiring jalan putaran speed kompresor tekanan freon turun sampai habis dan ampere kompresor tinggi melebihi batas ampere dan overload.
Itu dinginya bisa maksimal ga bro?? TRIms infonya
Bisa, normal dingin seperti biasa.., tapi kalo disetting low watt di remote agak kurang dingin karena kompresor pada low speed di putaran bawah, fungsi katup expansi sudah tidak ada jadi loss konstan menggunakan kapiler, jika kompresor ngegas pd putaran atas dinginnya normal seperti biasa.
Tak boleh modified expenses valve begitu ,AC sudah hilang digital thermal energy control kalau Di ganti dengan capillaries. Warranty dari Daikin langsung void Di modified begitu .
Betul sekali otomatis system tidak akan bekerja dengan baik, di kemudian hari akan ada error tambahan
Bli Untuk pastikan body expansi rusak/bagus bgaimana caranya ya bli?
Klo expamsi valve rusak, out door nya mati hidup atau gmn pak? 🙏
Iya mati-hidup, compressor overheat
Mau tanya dr jember jawa timur ,van hidup yg jalur konpresor mati hidup sebentar itu kira2 dari apa ya mas....
Ac apa bos
@@madearsa93 ac daikin 2pk inverter
Cek kode error nya apa
@@madearsa93 code eror 6h
Mas made posisi daerah mana
Apa setiap kode error F3 seperti ini kerusakannya?.. mohon infonya, terima kasih
Penyebab error F3 bnyk indikasi bisa dari kebocoran freon, expansi valve rusak, elektronik expansi rusak, sensor thermis discahrge rusak, pcb outdoor rusak. Harus di cek dulu dan di pastikan di bagian mana yg rusak.
Halo mas, mau bertanya nih. Ac inverter daikin 1pk saya ada masalah di sensor magnet valve nya, kalau di pasang.. outdoornya mati, namun kalo di copot, outdoor nya nyala. Sudah beli magnet valve baru, namun tidak ada perubahan.. mau di copot tapi takut nantinya akan rusak merembet. Nah ada saran, pipa nya diganti menjadi kapiler.. apakah aman mas?
AC kalau pakai EEV, maka di pcb akan ada IC stepper untuk ngatur EEVnya. Itu juga harus anda ganti.
Persis sama spt AC Daikin 1 PK inverter saya.F3 error...kmd ..dibersihkan karat2 pd sensor2 itu....berhasil...kmd dingin...namun cuma bertahan 3 bulan...kmd F3 error lagi....kl begini apa solusinya Mas?
Ganti body expansi valve dan elektronic expansi nya kemungkinan rusak.
Pernah nangani error u2 bli AC seperti itu,jd klu di mode low watt ac jalan normal.tp klu di mode normal outdoornya mati hidup....
@@madearsa93 sudah pernah tp hasilnya sama cek teg input 220 normal,system kelistrikan jg normal pakai 4 kabel standart pemasangan daikin,kompressor jg tdk short. blm di cek bagian modulnya karena tdk punya skemanya.
@@madearsa93 oke terima kasih banyak bli made atas ilmunya,coba saya pelajari dl system kerjanya besok 🙏
Ardy Permadi
biasanya u2 modul pcb outdoornya bermasalah.. cek sekring, kapasitor, biasanya kapasitor dc nya itu bang
Pcb noise filter dan fan motor outdorr
@@masmincoolteknik8033 ganti kapasitor VDC di outdoor
Maaf maksudnya controlnya di lepas atau dibiarin ?
Dilepas
Mau nanya bli
Ac daikin inverter stengah pk waktu ac hidup
DinginNya hanya mau 15 menit
Stelah itu compresor tambah panas jarum manipol naik terus dan
Amper di compresor naik terus
Stelah itu dinginNya hilang
Kira "dimana rusakNya bli tolong solusinya bli,,🙏
Kapasitor DC nya yang kotak sudah coba ganti?
Itu kira kira bermasalahny apa ya om kalau termistor out sm exvansi dg error f3
Apakah ciri ciriny kompressor panas atau kompressor dingin
kalo error E6 biasanya kompresor macet apa modulnya bli
Kompresor macet
@@madearsa93 trimakasi bli..
AC punya saya sensor yg diluarnya putus kayaknya bagian dalamnya, soalnya kegencet tutup atas. Waktu AC abis di cuci tidak memperhatikan ternyata kabel sensornya kegencet.
Untuk menggantinya gimana ya? Atau bisakah kabelnya disambung? Saya belum coba liat daleman kabelnya seperti apa.
Pd outdoor ac sensor thermis putus ?
Iya, thermistor yg ada dibagian luar belakang AC sepertinya putus bagian dalam kabelnya, soalnya kegencet tutup atas casing outdoor. Itu kabel isinya tembaga atau apa ya? Kalo tembaga bisa disambung kan?
Ow, iya bisa di sambung kabel thermisnya.
Pak mau tanya apa expansi nya dicabut dari vcbnya atau dibiarin ?
Dicabut
Minta skema expasi valvenya om 6 kabel mana yg negati dan positifnya
@made arsa ada nomer
g bisa di hibungi mas.mau tanya ilmu nya dan sedikit curhat tentang permalahan ac inverter 1 pk.saya baru belajar dari 0
Bli made izin tanya , untuk kode error F6, Sudah pernah menqngabi kah?
Error F6 kontrol Tekanan Tinggi dalam Pendinginan
Metode
Pendeteksian
Kode Error
Kontrol tekanan tinggi (Operasi berhenti, penurunan frekuensi, dll) diaktifkan dalam operasi
pendinginan jika suhu dirasakan oleh Termistor Penukar Panas outdoor melebihi batas.
Kondisi Keputusan Error
Suhu dirasakan oleh Termistor Penukar Panas outdoor naik di atas 60 ° C.
Kesalahan menjadi jelas ketika suhu turun di bawah sekitar 55 ° C.
Dugaan Penyebab
Ruang instalasi tidak cukup besar.
Heat Exchanger outdoor Kotor
Fan motor outdoor rusak
Stop valve rusak
Katup ekspansi elektronik atau kumparan rusak
Termistor Penukar Panas outdoor
PCB Unit Outdoor rusak
Ngatasinnya gmn?
Bli,
Sepertinya kasusnya mirip dgn ac saya,
Indoor tidak mau dingin, ketika baru ON, lalu outdoornya harus di semprot air dulu baru mau dingin indoornya,
Apakah kasus demikian masalahnya di katup expansi jg?
Kode error di remot ac tidak terdeteksi
gmn cara kerja expansi valve itu?...trs posisi expansi valve di outdoor di mananya?
Ngatur besaran sirkulasi freon. Lihat di bagian belakang kompre kalau Daikin. Ada benda bulat dengan magnet di dalam. Itu EEVnya.
@@arapaimagold8088 kalau dibersihin atau diganti masih error berart pcbnya donk itu kan nyambung pcb yah,
Kalo kapiler daikin 0,5 pk berapa mili ukuranya ya gan
R32
Bagaimana ac 1pk sharp tidak dingin,kompresor mati hidup,kipas jalan.ac dibeli sudah ada 5thn.thanks sebelumnya,bagaimana memperbaikinya.
Bli ac invrter saya set d suhu 24 mau dingin, ketika suhu sudah tercapai kan dia kerja nya melambat, tapi setela itu gamau naik lagi kerja nyq. Kenapa ya? Kalo di mtiin kemudian nyalain kembali dia mau dngin lagi
yah suhu ruangan sudah tercapai kalau naik lagi kompresor hidup lagi inverter itu harusnya di ruang tidur tidak disarankan di tempat ruang kelurga bisa tapi harus rapat ruangan agar kompresor tidak gas terus
tekanan brp psi daikin bukan
Terlalu cepat vidio di tekanan freon bos.jd gsk jelas tekenannya.
sore gan,saya mau nanya nih,ac daikin inverter 1pk saya kalau dihidupin pada suhu 24'c 1jam kemudian suhu dinginnya ilang,tp kalau stel suhu 16'c bisa sampe 3jam baru hilang suhu dinginnya,tp indoor tetap hidup,kalau dimatiin pake remote n hidupin balik tetap gak mau dingin,tp kalau matiin kontak listrik dan pasang balik lalu dihidupin baru bisa dingin kembali.tp masalah tetap 1jam kemudian suhu dingin ilang lagi.kenapa ya kira2 n apa kerusakannya.tq
kelupaan,gak ada kode errornya,semua bagus stel sam00
Sudah dapat di cleaning indoor dan outdoor
Cek kode error pada saat ac error atau tidak dingin.
@@madearsa93
Ini juga sama dengan AC saya daikin inverter 15 menit setelah jalan dinginya hilang
Bli.yang mau saya tanyakan?
Itu expansi nya di copot.tidak pakei atau gimana yah🙏
Expansi di lepas di ganti dengan kapiler
Apa tandanya,dan bagaimana cara megetahui klo expansi palep xg rusak boss ku
Ampere naik, tekanan freon turun drastis
ijin bertanya master. jika ac matot apa bisa cek kode erornya?
kalau pakai ekpansi valve berarti gak pakai pipa capiler bos ?
pipa kapiler 0,54 ini diameter luar apa diameter dalam ya om?
Pak itu klo diganti expansionya persis aslinya apa tidak ada djual?
Ada yg jual di dealer nya harga lumayan
@@madearsa93 boleh info dealer mna kebetulan saya tinggal dijimbaran, daikin mana, kisaran brp harganya?
Service center daikin di buluh indah harga sekitar 800an komplit body exvansi sm elektronic expansi nya.
@@madearsa93 oke makasih infonya pak sukses selalu
@@lingkanpradana iya sm2, trimksih kmbli.
apakah gk pengaruh di modul nya kalo gk pakai electronic expansion
Gk ada masalah, aman
@@madearsa93 jadi apakah tidak muncul kode eror lagi setelah melepas komponen ter sebut.. dan di terapkan di ac non inverter misal panasonic dan merk ac lainya..
Kenapa gk di ganti baru ekspensinya aja bang
Iya benar ganti expansi lebih bagus, ini cara alternatif tanpa expansi memungkinkan ac masih bisa bekerja dengan baik.
Iya tapi lowat nya jadi hilang bang
Luar biasa,,,,,berkah dan bermanfaat,,saya punya problem,Ac Daikin Tipe RKD 25GVM4, 1 pk,outdoor nyala,kompresor nyala,tapi sebentar dingin,sebentar hilang,,dinginnya cuman 1 menit,kemudian dingin lagi,,hilang lagi,dan seterusnya,apa penyebabnya ya mas? terima kasih,,,,,
Kalau untuk 1/2 pk ukuran dan panjangnya berapa?
Saya punya ac daikin inverter eroor u4 belum saya pasang unit outdoor nya saya nyalain indoor nya saja saya cek pakai remot u4
Kira2 apanya ya om,apakah tes ac inverter harus pakai freeon juga supaya gak muncuk eroor u4
@@sbs_herry_prass6434 instalasi kabek indoor ke outdoor harus terkoneksi.
Tapi tanpa freoon bisa gak gan?/ selang flexibelnya tidak si pasang?
@@sbs_herry_prass6434 pipa ac tidak terpasang, modul akan protek indikasi error pada saat nyala
Baik sangat bermanfaat dan terimakasih
Apakah inverternya ttp berfungsi dgn normal?
Kenapa gak ekspansinya aja yg diperbaiki, kan bisa di bersihkan pake r11
Bli made, kalau kerusakan U0 apa yang harus dicek ya? Saya baca di web artinya tersumbat atau expansion valve. Mohon bisa dibantu spesifiknya bli
U0 = kekurangan freon, ada kebocoran freon.
@@madearsa93 freon sudah dicek nggak bocor bli, tekanan malah di 120. Ampere stabil, tekanan stabil, ac nggak dingin kadang suka mati dan lampu indikator kedip
Ac daikin inverter ? Cek kode error sudah tepat ? Ac sudah dapat di cleaning indoor dan outdoor ?
@@madearsa93 baru indoor bli, kode sudah bener berkali2 cek dapetnya U0. Nanti akan coba saya turunin outdoornya biar keliatan dan saya flush. Kemarin karena freon mau habis, jadinya tukang ac ngisi posisi tabung freon dibalik, takut gram2nya masuk bli. Apakah bisa dari situ penyebabnya bli? Karena setelah diisi freonnya selang 4 hari kejadian seperti ini bli
Freon jenis apa
👍 grande
Maaf
Kenapa ga di vacum ya
Bang klo panasonic inverter gak mau dingin knpa ya,,,freon 170 amper 1,4,,,itu ac nya 3/4 pk
Kode nya h 23
Saya service ac
Kata orang servicenya beli part dan harganya mahal
Nah saya di kasih saran modif, jadi dari mesin yg diluar itu ada kabel sama sklar bell..
Disuruh manual katanya biar ada freonnya, karna mesin yg diluar rusak otomatisnya jadi di buat manual gitu pake saklar
Nah apa ya namanya alat nya itu yg mahal katanya..?
Maksudnya ? Pcb outdoor modul inverter.
@@madearsa93 mungkin itu ya
@@madearsa93 tapi gak paham saya begituan
Jadi selama ini saya ya kalo gak dingin saya tekan sklar bell itu, langsung dingin.. Nanti gak dingin lagi saya tekan lagi dingin lagi
@@anaketv ini ac biasa bukan inverter ?
Munkin maksudnya yg rusak modul pcb indoor ac jadi gak bisa auto kontak power ke power ke outdoor, jadi di ganti manual hidupin dengan saklar.
ukuran kapiler dan panjang buat 2pk inverter brapa mas
Maaf bli kalo daikin inverter eror u2, bagian mana yg harus di perbaiki
Kata service center daikin harus ganti modul dgn harga 2,5 juta.
Konsumen saya gak mau, mohon bantuannya
@@rijalengineering5188 ganti kapasitor vdc outdoor
@@raihanraqqilla3186 mohon maaf bentuk nya seperti apa ya?
@@rijalengineering5188 bongkar pcb outdoor nya bawa ke tukang servis elektronik nati di tujukin rupa kapasitor VDC
Maaf minta solusi saya bnerin AC daikin sama persis cuma 1/2pk gk dingin sy cek freon 200psi amper 0.8 itu knapa y mas
@@madearsa93 tapi hidup posisinya mas sya sampai gonta ganti tang amper bingung gmn caranya mas
@@madearsa93 tang amper posisi di 1 di tespen nyala.saya cek kode eror pake remot gk ad eror sampai terakhir ke 00 bunyi panjang.saya isi freon 80 pipa tekan dingin sebentar tekanan manifol naik ke 200 psi amper trun ke 0.8 trus gk dingin sama sekali.
@@madearsa93 posisi sting remot di temperatur terendah 18 derajat.
@@madearsa93 stat awal amper 1.2 mas itu ac daikin baru 6 bulan masih baru sy blom buka elektronik valvenya.ok sy cba mas mksh saranya
@@madearsa93 freon R32 mas..star awal kipas outdor kencang lama amper trun 0.8 tekanan 200psi kipas melambat apa itu normal mas
Wah itu eev nya dikemanain?
Di lepas
@@madearsa93 ok2, ga detect eror lagi kah? kan sudah di copot.
Mas tlg impo nya kah AC Daikin inverter saya audor nya nyala sbntr trus mati..ap ya mas..
Cek kode error nya apa ?
L5 made
Bahkan pipa ac nya saya ganti baru 5m & sblm di isi freon nya saya vaccum dulu tapi yg saya bingung setelah 3 hari ac nya mati lagi 🤔
Ganti baru