HVAC Interview Questions and Answers | HVAC Job Interview Part-1 in Urdu/Hindi

Поделиться
HTML-код
  • Опубликовано: 24 ноя 2024

Комментарии • 136

  • @TanweerAhmed
    @TanweerAhmed  3 года назад +4

    Part-2 video link: ruclips.net/video/-lyDKsepLHg/видео.html

  • @jamal6626
    @jamal6626 4 месяца назад +1

    Sir, aap ka bahut shukriya itni informative videos banane ke liye. Interview me ek question pucha gaya mujhse ki "3 Way Valve ko return ke bajay supply line me laga sakte hai ya nahi".
    Please iska answer de aap.

    • @TanweerAhmed
      @TanweerAhmed  4 месяца назад +1

      DRV/Balancing/2-way/3-way vales is used for control chilled water flow as per design requirements which is installed return pipeline.
      It is normally installed on return because of the following reasons:
      1. ASHRAE Recommendations.
      2. The coil of the unit should be flooded in case the valve is closed.
      3. With a control valve on the return side, the water is at a higher pressure through the coil, reducing off gas, thereby lowering dissolved oxygen content. Lower dissolved oxygen extends equipment life by minimizing the air entrapment.
      4. In coil return line, after AHU/FCU install two way or three way valve, afterward install DRV due to above reasons.

  • @yaqoobgrandsonsengineering6817
    @yaqoobgrandsonsengineering6817 3 года назад +3

    Salute you our Hero Tanveer Ahmad

  • @Gulbarga_notebook
    @Gulbarga_notebook 3 года назад +1

    And also in 2-way valve system differential pressure transmission is required. In least points sense the proper temperature, and flow meter also required to modulate the flow which is interfaced with the bms system

  • @shahidansari9139
    @shahidansari9139 3 года назад +3

    Thanks for making useful video...Keep it up.May Allah increase you in knowledge.

  • @MustaqueAlam-o1z
    @MustaqueAlam-o1z 2 месяца назад

    Bhut khoob .bhut acchi trhaa se explain krte hain aap

  • @TradingHeights
    @TradingHeights 10 месяцев назад +1

    your videos are very helpful sir, im working as a modeller, please make videos on quality control topic on navisworks, how to detect clashes and report them to the designers who are working on revit software., naviswork software pe
    ek playlist bana dijiye

  • @mohammedkirmanisyed7960
    @mohammedkirmanisyed7960 3 года назад +2

    In my interview ,the question asked was.. why there are pressure gauges on pump suction and discharge and it's importance?

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      I will inform in next video, Insha'Allah

  • @shadabrehman709
    @shadabrehman709 2 года назад +1

    Very good information.

  • @imranalisoomro1844
    @imranalisoomro1844 Год назад +1

    walikum salam sir ,very great knowledge provide, and hard work. but i personal request you some videos make in sindhi language for HVAC filed.

    • @TanweerAhmed
      @TanweerAhmed  Год назад

      سنڌي ۾ ويڊيو ڏسڻ وارا گھٽ آھن

  • @mrhussainimamkhan1233
    @mrhussainimamkhan1233 3 года назад +2

    intresting video sir

  • @muqudiskhattak434
    @muqudiskhattak434 10 месяцев назад +1

    your videos are highly helpful... keep it up

  • @rohanrajhasim8332
    @rohanrajhasim8332 2 года назад +2

    Very good and thanks so much

  • @arshorts9868
    @arshorts9868 2 года назад +1

    Sir aaj kal Troubleshooting questions zyda pochaa jata h toh aap iss pe video bnaye naa....
    Mohammad Aqif Rizwan from India🇮🇳

  • @technicalviews6207
    @technicalviews6207 3 года назад +1

    Well done Sir ,kindly HVAC design thumb rules pa video bnaen buildings and industries ka lia .

  • @BebaMusic-bs2uy
    @BebaMusic-bs2uy 9 месяцев назад +1

    Tanweer Sab you excellent explain , Now i Become HVAC Engineer. hahaha

  • @ferozkhanpathan2310
    @ferozkhanpathan2310 Год назад +1

    Assalam alaikum sir,,,,,, thank your for your all videos for sharing knowledge.
    I have 1 doubt, that 2 way valve is used in return line for AHU or FCU . But for chilled water HI-Wall unit which is wall mounted like split AC why we connect 2 way valve in supply line?? Please answer

    • @TanweerAhmed
      @TanweerAhmed  Год назад

      You can install in supply line but if you install in return line the it will be more beneficial

  • @ak-lr5jc
    @ak-lr5jc Год назад +1

    Assalam O AllikUm Tanveer Sahib...we are building a 5 floor hospital with cooling load of approximately 500000 cfm for the whole building (average of 100,000 cfm per floor) We r having 4 chillers (3 functional + 1 standby) with a cooling load of 700 TR per chiller. We have 5 VFD based condensed water chillers each with a capacity of 1700 GPM at 185 feet head and 5 VFD based chilled water pumps with a capacity of 2100 gpm at 125 feet head. We have 2 cooling towers with 4 cells and 4000 gpm for each cooling tower. Moreover, we planning to make 2 out of 5 floors operational at this time only and energizing 1 chiller at this time.
    My question is that for only energizing 1 chiller (700 TR) only, will it be sufficient for cooling 2 out of 5 floors and if yes, gthen how many VFD based HVAC pumps (out of 5 each for chilled and condensed water pump) be required to run for this partial energization? Regards

    • @TanweerAhmed
      @TanweerAhmed  Год назад

      W.Salam,
      Contact with design consultant

  • @funtvwithamnaandhassan8674
    @funtvwithamnaandhassan8674 3 года назад +1

    excellent bro
    very nice explantation

  • @NirajKumar-mm3zz
    @NirajKumar-mm3zz 11 месяцев назад +1

    Sir, HVAC ka wire connection ka bare main bhi video bnaye

    • @TanweerAhmed
      @TanweerAhmed  11 месяцев назад

      What do you want to know about wire connections ⁉️

  • @Krishhhhhn
    @Krishhhhhn 2 года назад

    Very very informative video sir...
    Thanks a lot...
    And ed Mubarak

  • @hardikjoshi7224
    @hardikjoshi7224 Год назад +1

    Chiller ka purging system pe video banaye?

  • @gauravkumarbobde8987
    @gauravkumarbobde8987 Год назад +1

    Great.. Sir

  • @zahidkalim8649
    @zahidkalim8649 2 года назад +1

    Hvac system mein chilled water line aur condenser water line mein kaun kaun se valve lage hote hain sequence mein ?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      Watch my videos how to read HVAC drawing of chilled and condenser pipelines

  • @mddanishiqbal9719
    @mddanishiqbal9719 2 года назад +1

    Very good

  • @MkMkk-v4v
    @MkMkk-v4v Год назад +1

    Asslm alkm...tanveer saab....how to make budgeting and estimation of project

  • @indiantraveller194
    @indiantraveller194 2 года назад +1

    Mashaallah

  • @atif-aftab1atif330
    @atif-aftab1atif330 3 года назад +1

    Assalamualaikum sir please make a vedio on interview questions vedio in which we can interview the person having more than 5 years of experience

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      These videos will useful for junior as well as senior Engineers. Insha'Allah

  • @mdgufrankhan4785
    @mdgufrankhan4785 2 года назад +1

    Good 👍

  • @AmirAli-li2ly
    @AmirAli-li2ly 3 года назад +1

    Zabardast ada from Mehran eccentric reducer for air pocket missing

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      Thanks for highlighting. You are right

  • @shahbaznezami4291
    @shahbaznezami4291 Год назад +1

    Assalamualaikum,,, taveer sir, mujhe yeh jankari lena hai Aapse ki, mujhe HVAC field me career bnana hai to kiya mujhe AutoCAD janna zaruri hai, kiyoki mai Mechanical engineer hu, lekin mujhe autocad nahi Aata hai, to kiya mai pahile AutoCAD sikh lu uske baad HVAC-MEP kr ke job, please reply me

  • @HVACR786
    @HVACR786 11 месяцев назад +1

    ❤ wow sir thanks

  • @sarabjitsingh3258
    @sarabjitsingh3258 2 года назад +1

    HVAC maintainance department mein vacancy batana.
    HVAC engineer or supervisor k level ki.
    ...bcoz I have iti in refrigeration and air conditioning and diploma in mechenical both i have done.

  • @skshahbaz1969
    @skshahbaz1969 3 года назад +1

    Thank you so much sir

  • @mdsitarekhan575
    @mdsitarekhan575 2 года назад +1

    Sir hamko interview dena hai HVAC ke regarding to ap Aisa trick bataye ki interview clear ho gayee

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      All tricks are useless without knowledge. First improve your skill knowledge, specially basics HVAC then mention points in your CV where your grip is strong. Mostly interviewers ask questions from your CV.

  • @mohammedshowkatakbar8933
    @mohammedshowkatakbar8933 2 года назад

    assalamualikum. iam requesting to upload a video for Design of Hospital project.
    Regards.

  • @henryhawk7625
    @henryhawk7625 2 года назад +1

    Nice Video!
    I have a query? Why are control valves(3-way or 2-way) on the return side?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад +2

      They are normally installed on return because of the following reasons:
      1. ASHRAE Recommendations.
      2. The coil of the unit should be flooded in case the valve is closed.
      3. With a control valve on the return side, the water is at a higher pressure through the coil, reducing off gas, thereby lowering dissolved oxygen content. Lower dissolved oxygen extends equipment life by minimizing the air entrapment.
      4. In coil return line, after AHU/FCU install two way or three way valve, afterward install DRV due to above reasons.

    • @henryhawk7625
      @henryhawk7625 2 года назад +1

      @@TanweerAhmed Thank you for such a detailed reply!

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      Welcome

  • @Anil-Veeramangalam
    @Anil-Veeramangalam 3 года назад +1

    Thank you sir...

  • @mustaquekhan945
    @mustaquekhan945 3 года назад +1

    The same question asked in my interview but he asked me like that why we used 3-way valve in FAHU instead of 2-way if 2 way we used it's also workable

  • @gramathara4907
    @gramathara4907 4 месяца назад +1

    But where is constand speed and variable speed needed? I mean which kind of building

  • @MDArif-gb9bi
    @MDArif-gb9bi 3 года назад +1

    Why we used 2-way valve in return line of Ahu/Fcu
    Sir Can u describe this.

    • @TanweerAhmed
      @TanweerAhmed  3 года назад +1

      DRV/2-way/3-way vales is used for control chilled water flow as per design requirements which is installed return pipeline.
      It is normally installed on return because of the following reasons:
      1. ASHRAE Recommendations.
      2. The coil of the unit should be flooded in case the valve is closed.
      3. With a control valve on the return side, the water is at a higher pressure through the coil, reducing off gas, thereby lowering dissolved oxygen content. Lower dissolved oxygen extends equipment life by minimizing the air entrapment.
      4. In coil return line, after AHU/FCU install two way or three way valve, afterward install DRV due to above reasons.

    • @MDArif-gb9bi
      @MDArif-gb9bi 3 года назад +1

      @@TanweerAhmed thank you sir.
      Plz upload next part

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      Welcome... Insha'Allah soon will upload

  • @indiantraveller194
    @indiantraveller194 2 года назад +1

    Bhai jaan mughe bhi hvac ka channel banana hai category kaun sa select karein please bataiye 🙏😘👍🇮🇳

  • @jimmyjohn4070
    @jimmyjohn4070 3 года назад +1

    👍

  • @ShivPriyo
    @ShivPriyo 2 года назад

    Thanks you sir 🥀

  • @SadiqKhan-qo5yg
    @SadiqKhan-qo5yg 2 года назад +1

    Sir vrf py video banaye

  • @safdarchuhan5705
    @safdarchuhan5705 2 года назад +1

    hvac legends or symbol in detail btayen plz

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      My videos are available on legends and symbols

  • @bimstrategy7560
    @bimstrategy7560 2 года назад +1

    Thanks

  • @jahirkhan8581
    @jahirkhan8581 6 месяцев назад

    sir HVAC / MECHANICAL SUPERVISOR KE KOI VIDEO SHARE KARE

  • @aliasghar7420
    @aliasghar7420 3 года назад +1

    Fire pump ka flow test kaise karte hai pls bataiye

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      Fire pump flow measure through flow meter installed in pump room. Some my videos are available and further will prepare

  • @motivationalmsp9681
    @motivationalmsp9681 2 года назад +1

    HVAC vs MEP pe ek video banaye

  • @asemtantawy5779
    @asemtantawy5779 2 года назад +1

    Could you put translation in English and thank you sir for your efforts

  • @Gulbarga_notebook
    @Gulbarga_notebook 3 года назад +1

    You have not showed eccentric reducer in the suction line , this is most important to provide eccentric reducer

    • @TanweerAhmed
      @TanweerAhmed  3 года назад +1

      Thanks for highlighting and sharing your positive response

    • @mohammedkirmanisyed7960
      @mohammedkirmanisyed7960 3 года назад

      In my interview also asked eccentric reducer on suction of pump and flat side to or bottom?

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      There are different conditions. Insha'Allah will prepare video on this topic

  • @funtvwithamnaandhassan8674
    @funtvwithamnaandhassan8674 3 года назад +1

    how we set the percentage in mixing valve

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      It is built-in in valves. Actually there are three types:
      1. On/Off valve as per temperature demand
      2. Proportional valve which automatically % open open or close as per demand i.e. may be 10%, 15%, 20%, 25%.....100%
      3. Percentage valve which open and close fixed %wise such like 0%, 50% & 100%

  • @MrShadab7
    @MrShadab7 2 года назад

    what is double regulating valve?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      Watch my video on Double Regulating Valve

  • @abdulkarim9807
    @abdulkarim9807 2 года назад

    Assalamualaikum sir

    • @abdulkarim9807
      @abdulkarim9807 2 года назад

      Sar compensation chain ka kya use Hota Hai

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      W.salam,
      Where is installed compensation chain?

  • @mathanraja43
    @mathanraja43 5 месяцев назад +1

    Hello sir, please translate in English

  • @s.kranjan2731
    @s.kranjan2731 Год назад +1

    Hi

  • @hardikjoshi7224
    @hardikjoshi7224 Год назад

    Plasr

  • @rajinfotech4020
    @rajinfotech4020 Год назад +1

    Tanweer Bhai aap APNA Whatsapp number send kar sakte hain...

    • @TanweerAhmed
      @TanweerAhmed  Год назад

      You can ask here, I will must reply or joint my Telegram group "HVAC|MEP Engineering"